A e r o S y s I
n
c
o
r
p
o
r
a
t
e
d
Ceiling Mounted Units
CeilMate
TM
Series 1 to 3 tons of cooling capacity Air Cooled, Self-Contained Water Cooled Glycol Cooled Remote Air Cooled Condenser Air Handler with Remote Condensing Unit Chilled Water AeroSys, Inc. 929 Eldridge Drive Hagerstown, Maryland, 21740 Tel: 301-620-0002 Fax: 301-620-0685 www.aerosysinc.com AeroSys, Inc.
1
AeroSys, Inc.
Introduction AeroSys, Inc. is owned, managed and operated by a team with decades of experience in the air conditioning and refrigeration industry. AeroSys, Inc. is an independent equipment manufacturer, an EPA Certified Refrigerant Reclaimer and is DOT approved to re-qualify recovery cylinders. AeroSys, Inc. is comprised of two divisions: Air Conditioning Equipment Manufacturing, and Refrigerant Reclaim Services.
Air Conditioning Equipment The Air Conditioning Equipment division has designed and manufactured thousands of air conditioning systems: AeroCool Chilled Water Air Handlers AeroCon Thru-the-Wall Condensing Units & Heat Pumps CeilMate Ceiling Mounted Spot Coolers
Refrigerant Reclamation Services AeroSys is an EPA approved Certified Refrigerant Reclaimer under 40 CFR 82.164. AeroSys provides refrigerant reclamation and recertification services exclusively to HVAC wholesalers, and markets certified (ARI-700 ) reclaimed refrigerants under the AeroPure brand of refrigerant through our HVAC wholesale customers. AeroSys is also approved by the DOT for re-qualification of refrigerant cylinders under Title 49, Code of Federal Regulations, 49 CFR. We test, repair, repaint and re-certify refrigerant cylinders from 15# tanks up to 250# tanks.
Table of Contents Page Features 3-5 Air Cooled, Self-contained 6 Water Cooled 7 Glycol Cooled 8 Air Cooled, Remote Condenser 9
2
Page Air Handler, Remote Condensing 10 Chilled Water 11 Electrical Data 12-13 Outside Heat Exchangers, Condensing Units 14 Dimensional, Pump Package Data 15-16 AeroSys, Inc.
CeilMateTM Applications These systems are designed for commercial IAQ (Indoor Air Quality) applications where cooling, heating, humidifying, dehumidifying, ventilating and air conditioning solutions are required. CeilMateTM systems are ceiling mounted air conditioners, designed for reliable 24/7 operation. Typical critical applications include: Telecommunication switch-gear rooms Data centers Clean rooms Medical MRI and CAT scan rooms
Laboratories Bank and ATM kiosks Conference rooms LAN and data relay facilities
Product Nomenclature C M - 24 - AS CM = CeilMateTM
AS = Self-Contained Air Cooled W = Water Cooled Nominal Cooling Capacity G = Glycol Cooled (in thousands of BTU/H) AR = Remote Condenser, Air Cooled AH = Air Handling Unit CW = Chilled Water ( 2 ton self contained air cooled shown in above example)
System View Multi-speed Blower Motor
Oversized blower for low RPM and field flexibility
Electric Box Electrode Canister Humidifier
Scroll Compressor Thermal Expansion Valve
A-Frame Evaporator
Heater
Stainless Steel Condensate Drain Pan
Standard Features Refrigeration System
Cabinet The CeilMateTM is manufactured from aluminum for light weight, corrosion resistance and asthetics. The cabinet is structurally reinforced throughout to provide a stable and secure platform for the air conditioning components.
The unit’s evaporator section is insulated with high density, 2 lb/ft 2 thermal and acoustical insulation and sealed with self-extinguishing gasket material. Panels are fastened with quick release hardware to simplify internal access.
The CeilMateTM system includes all necessary components for safe and reliable operation. Easily accessible components include: thermal expansion valve, sight glass with moisture indicator, high and low pressure safety switches, refrigeration service access ports, and refrigerant drier/strainer. Self-contained air cooled, water and glycol cooled units are evacuated and shipped with a full refrigerant charge. Split systems include a refrigerant pump-down solenoid to prevent liquid slugging. Units are evacuated and charged with dry nitrogen.
