Vortex Coolers

Report 5 Downloads 356 Views
Sealed Enclosure Cooling Vortex Coolers Cooling Sealed Enclosure Cooling Vortex Coolers

Spec-00302 H63.422.2211 7 763.576.3200

Vortex Coolers Indoor/Outdoor

INDUSTRY STANDARDS

NEMA Type 4 Models: Maintains UL/cUL Type 4 when properly installed on a UL/cUL Type 4 enclosure.

UL508 Listed; Type 4; File No. E187045 NEMA Type 4X Models: Maintains UL/cUL Type 4X when properly installed on a UL/cUL Type 4X enclosure.

FINISH

Brushed satin aluminum or stainless steel

ACCESSORIES

(for the enclosure) Can be installed on all enclosure product families. Separate accessories include an in-line oil filter.

Compressed Air In (70 F/21 C)

UL508 Listed; Type 4X; File No. E187045 NEMA Type 12 Models: Maintains UL/cUL Type 12 when properly installed on a UL/cUL Type 12 enclosure.

UL508 Listed; Type 12; File No. E187045

Vortex Tube

Control Valve

Cold Air Outlet

Hot Air Outlet Vortex Generation Chamber

APPLICATION

Powered by compressed air, Vortex Cooling Systems generate chilled air to cool small enclosures without refrigerants or moving parts. These systems are exceptionally reliable and low maintenance, even in the harshest and dirtiest environments.

Vortex Tube Air Flow Schematic

FEATURES • • • •

1

Five-micron airline filter, 115 V solenoid T hermostat Ducting kit Cooling capacities to 2500 BTU/Hr. (733 W)

Cooling

SUBJECT TO CHANGE WITHOUT NOTICE

EQUIPMENT PROTECTION SOLUTIONS Spec-00302 H

Sealed Enclosure Cooling Vortex Coolers

Performance Data  VC Series NEMA Type 12 CATALOG NUMBERS Aluminum COOLING PERFORMANCE Cooling Capacity (BTU/Hr.) Cooling Capacity (Watts) Compressed Air Consumption (SCFM) Compressed Air Consumption (L3/M) SOUND LEVEL Noise Level (dB) ENCLOSURE PROTECTION UL Type ELECTRICAL DATA Rated Voltage Frequency (Hz) UNIT DIMENSIONS Weight (lb./kg)

VC0416012

VC0916012

VC1516012

VC2516012

400 117 8 227

900 264 15 425

1500 440 25 708

2500 733 35 991

69

80

83

90

Type 12 115 50/60

115 50/60

115 50/60

115 50/60

5/2.27

6/2.72

6/2.72

6/2.72

Performance Data  VC Series NEMA Type 4, 4X CATALOG NUMBERS Aluminum Stainless Steel COOLING PERFORMANCE Cooling Capacity (BTU/Hr.) Cooling Capacity (Watts) Compressed Air Consumption (SCFM) Compressed Air Consumption (L3/M) SOUND LEVEL Noise Level (dB) ENCLOSURE PROTECTION UL Type ELECTRICAL DATA Rated Voltage Frequency (Hz) UNIT DIMENSIONS Weight (lb./kg)

VC0916004 VC091604X

VC1716004 VC171604X

VC2516004 VC251604X

900 264 15 425

1700 498 25 708

2500 733 35 991

83

86

90

Type 4, 4X 115 50/60

115 50/60

115 50/60

6/2.72

6/2.72

6/2.72

 Vortex Cooling System Accessories  CATALOG NUMBERS PERFORMANCE Description Use with VCool Model Capacity

EQUIPMENT PROTECTION SOLUTIONS Spec-00302 H

VCOF17 Up to 1700 BTU/Hr.

VCOF25 Oil Filter

PH 763.422.2211 • FAX 763.576.3200 • HOFFMANONLINE.COM

2500 BTU/Hr.

Cooling

2

Sealed Enclosure Cooling Vortex Coolers

7\SLFDO,QVWDOODWLRQ 9RUWH[&RROHU

6ROHQRLG9DOYH 1371RUPDOO\&ORVHG 1(0$RU;5DWHG 9+]RU9+]

0LFURQ)LOWHU 6XSSOLHG

$LUIORZ

&ROG$LU 'XFWLQJ.LW

7KHUPRVWDW





1

3



3

Cooling

SUBJECT TO CHANGE WITHOUT NOTICE

EQUIPMENT PROTECTION SOLUTIONS Spec-00302 H