A6.4 - CONSTRUCTION DETAILS INTERIOR

Report 5 Downloads 182 Views
TOP OF SLAB ELECTRICAL METALLIC TUBING

T

RIDID STEEL CONDUIT THRU SLAB SLAB SAND GRAVEL

Harold Thompson Architects architecture

EARTH PAD

NOTE: GREEN GROUND WIRE REQUIRED IN ALL CONDUITS, SIZED PER N.E.C. REQUIREMENTS.

UNDER SLAB CONDUIT

N.T.S.

design

consulting

YES001

17

FIRE SUPPRESSION SYSTEM WIRING DIAGRAM

N.T.S.

9

NOT USED

1

N.T.S.

WATTSTOPPER DT-355 LINE VOLTAGE DUAL TECHNOLOGY CEILING SENSOR LOAD L O A D

SYMBOL ON PLAN -

HOT

SEAL

NEUTRAL

LINE 120VAC,60Hz

GREEN GROUND

2/18/16

GREEN

NOT USED

N.T.S.

18

NOT USED

N.T.S.

14

NOT USED

N.T.S.

10

SHUNT TRIP CIRCUIT BREAKER (TYP.). SEE PANELBOARD SCHEDULES FOR ACTUAL QUANTITY.

CANOPY 120V, 60Hz, 4A USED SAME TIMED CIRCUIT AS MENU BOARD

ST

ST

SHUNT TRIP CIRCUIT BREAKER COIL (TYP.)

PROTOTYPE REVISIONS 9.15.15

(1) 3/4" POWER CONDUIT TO BLDG. FROM CANOPY

HOOD FIRE EXTINGUISHER CONTACT

ST

A

MENU BOARD TO PANEL "A"

SEQUENCE OF OPERATION: UPON ACTIVATION OF ANY HOOD FIRE SUPPRESSION SYSTEM RELAY, A RELAY IN THAT FIRE SUPPRESSION SYSTEM SHALL CAUSE ALL SHUNT TRIP CIRCUIT BREAKERS TO OPERATE, THUS REMOVING POWER FROM ALL DEVICES CONNECTED TO EQUIPMENT LOCATED UNDER THE GREASE HOOD. EXHAUST FANS SHALL NOT BE AFFECTED BY THIS ACTION AND SHALL CONTINUE TO BE CONTROLLED AS INDICATED IN THE SEQUENCE OF OPERATIONS INDICATED IN DETAIL 2/E6.0.

EXTEND CONDUIT TO ABOVE CEILING

CURB

PRE-PAY WINDOW

"

SHUNT TRIP DETAIL

N.T.S.

1'-3

11 5'-

CONTRACT DATE: BUILDING TYPE:

EXPLORER MED40

PLAN VERSION:

ARRIL 2015 (N)

DRIVE-THRU WINDOW

SITE NUMBER: STORE NUMBER:

MIN SECURITY MONITOR BASE ATTACHMENT. PROVIDE WD. BLKG.

DATA OUTLET. SEE SHEET E5.0

ELECTRICAL OUTLET. SEE SHEET E3.0

VIEW IS LOOKING UP AT WALL BEHIND SERVICE COUNTER & BOTTOM OF MENU BOARD SOFFIT.

N.T.S.

(1) 1" DATA CONDUITS TO BLDG. (1) 3/4" POWER CONDUIT TO BLDG.

12

EXPLORER MEDIUM 54

NOTE: SOLDER & INSULATE BOTH MAG. LOOP CONN. MAGNETIC LOOP FOR PRE-PAY WINDOW. RUN ALL LOOP SENSOR WIRING TO POINT OF CONNECTION AT THE DRIVE-THRU TIMER.

NOTE:

POWER/DATA @ SECURITY MONITOR

(3) 1" DATA CONDUITS TO BLDG. (1) 3/4" POWER CONDUIT TO BLDG. ORDER CONF BOARD. 120V, 60Hz, 0.45A ISOLATED GROUND CIRCUIT ALWAYS HOT (UN-TIMED) I.G. RECEPTACLE. INSTALLED IN BASE OF SPEAKER POST.

WALL BEHIND SERVICE COUNTER

MIN

XXXXX

HIGHWAY 100 NASHVILLE, TN

BOTTOM OF MENU BOARD SOFFIT

4"

XXX-XXX

TACO BELL

0"

SECURITY SYSTEM MONITOR. SEE SHEET A2.0.

4"

XX.XX.XX

EXTEND CONDUIT TO ABOVE CEILING

ELECTRICAL DETAILS PREFAB MAGNETIC LOOP (SEE SCOPE OF WORK) LOCATE 2" BELOW TOP OF CONCRETE PAVEMENT.

DRIVE-THRU COMMUNICATIONS ISOMETRIC

YES006A

SCHEDULE 40 PVC

N.T.S.

E7.0 4