A-Frame Coil The unit has a large face area coil to increase cooling efficiency and reduce power consumption. The copper tube, aluminum fin coil is mounted in a stainless steel condensate pan; a condensate safety switch guards against condensate overflow. Blower and Blower Motor The CeilMateTM incorporates a three speed direct drive blower motor in a draw-thru configuration for even air distribution across the coil . The large blower runs at a low rpm to minimize air noise and motor horse power consumption. The blower assembly is mounted to an internal chamber to further reduce noise levels. Electrical System The unit has a Class 2, 24VAC control circuit, all necessary contactors, fuses and/or circuit breakers for full operation. 24 VAC field connections and high voltage connections are provided through separate termination blocks in the electric box.
Compressor All D.X. systems, 1-1/2 ton and larger (CM18 thru CM-36) incorporate scroll compressors for high reliability, high efficiency and low noise. CM-12, one refrigerant ton, systems include the latest generation in reciprocating compressors. Compressors are mounted on vibration isolators to minimize noise transmission to the cabinet. Chilled Water Units Chilled water CeilMateTM systems are completely piped, wired and factory tested. Units include a 24 volt motorized zone valve for chilled water control. Water Regulating Valves All Water and Glycol cooled systems are delivered with factory installed, tested and adjusted 2-way water regulating valves, rated for 150 psi w.w.p, to maintain proper refrigerant head pressure.
Optional Features Ducted System The system is available in three air patterns: ducted return and supply, ducted return and “free” air discharge, or “free” return and ducted discharge. “Free” air is through the bottom of the unit the supply or return air pattern.
4
Ultra Violet Sterilization Light The unit incorporates a high intensity UV light to sterilize the air passing through the coil. As airborne mold bacteria are exposed to the UV light they are killed, preventing them from depositing active contaminants on the coil surface, the condensate pan and other internal surfaces. As the air is changed several times in the conditioned room, the contaminants are constantly being reduced in number.
AeroSys, Inc.
Optional Features CeilStat I
Electrode Canister Humidifier Integrated with the CeilStat, the humidifier provides humidification to your facility. An optional electrode canister is available providing state-of-the-art humidity control. The humidifier senses cylinder current draw, automatically flushing and filling the cylinder to control the mineral content of the water and humidity output The output is field adjustable from 1 to 5 lbs/hr. A “Change Cylinder” light alerts service personel when the humidifier output requires service. Electric Heat/Reheat Electric reheat is designed to offset the cooling effect of the dehumidification cycle; electric heat provides resistance heat regardless of the dehumidification cycle. The unit incorporates a factory installed, wired and tested nichrome wire heater. The heater has low voltage thermal safety cutouts, one pilot duty automatic resettable and a second power line fuselink (overtemperature) safety device for each bank of heat.
Electronic Thermostat/Humidistat The CeilStat I temperature and humidity controller incorporates temperature and humidity control in an attractive, wall mounted unit. This line powered, backlit system incorporates several salient features: * Manual override * 7 day programming * Programmable Fan * Adjustable Differential * Compressor Short Cycle Protection * Air Filter Monitor * 4 Hour reserve for settings * Status Indicators * Humidification in heat or air circulation modes * Hidden Service Level * Condensation Control CeilStat II Internet Accessible Thermostat/Humidistat The CeilStat II temperature and humidity controller incorporates temperature and humidity control in an attractive, wall mounted unit. This line powered, backlit system incorporates several salient features:
Condensate Pump options: External: The condensate pump is factory mounted, wired and integrated into the moisture removal system of the unit. In the event the condensate pump can not remove the water fast enough, an emergency shut-off switch locks out the compressor and humidifier until the condensate pump has emptied its sump. Internal: The condensate pump is factory mounted in the stainless steel condensate pan, wired and integrated into the moisture removal system of the unit. In the event the condensate pump can not remove the water fast enough, an emergency shut-off switch locks out the compressor and humidifier until the condensate pump has emptied its sump.
