Features and Benefits Save space by connecting conductors up to 4 mm² (CB certified) 12 AWG in just 5.2 mm 0.205 in spacing.
48.8 1.92"
56.3 2.22"
53 2.09"
26.7 1.05"
3D CAD outline drawings available on "Control Product 3D" portal
Ordering Details
Type
Order Code
EAN Code
Pack(ing)
Weight g (1 pce)
Grey
ZS4
1SNK 505 010 R0000
3472595050109
50
8.77
Blue
ZS4-BL
1SNK 505 020 R0000
3472595050208
50
8.77
Orange
ZS4-OR
1SNK 505 030 R0000
3472595050307
50
8.77
Yellow
ZS4-YL
1SNK 505 060 R0000
3472595050604
50
8.77
Green
ZS4-GN
1SNK 505 061 R0000
3472595050611
50
8.77
Red
ZS4-RD
1SNK 505 062 R0000
3472595050628
50
8.77
Purple
ZS4-PR
1SNK 505 063 R0000
3472595050635
50
8.77
Brown
ZS4-BR
1SNK 505 064 R0000
3472595050642
50
8.77
White
ZS4-WH
1SNK 505 065 R0000
3472595050659
50
8.77
Black
ZS4-BK
1SNK 505 066 R0000
3472595050666
50
8.77
Declarations and Certificates
Document Part Number
CE
UE Directive
1SND 225 081 C1006
CB
Third Party Certificate
1SND 161 017 A0201
RoHS
1SND 230 491 F0203
Atex Declaration
1SND 225 085 C1003
RoHS
1
General Information The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
Protection
IP 20
Rail
DIN3-TH35
Wire stripping length
10.5 mm
NEMA 1
0.413 in
Screw clamp
Screw rail contact (Maximum value)
Flat screwdriver Operating tool
3.5 mm
Torque
0.138 in
0.6 Nm
5.31 lb.in
± 0.1 Nm
± 0.885 lb.in
± 0.1 Nm
± 0.885 lb.in
Mechanical endurance of disconnect system
Material Specifications Polyamide 600 V UL94 V0 NF F 16 101 I2F2 Needle flame test IEC 60695-11-5 Compliant
Insulating material IRC Flammability
Connecting capacity per clamp 0.2-4 mm² 0.22-4 mm² 0.22-4 mm²
1 Rigid conductor 1 Flexible conductor without ferrule 1 Flexible conductor with ferrule
4.7 mm
Ferrule maximum outer diameter
24-10 AWG 24-12 AWG 24-12 AWG 0.185 in
Multi Connecting capacity per clamp 2 Rigid conductors 0.2-1 mm² 2 Flexible conductors without ferrule 0.22-1 mm² 2 Flexible conductors with twin ferrule 0.22-1.5 mm² Don't mix solid and flexible conductors in the same clamp Don't mix solid or flexible conductors of different sizes in the same clamp
24-18 AWG 24-18 AWG 24-16 AWG
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Cross section Rated cross section Maximum Cross section Gauge
Manufacturer data
4 mm² 4 mm²
Manufacturer data
12 AWG 10 AWG
A3-B3 / 3 mm / 0.118 in / IEC 60947-7-1
Electrical characteristics Current Rated current Field and factory wiring Cat.2 Factory wiring Cat.1 Rated short-time withstand current 1 s (Icw) Short-time withstand current 0.5 s 5s 10 s 30 s 1 mn Rated short circuit withstand Max. current (45° temperature increase) / Max. cross section (mm²) Maximum short circuit current (1s)
2
IEC 60947-7-1 32 A UL 1059 20 A UL 1059 CSA-C-22.2 n° 158 20 A 480 A Manufacturer data Manufacturer data Manufacturer data Manufacturer data Manufacturer data CSA-C-22.2 n° 158 Manufacturer data 32 A Manufacturer data 480 A
4 mm²
Short Circuit Current Rating (SCCR) SA UL 1059 supplement
SCCR UL 1059
With the following configurations: Maximum voltage Suitable conductor wire range Fuse rating Fuse designation Fuse manufacturer name Fuse type Short circuit current
Voltage Rated voltage Rated voltage Use Group Rated voltage Rated voltage Ex e
IEC 60947-1 UL 1059 UL 1059 CSA-C-22.2 n° 158 IEC/EN 60079-11
1000 V 600 V C 600 V 630 V
8000 V 2200 V IEC 60947-1 3 IEC 60947-1 III
Rated impulse withstand voltage Dielectric test voltage Pollution degree Overvoltage category
Dissipated power IEC 1 W
Maximum dissipated power at rated current
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3 Overload and short-circuit protection Separate arrangement Exclusive short-circuit protection Separate arrangement
IEC 60068-2-2 Temperature Duration of test IEC 60068-2-30 Temperature Number of cycles IEC 60068-2-1 Temperature Duration of test IEC 60068-2-61 Dry heat Duration of test / Temperature Cyclic damp heat Number of cycles / Temperature Cold Duration of test / Temperature
Compliant +100 °C 96 h Compliant +55 °C 2 Compliant -40 °C 96 h Compliant 16 h +85 °C 1 +55 °C 2h -25 °C
Corrosion Salt mist Conditions SO2 Conditions Sulfur dioxide Conditions Hydrogen sulfur Conditions Flowing mixed gas corrosion test Conditions
IEC 60068-2-11 Duration of test Concentration ISO 6988 Duration of test Concentration IEC 60068-2-42 Duration of test IEC 60068-2-43 Duration of test IEC 60068-2-60 Number of the test method Duration of test
Compliant 96 h 5% Compliant 48 h 0.2 dm³
IEC 60068-2-6 Frequency range Number of cycles Amplitude Acceleration IEC 60068-2-64 Duration of test Frequency range Acceleration
Compliant 10-55 Hz 10
Vibrations Vibrations Conditions
Ramdom vibrations and climatic sequence Conditions
Climatic cycles Step 1 -> Temperature / Duration of test Step 2 -> Temperature / Duration of test Temperature variation per minute