Type KOR-11 Outdoor current transformer

Report 10 Downloads 698 Views
Instrument transformers

Type KOR-11 Outdoor current transformer

Product features −− 15 kV outdoor, 110 kV BIL −− 60 Hertz −− Primary amperes: 5 - 1200 −− Electrical clearances: Strike: 10.75" (273 mm) Creep: 20.0" (508 mm) Application KOR-11 current transformers operate with a high degree of accuracy on either metering or relaying circuits. The single primary bushing construction makes them particularly suited to applications on overhead lines with drop leads. Double ratio designs are available by means of a secondary tapped winding. Construction features Primary and secondary windings are assembled around a toroidal core and attached to a support frame. For insulation and protection, the assembly is vacuum cast in polyurethane. Terminals Primary terminals are conveniently located at the top of the high voltage bushing electro-tin plated copper. Clamp-type secondary terminals accommodate #14 to #1 wire. Terminal screws are slotted-head type. Junction box The junction box has a 1" diameter conduit entrance from three directions and is removable for simplified changeout. A ground terminal inside the box is conveniently located for grounding the transformer, or it may be grounded externally by the grounding lug located on the baseplate. Baseplate The base is constructed of corrosion-resistant aluminum and is secured to the encapsulated base support. Mounting The KOR-11 can be mounted in upright, cantilever, or upside-down positions. Stress relief devices should be used to support cable connections.

Test reports Test reports are stored electronically and can be e-mailed in various formats at the time of shipment. Standards This unit can be tested to all applicable IEEE, CSA, or IEC standards as requested. Optional mounting accessories − − Vertical mounting with mounting brackets & back-up plates: Mounting bracket 463C035G02 Back-up plate 28D2876G01 − − Vertical mounting with mounting brackets and hangers: Mounting bracket 463C035G02 Hangers 261A233G01 − − Vertical mounting with channel brackets for tandem mounting of voltage and current transformers: Channel bracket 332B955G02 − − Horizontal mounting with hangers: Hangers 261A233G01

Primary amp rating

Rating factor @ 30°C

Metering accuracy

Relaying accuracy

Thermal rating (x normal, 1 sec)

Mechanical rating

Style number

5

1.5

0.3B-1.8

T200

100

150

7524A12G01

10

1.5

0.3B-1.8

T200

100

150

7524A12G02

15

1.5

0.3B-1.8

T200

100

150

7524A12G03

20

1.5

0.3B-1.8

T200

100

150

7524A12G04

25

1.5

0.3B-1.8

T200

100

150

7524A12G05

30

1.5

0.3B-1.8

T200

100

150

7524A12G06

40

1.5

0.3B-1.8

T200

100

150

7524A12G07

50

1.5

0.3B-1.8

T200

100

150

7524A12G08

75

1.5

0.3B-1.8

T200

100

150

7524A12G09

100

1.5

0.3B-1.8

T200

100

150

7524A12G10

150

1.5

0.3B-1.8

T200

100

150

7524A12G11

200

1.5

0.3B-1.8

T200

100

150

7524A12G12

5/10

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G01

10/20

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G02

20/40

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G03

25/50

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G04

50/100

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G05

75/150

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G06

100/200

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G07

150/300

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G08

200/400

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G09

300/600

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G10

400/800

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G11

600/1200

2.0/1.5

0.3B-0.9/0.3B-1.8

T90/T200

100/200

300/150

7524A13G12

For 50 Hz styles, contact the factory.

Unit dimensions For more information please contact:

5.00 [127]

.438 [11] x .875 [22] SLOTS 4-TOTAL 1" [25] KNOCKOUT IN BOTTOM OF JUNCTION BOX

5.00 [127]

10.88 [276]

12.79 [325] 4.63 [118] 8.63 [219] 4.19 [106]

5.46 [139]

.44 [11] 8.00 [203]

8.75 [222]

5.81 [148] 1.00 [25]

A

15.75 [400] 15.06 [383]

TRANSFORMER RATING DECAL BOTH SIDES

GROUND LUG WITH HOLE FOR .375 [10] BOLT

NAMEPLATE

2.88 [73] 4.44 [113]

1.38 [35]

B

1.38 [35]

3.25 [83]

.50 [13]

1.00 [25]

.562 [14] x 1.31 [33] SLOT 2-TOTAL

Ø.562 [14] 2-TOTAL

.75 [19]

H1

PRIMARY POLARITY MARKER

CLAMP TYPE SECONDARY TERMINALS FOR #14 TO #1 WIRE. SECONDARY TERMINALS ARE SHIPPED SHORT CIRCUITED.

SECONDARY POLARITY MARKER X1

1.19 [30] 1" STD. PIPE TAP BOTH SIDES

.19 [5]

3.25 [83]

Note:

Bar dimensions Primary ampere rating

A

B

www.abb.com/mediumvoltage

X2

6.50 [165]

1.38 [35]

ABB Inc. Medium Voltage Distribution Components 3022 NC 43 North Pinetops, NC 27864 USA Phone: +1 252 827 3212 Fax: +1 252 827 4286

Weight

(in)

(mm)

(in)

(mm)

(lb)

(kg)

5 - 150

.25

6

1.5

38

70

32

200 - 800

.375

10

2.0

51

73

33

The information contained in this document is for general information purposes only. While ABB strives to keep the information up to date and correct, it makes no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability, or availability with respect to the information, products, services, or related graphics contained in the document for any purpose. Any reliance placed on such information is therefore strictly at your own risk. ABB reserves the right to discontinue any product or service at any time.

Copyright 2014 ABB. All rights reserved.

1VAP429224-DB June 2014 Rev. A (replaces 42-922)

Selection guide