* Internet Connectivity for monitoring, management and configuration capability (requires secure customer internet access) * Easy installation * Backlit Graphic LCD display * EnergyStar Compliant * FCC Class B Compliant * Failsafe Temperature Switch * Adjustable Differential * Compressor Short Cycle Protection * E-Mail or Text Messaging Fault reporting * Status Indicators * Independent humidify and dehumidify control in cooling and heating modes * Hidden Service Level Alarms * Air Filter Monitor * Over/Under Temperature Alarm * High Humidity alarm * Customer selected contact closure
High Pressure Glycol/Water Systems Water cooled systems are available with factory installed, tested and adjusted 2way water regulating valves, rated for 350 psi w.w.p, to maintain proper refrigerant head pressure. 500 psi valves are also available.
AeroSys, Inc.
5
Air Cooled, Self-Contained Systems Model CM-( )-AS Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity
(12)
(18)
(24)
(30)
(36)
15,660 11,940
19,970 16,300
24,090 18,700
29,890 24,870
36,730 27,990
14,530 11,860
18,430 16,010
22,290 18,490
27,790 24,520
31,220 27,550
13,770 11,560
17,650 15,640
21,250 18,100
26,680 24,060
29,550 26,840
5.0 kW 17,500
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
750 1/6 20x20
800 1/4 20x20
1,200 1/2 20x20
1,400 1/2 20x20
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 Motor Horsepower 1/8 Filter, 1” deep throw away, Qty. 1 20x20
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm
2/2.7 185
2/3.2 234
2/3.2 250
2/3.7 324
2/3.7 378
1/4 750
1/2 1,000
1/2 1,200
1/2 1,400
1/2 1,600
------
------
Speed Control
------
------
Condenser Blower, DWDI, Direct Drive, 3 speed Motor Horsepower CFM @0.3” esp Condenser Coil, Aluminum Fin, Copper Tube Head Pressure Control (std)
Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)
1 Hp Recip. 20,100
1.5 Hp Scroll 25,750
2 Hp Scroll 31,160
2.5 Hp Scroll 38,980
3.0 Hp Scroll 43,800
3/4 1/4
3/4 1/4
3/4 1/4
3/4 1/4
3/4 1/4
215
220
245
260
270
Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper
Physical Data Dimensions-- see page 15 for details Approximate weight
6
AeroSys, Inc.
Water Cooled Systems Model CM-( )-W
(12)
(18)
(24)
(30)
(36)
18,090 13,030
21,850 17,160
26,520 19,910
33,260 26,520
38,380 30,200
16,600 12,810
20,180 16,870
24,450 19,530
31,230 26,290
36,010 29,950
15,530 12,430
18,980 16,390
23,010 19,000
29,380 25,540
33,880 29,110
5.0 kW 17,500
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
750 1/6
800 1/4
1,200 1/2
1,400 1/2
Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower
500 1/8
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) 2/2.7 2/3.2 Face Velocity, fpm 185 234 Filter, 1” deep throw away, Qty. 1 20x20 20x20
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
2/3.2 250 20x20
2/3.7 324 20x20
2/3.7 378 20x20
2 Hp Scroll
2.5 Hp Scroll
3.0 Hp Scroll
Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type
1 Hp Recip.
1.5 Hp Scroll
Water Cooled Condenser, Coaxial type, with 2 way water regulating valve GPM @ 85oF EWT Unit Pressure Drop (ft of H2O) Total Heat of Rejection (@75/62.5)
3.5 2.5 19,700
4.7 4.6 23,980
5.6 6.5 29,150
7.5 11.5 37,270
8.6 15.1 43,420
3/4 1/4 1/2
3/4 1/4 1/2
3/4 1/4 1/2
3/4 1/4 3/4
3/4 1/4 3/4
195
200
225
245
250
Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Condenser In/Out, Sweat OD
Physical Data Dimensions-- see page 15 for details Approximate weight
AeroSys, Inc.
