BB, BBO Current Transformer Bushing Type

Report 13 Downloads 219 Views
Medium Voltage Product

BB, BBO Current Transformer Bushing Type

Technical parameters Highest voltage for equipment

[kV]

Power frequency test voltage, 1 min. [kV]

12 - 24 ( 25) 28 - 50

Lighting impulse test voltage

[kV]

600 - 5000

Rated Current

[ A]

4000 - 5000

Burdens, classes

[ VA/cl]

Reconnectible

10 - 60 / 0,5 - 5 P Secondary reconnectible

Description Transformers of this type series enable the measuring and protection in the medium voltage switchboard with rated primary currents of up to 5000 A. They are designed for use in indoor installations, both in normal and severe climatic conditions. The transformers are all of trought-going conductor design, with one to three secondary outlets, according to the type of its use. The magnetic circuits together with windings are embedded in epoxi resin and the intermal paint oftransformer body is provided with a semiconductive pain which is fitted on the front surface of transformer body too.While in operation, the potential of primary winding is connected to this paint.

BB 104 (BBO)

BB 223

1 to 2

3

12 kV

17,5 kV up to 5000

1 to 2 25 kV

Transformer type Number of cores

BB 103

Insulation voltage level Rated primary current

up to 4000 5 or 1 A

ated secondary current

Transformers are equipped with a baseplate with four mounting holes, the BB 104 types have a third secondary outlet to connect differential protection relay. In case a third secondary winding is needed, we use the type BBO 104 with a transformer ratio of 1:100 of primary current value. All the transformers meet the specifications of relevant standards, i.e.the IEC, VDE, ANSI, BS, GOST, ČSN.

5 or 1 A BBO types - third winding 1/100 ln

up to 4000 A 5 or 1 A

Dimensions

Type

Dimensions

Weight

Marking of current transformer outlets

a) Single-core design

b) Double-core design

d) Single-core design, reconnectable on the secondary side

e) Double-core design, reconnectable on the secondary side

c) Three-core design

Standartized transformers

Ratio

Burden [ VA ]

Accuracy

FS/ALF

Ratio

2000/5 A 2000/5/5 A 2000/5/5/5 A 2500/5 A 2500/5/5 A 2500/5/5/5 A 3000/5 A 3000/5/5 A 3000/5/5/5 A 4000/5 A 4000/5/5 A 4000/5/5/5 A 5000/5 A 5000/5/5 A 5000/5/5/5 A

BB104 120 5P 30/120 0.5/5P 30/60/60 0.5/5P/5P 120 5P 30/120 0.5/5P 30/120/120 0.5/5P/5P 120 5P 30/120 0.5/5P 30/120/120 0.5/5P/5P 120 5P 60/120 0.5/5P 60/120/120 0.5/5P/5P 120 5P 60/120 0.5/5P 60/60/60 0.5/5P/5P

20 5/15 5/6/12 25 5/20 5/5/10 30 10/25 10/6/10 35 5/30 5/8/15 40 5/35 5/10/18

1500/5/5/15 A 2000/5/5/20 A 2500/5/5/25 A 3000/5/5/30 A 4000/5/5/40 A

BBO 104 30/60 0.5/5P 30/60 0.5/5P 30/120 0.5/5P 30/120 0.5/5P 60/120 0.5/5P

5/5 5/5 5/5 10/6 5/8

1500/5 A 1500/5/5 A 2000/5 A 2000/5/5 A 2500/5 A 2500/5/5 A 3000/5 A 3000/5/5 A 4000/5 A 4000/5/5 A

BB 103 60 5P 30/30 0.5/5P 60 5P 60/30 0.5/5P 60 5P 60/60 0.5/5P 120 5P 60/60 0.5/5P 120 5P 60/60 0.5/5P

5 5/5 6 5/6 8 5/5 5 10/6 6 10/8

1500/5 A 1500/5/5 A 2000/5 A 2000/5/5 A 2500/5 A 2500/5/5 A 3000/5 A 3000/5/5 A 4000/5 A 4000/5/5 A

BB 223 60 5P 30/30 0.5/5P 60 5P 60/30 0.5/5P 60 5P 60/60 0.5/5P 120 5P 60/60 0.5/5P 120 5P 60/60 0.5/5P

5 5/5 6 5/6 8 5/5 5 10/6 6 10/8

600/5/6 A 15 750/5/7.5 A 15 800/5/8 A 15 1000/5/10 A 30 1250/5/12.5 A 30 1500/5/15 A 60

BBO 102 0.5 0.5 0.5 0.5 0.5 0.5

10 10 10 10 10 5

Burden [ VA ]

Accuracy

FS/ALF

A358-061-I/2011P