TRAILBLAZER™ Air-Cooled Scroll Chiller

Report 12 Downloads 20 Views
TRAILBLAZER™ Air-Cooled Scroll Chiller Job Information Job Name Date Submitted By Software Version Unit Tag

Technical Data Sheet Milligan College 5/11/2015 Brett Harris 05.40 140 Ton Air Cooled Chiller

Unit Overview Model Number

Capacity

IPLV

Voltage

AGZ140E

140.2

15.7

460 / 60 / 3

ton

EER

Unit Starter Type Across the Line

ASHRAE 90.1 '07, '10

LEED EA Credit 4 Pass

Unit Unit Type

Platform

Air-Cooled Scroll Compressor Chiller

Packaged

Head Pressure

Unit Revision

00 Tubing

VFD w/Line Reactors & Control Box Heaters [First Fans / Circuit] Replaceable Filter Dryer with Discharge & Liquid Valves, no HGBP Unit Controls

Display

Electronic Expansion Valve

On Controller only

Refrigerant Type

Refrigerant Weight

R410a

152 lb (per unit) Pump Controls

Dual Evaporator Pumps - Dual Control Output Approval

ETL/cETL, AHRI & ASHRAE 90.1 Evaporator Connection Hand: Connection Size: Insulation:

Universal Connection - Facing out back 4.00 in Single Layer Insulation to Suction at each Compressor

Entering Fluid Temperature

Leaving Fluid Temperature

Fluid Type

Fluid Flow

Fluid Flow Min / Max

Pressure Drop

55.0 °F

45.0 °F

Water

336.4 gpm

201.5/ 537.2 gpm

10.8 ft H₂O

Fouling Factor

0.00010

°F.ft².h/Btu

Condenser Coil Fins: Guards:

MicroChannel Condenser Coil Louvers & Base Frame Wire Grilles

Design Ambient Air Temperature

Altitude

Fan Diameter

Fan Motor Horsepower

Fan Speed

Minimum Design Ambient Temperature

Unit Airflow

95.0 °F

1526 ft

30.0 in

2.0 hp

1140 RPM

0.0 °F

112900 CFM

Page 1 of 3

www.DaikinApplied.com

TRAILBLAZER™ Air-Cooled Scroll Chiller Unit Performance Design Capacity

Input Power

Efficiency

IPLV

140.2 ton

159.0 kW

10.6 EER

15.7 EER

Performance Points rated at AHRI Ambient Relief Point #

% Load

Unit Capacity ton

1 2 3 4

100.0 75.0 50.0 25.0

140.2 105.1 70.1 35.0

Input Power kW

Efficiency EER

Fluid Flow gpm

159.0 92.6 49.7 22.9

10.6 13.6 16.9 18.4

336.4 336.4 336.4 336.4

Evaporator Condenser Pressure Entering Leaving Ambient Altitude Drop Fluid Fluid Air ft ft H₂O Temperature Temperature Temperature °F °F °F

10.8 10.8 10.8 10.8

55.0 52.5 50.0 47.5

45.0 45.0 45.0 45.0

95.0 80.0 65.0 55.0

1,526 1,526 1,526 1,526

Sound (without insulation) Sound Pressure (at 30 feet) 63 Hz dB

125 Hz dB

250 Hz dB

500 Hz dB

1 kHz dB

2 kHz dB

4 kHz dB

8 kHz dB

Overall dBA

68

69

69

65

61

60

61

56

69

63 Hz dB

125 Hz dB

250 Hz dB

500 Hz dB

1 kHz dB

2 kHz dB

4 kHz dB

8 kHz dB

Overall dBA

95

98

93

94

93

87

86

85

97

Sound Power

Octave band is non ‘A’ weighted and overall readings are 'A' weighted. Sound data rated in accordance with AHRI Standard-370.

