V4043, V4044 Valves; V8043, V8044 Zone Valves INSTALLATION INSTRUCTIONS
APPLICATION
flow in the direction of the arrow. Reversal of the powerhead will result in damage to the gear train. On 24V systems, never jumper the valve coil terminals even temporarily. This may burn out the heat anticipator in the thermostat.
These valves consist of an actuator motor and valve assembly for controlling the flow of hot and/or cold water. The V4043 and V8043 provide two-position, straightthrough control of supply water. The V4044 and V8044 provide two-position, diverting control of supply water. The valves are designed for use with fan coil and other units requiring quiet, compact water valves. The V8043E and F also control supply water for baseboard radiators and convectors. The V4043E and V8043J provide straight-through control of steam only. Models are available with 125 or 300 psi operating pressure.
IMPORTANT Use this valve in hydronic heating systems which do not contain dissolved oxygen in the system water. The dissolved oxygen, which is found in systems that have a frequent source of makeup water, causes the rubber plug inside the valve to deteriorate and eventually fail.
INSTALLATION
LOCATION Install the valve in an area with adequate clearance to:
When Installing this Product... 1. 2. 3. 4.
Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions
CAUTION 1. 2.
Disconnect power supply before connecting wiring to prevent electrical shock of equipment damage. Normally it is not necessary to remove the powerhead from the valve body during installation. If the valve must be disassembled, be certain that it is reassembled with the water
3.
— — — —
Move the manual opening lever on the side of the powerhead. Remove the powerhead cover. Wire the powerhead. Replace the powerhead motor.
The valve location should be in an area where the temperature does not exceed the maximum valve operating temperature as shown in Fig. 1. The maximum valve operating temperature depends on the maximum ambient temperature at the valve location and the maximum fluid temperature. Using the graph in Fig. 1, the maximum valve operating temperature can be found as follows: 1. 2. 3.
Measure ambient temperature at valve and locate this temperature on the ambient temperature scale on the graph. Draw a line from this ambient temperature, parallel with the fluid temperature scale, to the maximum fluid temperature line. Draw a line from this point down to the fluid temperature scale to find maximum operating temperature. (Note the example, shown by the dashed line in Fig. 1).
Place Bar Code Here 95-6983-11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
MAXIMUM AMBIENT TEMPERATURE LINE
210 (99) 200 (93) 190 (88) 180 (82)
MAXIMUM FLUID TEMPERATURE LINE
AMBIENT TEMPERATURE
170 (77) 160 (71) 150 (66) EXAMPLE: 150°F (66°C) IS THE AMBIENT TEMPERATURE AT THE VALVE, 235F (113C) IS MAXIMUM FLUID TEMPERATURE.
140 (60) 130 (54) 120 (49) 110 (43) 100 (38) 90 (32) 80 (27)
DEGREES F
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
DEGREES C
(21)
(27)
(32)
(38)
(43)
(49)
(54)
(60)
(66)
(71)
(77)
(82)
(88)
(93)
(99)
(104)
(110)
(116)
(121)
FLUID TEMPERATURE
M8164
Fig. 1. Maximum temperature characteristics of valves.
MOUNTING The valve can be mounted in any position on a vertical line. If the valve is mounted horizontally; the powerhead must be even with or above the center line of the piping. Make sure that enough room is provided above the powerhead to remove the cover for servicing.
Fig. 3. Inlet and outlet ports on straight-through and diverting valves.
HORIZONTAL PIPING VERTICAL PIPING
M10162A
Fig. 2. Mounting positions. Mount the valve directly in the tube or pipe. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body. On diverting valves, the three fittings or ports are labeled on the bottom of the valve body casting. See Fig. 3. Port AB is the inlet port and is open at all times. Port A is closed when the valve is de-energized; port B is open 95-6983—11
when the valve is de-energized. Refer to the equipment manufacturer’s instructions to determine which port (A or B) should be connected to the coil bypass.
FLARE FITTING MODELS Use new, properly reamed pipe, free from chips. The valve body is threaded for standard 5/8 in. OD copper, 45 degree SAE flare fitting nuts. These nuts are not furnished with the valve and must be obtained separately. SWEAT COPPER MODELS 1. Use new, properly reamed pipe, free from dents or corrosion. 2. Place the valve onto the pipe. Set the manual opening lever to MAN. OPEN position before applying heat. This protects the plug inside the valve by removing it from the seat. 2
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES 3. 4.
IMPORTANT: Take care not to burn the plastic portion of the composite adapter plate when soldering. Sweat the joints, keeping the outer surface free from solder. DO NOT use silver solder because of the high melting temperature required.
1. Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage. 2. Disconnect the leadwires to the powerhead at the terminal block or conduit connection. Remove the conduit or cable connector if fitted. Label each wire for rewiring later. 3. Drain the water from the system. 4. Remove the old powerhead from the valve body (Fig. 4) a. Place the manual opening lever (normally closed models only) on the old powerhead in the MAN. OPEN position (see Fig. 4A). b. Remove the cover (Fig. 4B). c. With the cover off, remove the four screws securing the powerhead to the valve body. d. Lift the powerhead off the valve body (Fig. 4C). e. Remove the O-ring from the top of the valve body.
To Install Replacement Powerhead SYSTEMS WITH OLD STYLE VALVE BODIES (SERIES 1-5) To install a replacement powerhead in a system with an old style body (series 1-5), the valve body must be converted to accept the new powerhead using Part No. 40003918 Conversion Kit. The kit includes a metal plate with a driveshaft and rubber plug, O-ring, and four screws. IMPORTANT Converting the valve body for use with the new powerhead does not require removal of the valve body from the pipeline. However, it is necessary to drain the water from the system before beginning the conversion. A
C
AUTO
MAN OPEN
MANUAL OPENING LEVER 6
51 3F 10 V804 /60 CY 24V 50 60 CY P@ .32 AM NADA CA IN MADE
A
B
A COVER RETAINING SCREW
B
6
51 3F 10 V804 /60 CY 24V 50 60 CY P@ .32 AM DA CANA IN MADE
A B M10174
Fig. 4. Remove old powerhead from systems using old style valve bodies 5.
Install 40003918 Conversion Kit (Fig. 5) a. Insert the new O-ring in the valve body. b. Place metal plate with the rubber plug on top of the valve body. Make sure the guide pins on the underside of the metal plate fit into the recesses on the valve body. c. Secure the metal plate to the valve body with the four screws (two sets) provided. One set of screws has heads with recessed threads to
insert screws for mounting the new powerhead; insert this set into the larger screw openings. The other set has domed heads; insert this set into the smaller screw openings. Each set of screws must be inserted in opposite corners of the metal plate so the screws sit flat on the plate. Make sure the guide pins on the plate fit into the recesses on the valve body.
3
95-6983—11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
HEX-NUT SCREW WITH DOMED HEADS (2) HEX-NUT SCREWS WITH RECESSED THREADS AND SHOULDER SHANK (2)
c. Secure the powerhead to the valve body with the two screws provided. d. If fitted, reconnect the conduit or cable. Reconnect the leadwires at the powerhead. e. Replace the powerhead cover. 7. Turn on power.
SECURING SCREW (2)
BRASS ADAPTER PLATE
O RING 6
F 1036 V8043 Y /60 C 24V 50 60 CY P M @ .32 A DA A N A C E IN MAD
LOCATING RECESSES (3)
REMOVABLE HEAD
A B
SHAFT
VALVE BODY
M32317
Fig. 5a. Install 40003918 conversion kit with brass adapter plate. A B HEX-NUT SCREW WITH DOMED HEADS (2) HEX-NUT SCREWS WITH RECESSED THREADS AND SHOULDER SHANK (2)
REMOVABLE HEAD VALVE BODY ASSEMBLY M10173
STEEL PLATE
PLASTIC PLATE
LOCATING RECESSES (3)
A B M32316
Fig. 5b. Install conversion kit with composite (steel & plastic) adapter plate. 6.
Install new powerhead (see Fig. 6) a. Place the manual opening lever (normally closed models only) on the new powerhead in the MAN. OPEN position. b. Fit the powerhead onto the valve body, ensuring that the shaft seats correctly. The powerhead should be aligned so that the manual opening lever or slot for lever is at the port A end of the valve body.
95-6983—11
SYSTEMS WITH NEW STYLE VALVE BODIES (SERIES 6) IMPORTANT On a new style valve body that has been converted to accept the new powerhead, it is not necessary to drain the system if the valve body remains in the pipeline.
O RING
VALVE BODY
Fig. 6. Install new powerhead.
1. Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage. 2. Disconnect the leadwires to the powerhead at the terminal block or conduit connection. Remove the conduit or cable connector, if fitted. Label each wire for rewiring later. 3. Remove the old powerhead (see Fig. 7): a. Place the manual opening lever (normally closed models only) on the old powerhead in the MAN. OPEN position (Fig. 7A). b. Remove the screw securing the cover to the powerhead (Fig. 7B). c. Lift off the cover from the powerhead. d. Remove the two screws securing the powerhead to the valve body (Fig. 6). e. Lift the powerhead off the valve body.