7
Glycol Cooled Systems Model CM-( )-G Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity
(12)
(18)
(24)
(30)
(36)
15,850 12,160
19,800 16,470
23,930 18,840
30,280 25,390
35,550 29,340
14,350 11,860
18,020 15,910
22,340 18,630
28,500 25,110
33,340 28,860
13,280 11,410
17,610 15,730
20,990 18,090
26,780 24,250
31,760 28,150
5.0 kW 17,500
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
750 1/6
800 1/4
1,200 1/2
1,400 1/2
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower
500 1/8
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm Filter, 1” deep throw away, Qty. 1
2/2.7 185 20x20
2/3.2 234 20x20
2/3.2 250 20x20
2/3.7 324 20x20
2/3.7 378 20x20
1.5 Hp Scroll
2 Hp Scroll
2.5 Hp Scroll
3.0 Hp Scroll
Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type
1 Hp Recip.
Glycol Cooled Condenser, Coaxial type, with 2 way glycol regulating valve GPM @ 105oF EWT 3.5 4.0 5.3 6.9 Unit Pressure Drop (ft of H2O) 5.7 6.4 6.8 9.3 Total Heat of Rejection (@75/62.5) 17,540 22,790 28,230 36,080 Fluid Cooler size, 95oF Ambient FC-012 FC-018 FC-024 FC-030 Pump Package--See pages 15 and 16 for dimensional information and pump selection
8.8 15.6 42,470 FC-036
Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Condenser In/Out, Sweat OD
3/4 1/4 1/2
3/4 1/4 1/2
3/4 1/4 1/2
3/4 1/4 3/4
3/4 1/4 3/4
195
200
225
245
250
Physical Data Dimensions-- see page 15 for details Approximate weight
8
AeroSys, Inc.
Remote Air Cooled Systems Model CM-( )-AR
(12)
(18)
(24)
(30)
(36)
21,200 14,400
26,400 18,900
31,600 21,900
38,700 28,400
41,300 31,000
16,100 12,600
20,100 16,800
23,900 19,300
29,300 25,200
31,400 27,700
12,800 11,200
17,500 15,700
20,200 17,800
25,700 23,700
27,800 26,000
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
800 1/4 20x20
1,200 1/2 20x20
1,400 1/2 20x20
Cooling Capacity, BTU/H @ 125oF Condensing 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
5.0 kW 17,500
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 750 Motor Horsepower 1/8 1/6 Filter, 1” deep throw away, Qty. 1 20x20 20x20
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm
2/2.7 185
2/3.2 234
2/3.2 250
2/3.7 324
2/3.7 378
Remote Air Cooled Condenser, 95oF Ambient, fan cycling control standard Model (see page 14 for details)
ACC-018
ACC-023
ACC-032
ACC-032
ACC-049
1 Hp Recip. 17,500
1.5 Hp Scroll 25,750
2 Hp Scroll 31,160
2.5 Hp Scroll 38,980
3.0 Hp Scroll 43,800
3/4 1/4 1/2 3/8
3/4 1/4 1/2 3/8
3/4 1/4 1/2 3/8
3/4 1/4 3/4 3/8
3/4 1/4 3/4 3/8
175
180
205
210
220
Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)
Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Liquid line, Sweat OD Hot Gas line, Sweat OD
Physical Data Dimensions-- see page 15 for details Approximate weight
AeroSys, Inc.
9
Air Handler for Remote Condensing Systems Model CM-( )-AH
(12)
(18)
(24)
(30)
(36)
21,200 14,400
26,400 18,900
31,600 21,900
38,700 28,400
41,300 31,000
16,100 12,600
20,100 16,800
23,900 19,300
29,300 25,200
31,400 27,700
12,800 11,200
17,500 15,700
20,200 17,800
25,700 23,700
27,800 26,000
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
800 1/4 20x20
1,200 1/2 20x20
1,400 1/2 20x20
Cooling Capacity, BTU/H @ 45oF Suction 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
5.0 kW 17,500
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 750 Motor Horsepower 1/8 1/6 Filter, 1” deep throw away, Qty. 1 20x20 20x20
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm
2/2.7 185
2/3.2 234
2/3.2 250
2/3.7 324
2/3.7 378
Remote Air Cooled Condensing Unit, 95oF Ambient, fan cycling control standard Model (see page 14 for details)
THDC-12
THDC-18
THDC-24
THDC-30
THDC-036
1 Hp Recip. 17,500
1.5 Hp Scroll 25,750
2 Hp Scroll 31,160
2.5 Hp Scroll 38,980
3.0 Hp Scroll 43,800
3/4 1/4 1/2 7/8
3/4 1/4 1/2 7/8
3/4 1/4 1/2 7/8
3/4 1/4 3/4 7/8
3/4 1/4 3/4 7/8
125
125
150
155
155
Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)
Connection Sizes Condensate drain Humidifier Inlet Liquid line connection, OD Suction line connection, OD
Physical Data Dimensions-- see page 15 for details Approximate weight, lbs.
