NEMA Type 4 Models: Maintains UL/cUL Type 4 when properly installed on a UL/cUL Type 4 enclosure.
UL508 Listed; Type 4; File No. E187045 NEMA Type 4X Models: Maintains UL/cUL Type 4X when properly installed on a UL/cUL Type 4X enclosure.
FINISH
Brushed satin aluminum or stainless steel
ACCESSORIES
(for the enclosure) Can be installed on all enclosure product families. Separate accessories include an in-line oil filter.
Compressed Air In (70 F/21 C)
UL508 Listed; Type 4X; File No. E187045 NEMA Type 12 Models: Maintains UL/cUL Type 12 when properly installed on a UL/cUL Type 12 enclosure.
UL508 Listed; Type 12; File No. E187045
Vortex Tube
Control Valve
Cold Air Outlet
Hot Air Outlet Vortex Generation Chamber
APPLICATION
Powered by compressed air, Vortex Cooling Systems generate chilled air to cool small enclosures without refrigerants or moving parts. These systems are exceptionally reliable and low maintenance, even in the harshest and dirtiest environments.
Vortex Tube Air Flow Schematic
FEATURES • • • •
1
Five-micron airline filter, 115 V solenoid T hermostat Ducting kit Cooling capacities to 2500 BTU/Hr. (733 W)
Cooling
SUBJECT TO CHANGE WITHOUT NOTICE
EQUIPMENT PROTECTION SOLUTIONS Spec-00302 H
Sealed Enclosure Cooling Vortex Coolers
Performance Data VC Series NEMA Type 12 CATALOG NUMBERS Aluminum COOLING PERFORMANCE Cooling Capacity (BTU/Hr.) Cooling Capacity (Watts) Compressed Air Consumption (SCFM) Compressed Air Consumption (L3/M) SOUND LEVEL Noise Level (dB) ENCLOSURE PROTECTION UL Type ELECTRICAL DATA Rated Voltage Frequency (Hz) UNIT DIMENSIONS Weight (lb./kg)
VC0416012
VC0916012
VC1516012
VC2516012
400 117 8 227
900 264 15 425
1500 440 25 708
2500 733 35 991
69
80
83
90
Type 12 115 50/60
115 50/60
115 50/60
115 50/60
5/2.27
6/2.72
6/2.72
6/2.72
Performance Data VC Series NEMA Type 4, 4X CATALOG NUMBERS Aluminum Stainless Steel COOLING PERFORMANCE Cooling Capacity (BTU/Hr.) Cooling Capacity (Watts) Compressed Air Consumption (SCFM) Compressed Air Consumption (L3/M) SOUND LEVEL Noise Level (dB) ENCLOSURE PROTECTION UL Type ELECTRICAL DATA Rated Voltage Frequency (Hz) UNIT DIMENSIONS Weight (lb./kg)
VC0916004 VC091604X
VC1716004 VC171604X
VC2516004 VC251604X
900 264 15 425
1700 498 25 708
2500 733 35 991
83
86
90
Type 4, 4X 115 50/60
115 50/60
115 50/60
6/2.72
6/2.72
6/2.72
Vortex Cooling System Accessories CATALOG NUMBERS PERFORMANCE Description Use with VCool Model Capacity