4
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
B
A COVER RETAINING SCREW
6
36 3F 10 V804 /60 CY 24V 50 60 CY P@ .32 AM DA CANA E IN MAD
AUTO
MAN OPEN
MANUAL OPENING LEVER
A
B
A
B M10161
Fig. 7. Remove old powerhead cover from systems using new style valve bodies. 4.
5.
Install the new powerhead (see Fig. 6): a. Place the manual opening lever (normally closed models only) on the new powerhead in the MAN. OPEN position. b. Fit the powerhead onto the valve body, ensuring that the shaft seats correctly. The powerhead should be aligned so that the manual opening lever or slot for lever is at the port A end of the valve body. c. Secure the powerhead to the valve body with the two screws provided. d. If fitted, reconnect the conduit or cable. Reconnect the leadwires to the powerhead. e. Replace the powerhead cover. Turn on the power.
THERMOSTAT (TYPICALLY T87F)
TO LINE
TO CIRCULATOR OR ANOTHER VALVE
YELLOW LEADS
RED LEADS
MOTOR
AUXILIARY SWITCH
WIRING
M5953
Fig. 8. Typical wiring for V8043E, V8044E.
Disconnect the power supply before connecting wiring to prevent electrical shock or equipment damage. All wiring must comply with local codes and ordinances. Connections to the individual valves are shown in Fig. 89. See Fig. 10 through 16 for typical hookups.
R
THERMOSTAT (TYPICALLY T87F) TO CIRCULATOR OR ANOTHER VALVE
If replacing a Taco, Dole, Flair or White Rodgers 3-wire valve with a 2-wire V8043E or F, see Fig. 17 through 29. Check that the pressure rating of the new valve is appropriate for the application.
END SWITCH
TH
TR
TH
TR
1 L1 (HOT) L2 24V TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M5952
Fig. 9. Typical wiring for V8043F. 5
95-6983—11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
T822
T822
T822
T822
L1 (HOT) L2
T822
L1 (HOT) L2
1
1
2
2
2
V8043A
V8043A
V8043A
2
2
2
V8043E
V8043E
V8043E
3
3
3
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2
T822
CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.
M10168
Fig. 10. T822 thermostat, V8043A valve hookup.
T T822
T822
B1
T
T822
TO BURNER CONTROL CIRCUIT 1
L1 (HOT) L2
B2
2
C1
C2
1 2
2
2
V8043E
V8043E
V8043E
3
3
3
CIRCULATOR
HIGH LIMIT
L4006A
TO OIL PRIMARY CONTROL OR TO TRANSFORMER AND LOW VOLTAGE GAS VALVE
CIRCULATOR 1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
3
CONNECT V8043E RED LEADWIRES TO L1 (HOT) LINE AND PRIMARY CONTROL.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
3
CONNECT V8043E RED LEADWIRES TO AQUASTAT®.
M10170
Fig. 13. T822, V8043E zone hookup for gas or oil with or without domestic hot water. Without domestic hot water, use L8148J for gas, L8148A for oil. With domestic hot water, use L8124E for gas, L8124A or C for oil.
ZONE 1 M10169
ZONE 2
HEATING COOLING THERMOSTAT
ZONE 3
T87F
T87F
Fig. 11. T822, V8043E zone hookup for gas or oil. No domestic hot water.
V4044, V8044 VALVE OPERATOR
1
T87F
V8043F
V8043F
V8043F
END SWITCH
END SWITCH
END SWITCH
TH-TR TH TR
TH-TR TH TR
TH-TR TH TR
ADD JUMPER TO EACH VALVE
RED
1
BLUE
TV
TO POWER
T
Z
2
1
L8124G
YELLOW
C1
C2
L1 (HOT) L2
B1 B2
120 V POWER SUPPLY
MOTOR
TO CIRCULATOR 1 AQUASTAT® CHANGEOVER CONTROL SWITCHES TO HEATING (RED) AT FLUID TEMPERATURE OF 85F (29C) MAX TO COOLING (BLUE) AT FLUID TEMPERATURE OF 60F (18C) MIN.
M5954
Fig. 14. Typical 3-zone system. Use an AT87A transformer to power up to 5 more zone valves.
M10171
Fig. 12. Wiring diagram for V4044 and V8044 with Aquastat changeover control.
