XJGD Combination Expansion/Deflection Coupling and Expansion ...

Report 2 Downloads 114 Views
220-223.qxp

12/16/2013

4:04 PM

Page 223

XJGD Combination Expansion/Deflection Coupling and Expansion Joint Internally Grounded

Wet Locations

XJGD Ordering Information

Applications: XJGD combination fittings are used with rigid metal conduit and IMC: • To accommodate axial expansion, angular misalignment and parallel misalignment

• To maintain a ground connection without the need for an external bonding jumper and clamps • In long conduit runs to prevent conduit from buckling and causing circuit failures • Indoors or outdoors where conduit expansion occurs and there are wide temperature swings

Hub Size

Cat. #

A Diameter

B Length

1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"

4" 4" 4" 4" 4" 4" 4" 4"

XJGD34 XJGD44 XJGD54 XJGD64 XJGD74 XJGD84 XJGD94 XJGD104

315/16" 41/4" 41/2" 415/16" 55/16" 515/16" 61/2" 8"

173/4" 181/8" 185/8" 191/4" 203/4" 215/8" 215/8" 273/4"

CP

• To couple together two (2) sections of conduit subject to longitudinal movement

Maximum Conduit Movement

• In conduit runs that cross structural joints • In conduit runs to prevent damage to conduit supports such as in a building or on a bridge

Certifications and Compliances: • UL standard: 514B

Standard Materials: • Body, Hubs, Gland Nut, Washer, Bushing – Feraloy® • Packing – Teflon® • Gasket – vellum • Ground Spring – phosphor bronze • Outer Jacket – molded neoprene • Jacket Clamps – stainless steel • Inner Sleeve – molded plastic • Ground Straps – tinned copper braid

Standard Finishes: • Feraloy® – electrogalvanized

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright© 2013 Eaton’s Crouse-Hinds Business

223