CURRENT MONITORING DETECT BELT LOSS, COUPLING SHEAR, AND MECHANICAL FAILURE
9EAR
7ARRANTY
H606
Current Switches: Adjustable Trip Point, N.C. Output Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable, and maintenancefree fan and pump status indication.
APPLICATIONS n Monitoring fans, pumps, motors, and other
electrical loads for proper operation
Detecting belt loss and motor failure...ideal for
Small split-core package for retrofits
fan and pump status Verifying lighting circuit loads Monitoring critical motors (compressor, fuel, etc.) Monitoring industrial process equipment status (OEM)
H706
Calibrated Trip Point Off
Wide monitoring range in a solid-core housing
Fan/pump On
Cost effective...reduced installation and service costs Adjustable trip point...4 amperage range options for versatility Easier to install than differential pressure switches...no tubing needed 100% solid-state, no moving parts to fail Output status LEDs for fast setup Adjustable mounting bracket on the solid-core housing...easy placement Self-gripping iris on the split-core housing for easy installation Bracket on H900 can be installed in three different configurations...added flexibility 5-year limited warranty
Electrical failure
Loss of belt/coupling shear
Off
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That's why our sensors are the industry standard for status.
Maximize Reliability Minimize Installed Cost
H806
Low turn-on in a mini solid-core package for small motors
H906
Wide monitoring range in a split-core housing
SPECIFICATIONS Sensor Power Insulation Class Frequency Range Temperature Range Humidity Range Hysteresis Off State Leakage On State Voltage Drop Terminal Block Maximum Wire Size Terminal Block Torque (nominal) Agency Approvals
5-30VDC 600VAC rms (UL), 300VAC RMS (CE) 50/60Hz -15° to 60°C (5° to 140°F) 10-90% RH, non-condensing 10% Typical 34μA@5VDC, 200µA@30VDC 1.9VDC
[email protected] 14 AWG 4 in-lbs (0.45 N-m) UL 508 open device listing CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage For applications requiring double or reinforced insulation, please contact the factory.
26
800.354.8556
503.598.4564
www.veris.com
©2008 Veris Industries
CURRENT MONITORING DIMENSIONAL DRAWINGS H606
H806
Removable Mounting Bracket 0.6" (16 mm) 0.7" (18 mm)
2.1" (54 mm)
H906
Removable/Adjustable Mounting Bracket 0.9" (23 mm)
ø 0.7" (18 mm)
1.2" (31 mm)
2.1" (54 mm)
0.4” x 0.2” Slot (x2)
1.1” (26 mm)
* * (793.1” mm)
Self-gripping Iris
2.8” (70 mm)
1.1" * (27 mm)
1.4” (36 mm)
Ø = 0.3” (8 mm)
2.3" (58 mm)
2.9" (74 mm) 3.5" (89 mm)
Bracket can be mounted on either side for added installation flexibility.
0.8” (21 mm)
1.7 (43 mm)
1.0" * (26 mm)
0.4” x 0.2” (10 mm x 5 mm) Slot (2x)
1.0” (25 mm)
2.8" (71 mm)
2.5" * (64 mm)
0.5" (13 mm)
Removable Mounting Bracket
*
2.5” (64 mm) 3.0” (76 mm)
H706
APPLICATION/WIRING EXAMPLE
Removable/Adjustable Mounting Bracket
Monitoring Fan /Pump Motors for Positive Proof of Flow 0.9" (23 mm)
0.7" Dia (19 mm) 3.0" * (75 mm)
CONTACTOR DDC CONTROLLER
2.8" (68 mm)
-
1.1" * (27 mm) 0.2” x 0.15” slot (2x)
+ -
3.8" (95 mm) 4.2" (106 mm)
+ DI
+
5-30VDC POWER SOURCE
Fan or Pump
* Terminal block may extend up to 1/8” over the height dimensions shown.
Motor
ORDERING INFORMATION MODEL AMPERAGE RANGE H606
1.25 - 50A
H706
1-135A
H806
0.75 - 50A
H906
2.5-135A
STATUS OUTPUT (max.) MIN. TRIP POINT N.C. 0.1A@30VDC
HOUSING STATUS LED
UL
CE
1.25A or less
Split-Core
n
n1
n
1.0A or less
Solid-Core
n
n
n
0.75A or less
Solid-Core
n
n
n
2.5A or less
Split-Core
n
n
n
1
Listed for use on 75°C insulated conductors.
ACCESSORIES
DIN Rail Clip Set, DIN Rail, and DIN Stop Clip...see page 219.
800.354.8556
503.598.4564
www.veris.com
©2008 Veris Industries
27