10
AeroSys, Inc.
Chilled Water Air Handler Model CM-( )-CW
(12)
(18)
(24)
(30)
(36)
Cooling Capacity, BTU/H @ 45oF Entering Water Temperature 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity GPM Rating (point flow water rate)
15,500 12,100
22,040 17,180
25,200 19,400
33,200 27,000
42,600 33,200
12,500 11,100
17,600 16,800
20,100 17,800
27,000 24,800
34,000 30,400
10,120 9,100 2.5 gpm
14,260 13,770 4.0 gpm
16,280 15,410 4.5 gpm
21,870 20,340 5.0 gpm
27,610 24,930 8.0 gpm
Heating Capacity, BTU/H, 60oF EAT, EWT= Entering Water Temperature, LAT= Leaving Air Temperature BTU/H @120oF EWT (oF LAT) GPM Rating BTU/H @150oF EWT (oF LAT) GPM Rating BTU/H @180oF EWT (oF LAT) GPM Rating
22,700 (101oF) 1.8 gpm 34,400 (123oF) 1.8 gpm 41,070 (136oF) 1.6 gpm
28,800 (98oF) 2.3 gpm 43,600 (117oF) 2.3 gpm 58,700 (137oF) 2.3 gpm
30,600 (95oF) 2.0 gpm 46,500 (113oF) 2.0 gpm 62,500 (131oF) 2.0 gpm
49,200 (98oF) 52,400 (94oF) 3.6 gpm 3.6 gpm 74,800 (117oF) 79,600 (112oF) 3.6 gpm 3.6 gpm 100,600(136oF) 107,200 (130oF) 3.6 gpm 3.6 gpm
5.0 kW 17,500
5.0 kW 17,570
7.0 kW 24,540
7.0 kW 24,690
750 1/6 20x20
800 1/4 20x20
1,200 1/2 20x20
1,400 1/2 20x20
Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60
3.0 kW 10,760
Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower Filter, 1” deep throw away, Qty. 1
500 1/8 20x20
Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
1-5 lbs/hr 1.8 kW
Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm
3/1.5 333
3/1.5 500
3/2.0 400
3/3.0 400
3/3.0 467
3/4 1/4 1/2
3/4 1/4 3/4
3/4 1/4 3/4
3/4 1/4 3/4
3/4 1/4 3/4
125
125
150
155
155
Connection Sizes Condensate drain Humidifier Inlet Chilled water connection, OD
Physical Data Dimensions-- see page 15 for details Approximate weight, lbs.
AeroSys, Inc.
11
Electrical Data Power Consumption at 208/1/60
Model
(12)
(18)
(24)
(30)
(36)
11.7 17.5 25
13.6 19.8 30
18.0 24.9 35
19.8 28.0 40
36.1 41.9 50
38.0 44.2 55
42.3 49.3 60
44.2 52.4 60
19.8 25.6 35
21.7 28.0 35
26.1 33.0 45
27.9 36.1 50
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
7.0 13.5 20
8.8 15.8 25
12.9 20.9 35
14.6 24.0 40
31.3 37.9 45
33.2 40.2 50
37.3 45.3 60
39.0 48.4 60
15.1 21.6 30
16.9 24.0 35
21.0 29.0 40
22.7 32.1 50
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
8.6 13.5 20
10.5 15.8 25
15.2 20.9 35
17.3 24.0 40
32.9 37.9 45
34.9 40.2 50
39.6 45.3 60
41.7 48.4 60
16.7 21.6 30
18.6 24.0 35
23.3 29.0 40
25.4 32.1 50
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
Air Cooled Self Contained, CM-( )-AS series Cooling only Full Load Amps 10.1 Minimum Circuit Amps 14.5 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 22.3 Minimum Circuit Amps 26.6 Maximum Overcurrent Protection 35 Humidification option only (and cooling mode) Full Load Amps 18.2 Minimum Circuit Amps 22.6 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
Water Cooled, CM-( )-W series Cool only Full Load Amps 7.5 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 19.7 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 15.6 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
Glycol Cooled, CM-( )-G series Cool only Full Load Amps 8.2 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 20.4 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 16.3 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
12
AeroSys, Inc.