95-6983—11
TO BURNER CIRCUIT
6
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
CONNECTIONS FOR V8043E (LEADWIRE MODEL) ZONE V8043E
ZONE 2
ZONE 3
END SWITCH
END SWITCH
YELLOW
YELLOW
RED
RED
ZONE 1 END SWITCH
RED
TO CIRCULATOR CONTROL CIRCUIT
B
V8043F
V8043F
RED
TH-TR
TH
TR
TH-TR
ZONE 4 END SWITCH
V8043F
TH
TH-TR
TR
TH
V8043F
TH-TR
TR
TH
TR
B ZONE 1
R
ZONE 4
ZONE 3
ZONE 2 B
B
B
B
B
B
B
B
R
R
R
R
W
W
W
W
BR
BR
BR
BR
YELLOW W YELLOW W775A PANEL
BR
INTEGRAL TRANSFORMER L1 (HOT)
POWER SUPPLY
L2 W775A PANEL
T87F
T87F
T87F
T87F
M5980
Fig. 15. Typical 4-zone system. Use an additional W775A to power up to 4 more zone valves.
ZONE 2
ZONE 1
T87F
T87F
ZONE 4
ZONE 3 T87F
T87F
V8043F
V8043F
V8043F
END SWITCH
END SWITCH
END SWITCH
TH-TR
TH
TH-TR
TR
TH
TH-TR
TR
AT87A TRANSFORMER
TO BURNER AND / OR CIRCULATOR CIRCUIT
ZONE 5
TH
TR
L1 (HOT) L2 1
1
T87F
V8043E
V8043E
YELLOW
YELLOW
YELLOW
YELLOW
RED
RED
RED
RED
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
NOTE: IF CODE PERMITS, V8043E AND V8043F CAN BE USED INTERCHANGEABLY WHEN WIRED AS SHOWN.
M10164
Fig. 16. Typical 5-zone system. Use an AT87A transformer to power up to 5 more zone valves.
How to Replace a Taco 3-Wire Valve with a Honeywell 2-Wire Valve
V8043E C YELLOW
1
L1 (HOT)
THERMOSTAT
1 A
L1 (HOT)
TACO VALVE
TO AUXILIARY CIRCUITS
D TO AUXILIARY CIRCUITS
2 D
3
E
RED
RED
E
1 1
YELLOW
THERMOSTAT
1 C
B
L2
B
L2
A
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M10163
M5958
Fig. 17. Existing Taco System. (Wires are identified by letters for easy correspondence to wires on Figs. 18 & 19.)
Fig. 18. Wiring a Honeywell V8043E to a Taco System. (Wires are identified by letters for easy correspondence to wires on Fig. 17.)
7
95-6983—11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
V8043F
V8043F
END SWITCH
END SWITCH
D
1 L1 (HOT)
TO AUXILIARY CIRCUITS
E
C
1 L1 (HOT) L2
L2 TH-TR TH
B
TR
A
F
TO TERMINALS T, T ON BURNER RELAY
E
A
TH-TR TH
C
TR
D
B THERMOSTAT
THERMOSTAT V8043F
V8043F
END SWITCH
END SWITCH
L1 (HOT)
1
D
1
E
C
L1 (HOT)
TO AUXILIARY CIRCUITS
L2
B
TH-TR TH
L2 TH-TR TH
TR
A
F
TO TERMINALS T, T ON BURNER RELAY
E
A
TR
D
C
B THERMOSTAT 1
THERMOSTAT 1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M5960
Fig. 19. Wiring a Honeywell V8043F to a Taco System (2 options). (Wires are identified by letters for easy correspondence to wires on Fig. 17.)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M5966
Fig. 22. Wiring a Honeywell V8043F to a Dole system (2 options). (Wires are identified by letters for easy correspondence to wires on Fig. 20.)
How to Replace a Flair 3-Wire Valve with a Honeywell 2-Wire Valve
How to Replace a Dole 3-Wire Valve with a Honeywell 2-Wire Valve
FLAIR VALVE
L2
A
1 L1 (HOT)
A
L1 (HOT)
DOLE VALVE 3
2
D
1
4
TO TERMINALS T, T ON BURNER RELAY
F
2 1
B
4
C
B
L2
E
3
1
5 D
C
THERMOSTAT E
F
THERMOSTAT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
1
TO TERMINALS T, T ON BURNER RELAY M5977
Fig. 20. Existing Dole System. (Wires are identified by letters for easy correspondence to wires on Figs. 21 & 22.)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M5978
Fig. 23. Existing Flair System. (Wires are identified by letters for easy correspondence to wires on Figs. 23 & 24.)