Physical Unit Length**

Height

Width**

Shipping Weight*

Operating Weight*

238 in

99 in

88 in

7055 lb

7174 lb

*Shipping and Operating Weights include the below Option weights only and do not include the weights of any Accessories. Contact Chiller Applications for additional information. Option Weights Louvers: Total:

500 lb 500 lb

Page 2 of 3

www.DaikinApplied.com

TRAILBLAZER™ Air-Cooled Scroll Chiller Electrical Unit Electrical Data Voltage

Starter Type

Fan Motor Quantity

LRA Fan Motor (each)

FLA Fan Motors (each)

460 / 60 / 3

Across the Line

10

18 A

3.6 A

Power Connection Type:

Single Point Disconnect Switch with Circuit Protection Single Point Power Connection

MCA: Fuse Size (recommended): Fuse Size (maximum): Connector Wire Range:

309.3 A 350 A 350 A (2) 3/0-500 Compressor Electrical Data

Compressor Type

Compressor Quantity

Starter Type

Scroll

4

Across the Line

1

Circuit #: Compressor #: RLA: Inrush Current:

2

1

3

2

4

54.5 A 310 A

73 A 408 A

54.5 A 310 A

73 A 408 A

Note: Power wiring connections to the chiller may be done with either copper or aluminum wiring. Wire should be sized per NEC and/or local codes. Wire sizing and wire count must fit in the power connection lug sizing listed in latest installation manual. Please contact your local sales office for more information.

Options Basic Unit Control Box Ambient:

High Ambient with Exhaust Fans (125ºF maximum) Control

Communication:

BACnet MS/TP Electrical

Water Flow Indicator:

With Factory Installed Strainer & Flow Indication (Thermal Dispersion)

Warranty Unit Startup Standard Warranty: First Year Labor Warranty: Extended Unit Warranty:

Domestic 1st Year Entire Unit Parts & Labor Parts Only Entire Unit; Extended 4 years parts only

AHRI Certification Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org

Page 3 of 3

www.DaikinApplied.com

00

AGZ-E Guards: Condenser Coil Louvers, Base Wire Grilles

Diagram Notes Diagram simulates wrap, grille and louver options as selected only. Refrigeration components may vary depending on selected options.

Product Drawing

Product: Air-Cooled Scroll Chiller Model: AGZ140-180E

Unit Tag: 140 Ton Air Cooled Chiller

Sales Office: Hoffman & Hoffman, Inc. Sales Engineer: Brett Harris

May 11, 2015

Scale: N/A

Project Name: Milligan College Ver/Rev:

Sheet: 1 of 1

Tolerance: N/A

Dwg Units: N/A

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 05.40

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

0A

AGZ140E Packaged (Microchannel Condenser) Unit Dimensions Unit Weight Data Units

Weight

Lifting Weight

Mounting Weight

Shipping

Operating

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

lb

6555

6674

1862

1868

1410

1415

1411

1416

1070

1074

850

853

kg

2973

3027

845

847

640

642

640

642

485

487

386

387

Unit and Center of Gravity Dimensions Center of Gravity

Units

A (No Strainer)

B (With Strainer)

Connection Size (Victaulic)

X

Y

Z

in

122.1

67.5

4.0

44.1

42.6

83.3

mm

3102

1715

102

1120

1083

2117

NOTE A water strainer must be installed at the inlet of the evaporator to protect it from damage. Please refer to the IOM for additional details.

Product Drawing

Product: Air-Cooled Scroll Chiller Model: AGZ140E

Unit Tag: 140 Ton Air Cooled Chiller

Sales Office: Hoffman & Hoffman, Inc. Sales Engineer: Brett Harris

May 11, 2015

Scale: NTS

Project Name: Milligan College Ver/Rev:

Sheet: 1 of 1

Tolerance: +/- 1.0"

Dwg Units: in [mm]

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 05.40

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

AGZ030-240E Single-Point Connection Field Wiring Diagram

Field Wiring Diagram

Product: Air-Cooled Scroll Model: AGZ030-240E Single-Point Sales Engineer: Brett Harris

0B

Unit Tag: 140 Ton Air Cooled Chiller Project Name: Milligan College

Sales Office: Hoffman & Hoffman, Inc. May 11, 2015

Ver/Rev:

Sheet 1 of 1

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 05.40 Scale: N/A Tolerance: N/A Dwg Units: N/A

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.