Electrical Data Power Consumption at 208/1/60
Model
(12)
(18)
(24)
(30)
(36)
7.7 13.5 20
9.6 15.8 25
14.0 20.9 35
15.8 24.0 40
32.1 37.9 45
34.0 40.2 50
38.3 45.3 60
40.2 48.4 60
15.8 21.6 30
17.7 24.0 35
22.1 29.0 40
23.9 32.1 50
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
Air Cooled Remote Condenser, CM-( )-AR series Cool only Full Load Amps 7.9 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 20.1 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 16.0 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
Air Handler with Remote Condensing Unit, CM-( )-AH series Cool only Full Load Amps 1.5 Minimum Circuit Amps 1.9 Maximum Overcurrent Protection 5 Heat/Reheat option only (in dehumidification mode) Full Load Amps 13.7 Minimum Circuit Amps 14.1 Maximum Overcurrent Protection 15 Humidification option only (and cooling mode) Full Load Amps 9.6 Minimum Circuit Amps 10.0 Maximum Overcurrent Protection 10 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
1.5 1.9 5
2.2 2.8 6
4.0 5.0 8
4.0 5.0 8
21.8 22.2 25
26.6 27.1 30
28.4 29.4 35
28.4 29.4 35
9.6 10.0 10
10.3 10.9 15
12.1 13.1 15
12.1 13.1 15
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
1.5 1.9 5
2.2 2.8 6
4.0 5.0 8
4.0 5.0 8
21.8 22.2 25
26.6 27.1 30
28.4 29.4 35
28.4 29.4 35
9.6 10.0 10
10.3 10.9 15
12.1 13.1 15
12.1 13.1 15
34.0 34.4 35
34.7 35.3 35
36.5 37.5 40
36.5 37.5 40
Chilled Water Air Handler, CM-( )-CW series Cool only Full Load Amps 1.5 Minimum Circuit Amps 1.9 Maximum Overcurrent Protection 5 Heat/Reheat option only (in dehumidification mode) Full Load Amps 13.7 Minimum Circuit Amps 14.1 Maximum Overcurrent Protection 15 Humidification option only (and cooling mode) Full Load Amps 9.6 Minimum Circuit Amps 10.0 Maximum Overcurrent Protection 10 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25
AeroSys, Inc.
13
Outside Heat Exchangers 9
Header
A
Electric Box
15 in 9
E Model ACC-014 ACC-018 ACC-023 ACC-032 ACC-049
/16 Mounting Mounting Legs (4)
F
Motor Data (208/1/60) # @ fan dia. Hp Amps 1@ 18 in 1/3 3.2 1@ 18 in 1/3 3.2 1@ 18 in 1/3 3.2 1@ 22 in 1/3 3.2 1@ 22 in 1/3 3.2
Model ACC-014 ACC-018 ACC-023 ACC-032 ACC-049
/16 Lifting
A 16-1/4 16-1/4 16-1/4 18-1/8 18-1/8
Ref. Charge R-22 (lbs.) 0.45 0.45 0.90 1.20 1.95
Cabinet Dimensions B C E 28 25-9/16 26-5/8 9 28 25- /16 26-5/8 9 28 25- /16 26-5/8 9 33 30- /16 31-5/8 9 33 30- /16 31-5/8
F 26-13/16 26-13/16 26-13/16 31-13/16 31-13/16
Net 78 80 86 107 116
THR @ oF ITD 20oF 25oF 13.5 16.8 17.8 22.3 22.8 28.6 31.2 39.0 48.9 60.5 Weight Shipping 97 99 105 128 137
30oF 20.2 26.7 34.3 46.8 72.5
Connections Liquid/Gas 7/8” OD 7/8” OD 7/8” OD 7/8” OD 7/8” OD
Remote Condensing Units BTU/H’s
Electrical Data
Dimensions
Weight
Connections
FLA/MCA/MOP
H x W x D (in)
net/ship (lb)
Liquid/Suction
10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45
23x291/2x181/2 23x291/2x181/2 23x291/2x181/2 23x291/2x181/2 23x291/2x181/2
