19 Meter Mains

Report 0 Downloads 33 Views
19

Meter Mains

100-200 Amp | 4 Terminal | Ringless & Ring Type | 240 VAC

1 1

1 1

1 2

1

1

3499 8144

1

1

1

2

1

3491 8143

3

U8144-XL

U3491-XL-200

4 Terminal — Meter Main — Ringless Catalog Number

Amps Service

Hub

Breaker Compatibility

Connectors CU/AL

Dimensions

Knockouts

Line

Load

D"

W"

H"

1

3

2

3

⁄4, ⁄2



U3499-XL

100

OH/UG

C.P.

QP2100

#6-2/0

#14-1/0

3 ⁄4

11

22

2

U3491-XL-150

150

OH/UG

C.P.

UFQB-150-X1

#6-350

#1-300

41⁄8

12

29

21⁄2

2

1

⁄4

U3491-XL-200

200

OH/UG

C.P.

UFQB-200-X1

#1-300

#1-300

4 ⁄8

12

29

2 ⁄2

2

1

⁄4

1

1

1

1

4 Terminal — Meter Main — Ring Type Catalog Number

Amps Service

Hub

Breaker Compatibility

Connectors CU/AL

Dimensions

Knockouts

Line

Load

D"

W"

H"

1

U8144-XL

100

OH/UG

C.P.

QP2100

#6-2/0

#14-1/0

33⁄4

11

22

2

U8143-XL-150

150

OH/UG

C.P.

UFQB-150-X1

#6-350

#1-300

41⁄8

12

29

21⁄2

2

1

⁄4

U8143-XL-200

200

OH/UG

C.P.

UFQB-200-X1

#1-300

#1-300

4 ⁄8

12

29

2 ⁄2

2

1

⁄4

1

1

2

3

⁄4,1⁄2



1

Notes • Hubs: For proper hub selection refer to the hub suffix chart on the accessory page. • Sealing Rings: Ring type units priced with MR-2 sealing ring. See accessory page for other choices. • Breakers: Bolt-on circuit breakers are factory installed in the U8143 and U3491 series. The U8144 & U3499 do not come with breakers unless specified on order and require plug-in style. • Short Circuit Current Rating: 10K AIC. However, this rating is limited to the lowest interrupting capacity of any circuit breaker installed. Watthour meter not included in short circuit current rating.

Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering or installing equipment in this catalog.

100-200 AMP METER MAINS