0-10 PWM LOW VOLTAGE OUTPUT STATION-DIN

Report 26 Downloads 55 Views
0-10 PWM LOW VOLTAGE OUTPUT STATION-DIN Load Controls

The 0-10 PWM Low Voltage Output Station-DIN is used for the control and automation of LED, CLF and CCFL lighting loads requiring either 0-10 or PWM for dimming control. Each LVOS DIN features eight 0-10 outputs with four that can be turned into PWM outputs. The LVOS DIN is firmware upgradable in the field through its station bus, has four dry contact inputs with two addtional override inputs and is powered by 13.8 to 36VDC. The dry contact inputs can be used with motion sensors, light sensors, pressure sensors,

IR

input,

magnetic

switches,

and

more.

Product Highlights • Controls up to eight separate sets of LED, CFL, or CCFL lighting loads • Offers control of either 0-10 or PWM type loads • Allows for the addition of dry contact inputs to the automation network including motion sensors, light sensor, IR input, pressure sensors magnetic switches, and more • Manual control and LED status for all eight outputs on front • Installs on DIN rail • Powered by 13.8 to 36VDC • Firmware upgradable in the field

ON

OFF

GND

3 4 IR SEN S

GND

2

OUT

1

OUT

LVOS-0-10PWM-DI N

OUT

S TATION BUS CLASS 2

OUT

0-10 PWM Low Voltage Output Station-DIN

SERIAL NUMBER

S TATION BUS CLASS 2

1

2

3

5

6

7

8

LOW VOLTAGE OUTPUT STATION-0-10-PWM-DIN

GN D

OU T

8 GN D

GN D

TOP VIEW

STATUS

7 GN D

OU T

6 OU T

GN D

5 OU T

OU T

GN D

4 GN D

3 OU T

2 GN D

1 OU T

INPUT 13.8-36 VDC

OU T

GN D

OU T

RED = 0-10 GREEN = PWM

4

2.28”

3.4”

SET

SIDE VIEW

LVOS-0-10-PWM-DIN 0-10: 10VDC@100mA MAX PWM: 12VDC@100mA MAX

6.18” FRONT VIEW

BOTTOM VIEW

Specifications Dimensions, HWD

3.4” x 6.18” x 2.28”



86mm x 157mm x 58mm

Model

LVOS-0-10-PWM-DIN

Weight

2lbs 8oz (1.13kg)

Mounting

DIN Rail

Ambient Operating Humidity

5-95% non-condensing

Ambient Operating Temperature

0-35°C (32-95°F)

Auxiliary Inputs

4 Dry Contacts

Override Inputs

2 (On and Off Contacts)

Input power

13.8 - 36VDC

Power Consumption

15W

LED Indicators

Microprocessor Status, Configuration, Load

Number of Low Voltage Loads

8 Low Voltage Loads



100mA Sink/Source (0-10)



100mA Source (PWM)

Station Equivalent

InFusion 0.35W on IC-24 / 0.55W on IC-36

Station Bus Connections

24V / 36V Station Bus

CE Listed

Yes

General Specifications

Wiring Specifications Station Bus Wiring

Minimum 2 conductor, 16 AWG stranded, non-shielded twisted pair, 30 pF/foot max, UL rated CL2

Station Bus Topology

Any combination of daisy chain or star or branch



Station Bus should be separated a minimum of 18” from other parallel communication



and/or high voltage runs

System Compatibility InFusion