Alarm For additional information regarding operation ... - See Water Inc

Report 3 Downloads 71 Views
Alarm

IM 256, Rev. 0217

Installation Manual

Liquid Level Alarms:

Panel Installation:

The HLA-4X-X provides constant monitoring of potential threatening liquid level conditions at multiple alarm points.

1. Determine mounting location for control panel. Mount panel using mounting hardware supplied. 2. The control panel should not be mounted in an area that is subject to submersion. 3. Run signal cables through conduit. Make appropriate field connections. 4. Branch circuit protection to be provided by installer.

Models: HLA-4X-2 - 2 Alarm Panel HLA-4X-3 - 3 Alarm Panel HLA-4X-4 - 4 Alarm Panel HLA-4X-5 - 5 Alarm Panel HLA-4X-6 - 6 Alarm Panel HLA-4X-7 - 7 Alarm Panel HLA-4X-8 - 8 Alarm Panel HLA-4X-9 - 9 Alarm Panel HLA-4X-10 - 10 Alarm Panel

Start up:

Features:

1. When the power is applied, the power light on each board shall illuminate. 2. To test the alarm circuit, push the test button on the side of the panel, the audible alarm shall sound and the red beacon will light. Press the silence button to silence the alarm.



Service:

• • • • • •

NEMA 4X polycarbonate enclosure with lockable latches UL listed for the United States and Canada Alarm visible indicators: red beacon alarm light, alarm test and silence buttons Audible alarm provides audio warning of alarm condition (85 decibel) 22mm indicator on front panel for each alarm point Remote monitoring dry contacts; form C for each alarm point Each panel comes standard with a narrow angle float switch with 20 cord for each alarm point

Options: • • • • •

S3 = S4 = BB = SS = AF =

No floats included Normally closed float (for low level applications 12V battery backup for alarm circuit Stainless steel enclosure Alarm flasher

1. All installations must be in accordance with the National Electrical Code, and any other applicable state and local electrical requirements.

For additional information regarding operation and troubleshooting questions, please call See Water, Inc. at 888-733-9283.

Caution: Before checking electrical connections within the control or attempting to replace any components, turn off all branch circuits supplying power to the main control panel. Troubleshooting: Alarm Circuit To test the alarm light and buzzer, press the test button on the front panel. If either the light or buzzer do not indicate, replace the light bulb or buzzer with same type. Control Board and Fuse The control board is rated for 120VAC. If fuse is blown, replace fuse with same type. The dry contacts are rated for 120VAC, 5 amps maximum. www.seewaterinc.com 951.487.8073 • 888.733.9283 [email protected] 22220 Opportunity Way, Suite 104 Riverside, CA 92518