70/75 75/81 79/85 91/102 70/75
3
12,500 20,300 25,500 30,000 35,400
10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45
285/8x26x181/2 285/8x26x181/2 285/8x26x181/2 285/8x26x181/2 285/8x26x181/2
70/75 75/81 79/85 91/102 70/75
3
12,500 19,900 25,400 30,000 35,900
10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45
32x233/4x181/2 32x233/4x181/2 32x233/4x181/2 32x233/4x181/2 32x233/4x181/2
70/75 75/81 79/85 91/102 70/75
3
“R” (Runt) Series THDC-12-R THDC-18-R THDC-24-R THDC-30-R THDC-36-R
12,500 20,200 25,200 30,000 35,300
“S” (Short) Series THDC-12-S THDC-18-S THDC-24-S THDC-30-S THDC-36-S
“T” (Tall) Series THDC-12-T THDC-18-T THDC-24-T THDC-30-T THDC-36-T ARI 210/240 conditions
14
AeroSys, Inc.
/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3
/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3
/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3
Dimensional Data Self-Contained Air Cooled CM-( )AS Series Units 511/2
237/8
17 211/8
101/4
81/4
451/8 473/4 22
CM-( )-W, G, CW, AR, AH Series Units
511/2
203/8 237/8
Field Connection Area for Condenser and Chilled Water Pipes
451/8 473/4
DUCTED Self-Contained Air Cooled CM-( )AS Series Units
14.1
10.0
10.3
6.9 8.3
16
.5
AeroSys, Inc.
Pump Package Performance Curves Head
PA_-005 (1/2 HP)
(ft)
1.25x1x5 @ 3500 rpm
Head
120
PA_-007 (3/4 HP)
(ft) 5.00 in
100
31
42
50
1.25x1x5 @ 3500 rpm
Head
120 57
5.00 in
63 64
80
100
63
31
42
50
57
61
5.00 in
63 57
64
3 hp
60
100
63
80
50
20
40
16
32
64
63 61 57
2 hp
40
0.75 hp 20
48
64
Flow (usgpm)
Ethylene Glycol: 40%, sg = 1.06
1.5 hp
3.25 in
1 hp
0.5 hp
80
0.333 hp 0.25 hp
System
0.75 hp
20
0 0
3 hp 50
60 3.88 in
1.5 hp
3.25 in 1 hp
0.333 hp 0.25 hp
System
61
2 hp
0.5 hp
0
57
80
50
3.56 in
1 hp
50
3 hp
60
0.75 hp
42
63
2 hp
3.30 in 40 3.25 in
31
61 57
1.5 hp
1.25x1x5 @ 3500 rpm 120
61
0
PA_-010 (1 HP)
(ft)
61
16
32
48
64
80
System
0
Flow (usgpm)
Ethylene Glycol: 40%, sg = 1.06
0.5 hp 0.333 hp 0.25 hp
0
16
32
48
64
Single and Dual Pump Packages L S PANE ACCES Electrical) ps &
tlet Pump Ou outs)
24"
(Knock
(Pum
let Pump Ints) ou (Knock
5"
36"
20"
38" 3/4"
REAR / RIGHT / TOP VIEW
FRONT / LEFT / TOP VIEW
Other AeroSys Products AeroCon THDC Series contrifugal condensing in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCon THHP Series heat pumps in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCool DDX Series D.X. air handlers in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCon Centrifugal condensing units from 3 to 5 tons AeroCool DCW Series chilled water air handlers in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroPure Refrigerants, certified to ARI 700.
Represented by:
Accepted for Use City of NY Dept. of Bldgs
MEA-371-05-E Specifications are subject to change without notice
16
Form CM-1208 Rev.0
AeroSys, Inc.
80
Flow (usgpm)
Ethylene Glycol: 40%, sg = 1.06