V8043E V8043E A
1 L1 (HOT) L2
B
THERMOSTAT TO TERMINALS T, T ON BURNER RELAY
L1 (HOT)
YELLOW
C
D
E F
L2 YELLOW
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
YELLOW
C
TO TERMINALS T, T ON BURNER RELAY
RED
D
E F
YELLOW
RED RED
RED
M5965
Fig. 21. Wiring a Honeywell V8043E to a Dole System. (Wires are identified by letters for easy correspondence to wires on Fig. 20.) 95-6983—11
B
THERMOSTAT
1 1
A
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M5965
Fig. 24. Wiring a Honeywell V8043E to a Flair System. (Wires are identified by letters for easy correspondence to wires on Fig. 23.)
8
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
V8043F
V8043F
END SWITCH
F
1 L1 (HOT)
E
A
L2
B
TH-TR TH
END SWITCH TO TERMINALS T, T ON BURNER RELAY
2
1
TR
C
TO AUXILIARY CIRCUITS
L1 (HOT) L2
F
1
E
A
L2
B
TH-TR TH
THERMOSTAT TO TERMINALS T, T ON BURNER RELAY
END SWITCH 2
TR
1
D
C
THERMOSTAT 1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M5966
Fig. 25. Wiring a Honeywell V8043F to a Flair System (2 options). (Wires are identified by letters for easy correspondence to wires on Fig. 23.)
WHITE-RODGERS 1311 OR 1321 VALVE
5 4
L1 (HOT) L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
3
TAPE UNUSED END AND TUCK INTO HOLE.
M5713
V8043F
4
2
5
1
L2
3
TR
TH-TR TH
TO AUXILIARY CIRCUIT
1 L1 (HOT)
6
6
TO AUXILIARY CIRCUITS
Fig. 28. Wiring a Honeywell V8043F to a WhiteRodgers System (one option).
How to Replace a White-Rodgers 3-Wire Valve with a Honeywell 2-Wire Valve WATER VALVE THERMOSTAT
4
3
V8043F END SWITCH
L1 (HOT)
6
5
THERMOSTAT
TR
TH
TH-TR
D
2
END SWITCH
TO AUXILIARY CIRCUIT
L1 (HOT) L2
1
TH
TH-TR 1
TR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M5711
6
5
Fig. 26. Existing White-Rodgers System.
3
4 THERMOSTAT
1 L1 (HOT) L2
2
5 3
6
YELLOW
4
1 L1 (HOT) L2
END SWITCH
L1 (HOT) L2
RED
THERMOSTAT
TO AUXILIARY CIRCUIT
1
YELLOW
TO AUXILIARY CIRCUIT
RED
TO AUXILIARY 2 CIRCUIT YELLOW TO 6 ON THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
3
TAPE UNUSED END AND TUCK INTO HOLE.
M5714
RED RED
Fig. 29. Wiring a Honeywell V8043F to a WhiteRodgers System (alternate option).
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
3
TAPE UNUSED END AND TUCK INTO HOLE.
M5712
Fig. 27. Wiring a Honeywell V8043E to a WhiteRodgers System. 9
95-6983—11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
OPERATION AND CHECKOUT Checkout
CAUTION
On 24 V systems, never jumper the valve coil terminals even temporarily. This may burn out the heat anticipator in the thermostat.
NORMALLY CLOSED MODELS With the manual opener set to AUTO and the powerhead energized, the valve is opened as shown in Fig. 30A. When the powerhead is de-energized, a spring-return mechanism drives the valve to the closed position as shown in Fig. 30B. The valve can also be opened with no electrical power by moving the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in the open position. The valve will return to the automatic position when the valve is energized. Auxiliary switch is not energized when the valve is manually opened. NORMALLY OPEN MODELS When the powerhead is de-energized, a spring-return mechanism drives the valve to the open position (Fig. 30A). When energized, the valve is closed as shown in Fig. 30B. A reverse-acting thermostat is required to control a normally open valve. NOTE: Inlet Port is stamped “A”, Outlet Port is stamped “B” on the valve body.
A IN OPEN POSITION A
B
A
OUT
IN
1. Raise the setpoint on the zone thermostat above the room temperature to initiate a call for heat. 2. Observe all control devices—the valve should open and the auxiliary switch should make the circuit to the circulator or other valve at the end of the opening stroke. 3. Lower the setpoint on the zone thermostat below the room temperature. 4. Observe the control devices. The valve should close and the auxiliary equipment should stop.
Service This valve should be serviced by a trained, experienced service technician. 1. If the valve is leaking, drain the system and check to see if the O-ring needs replacing. 2. If the gear train is damaged, replace the entire powerhead assembly. See the Installation section. If the motor is burned out, replace the motor. See Replacement Parts list in the TRADELINE® Catalog. NOTE: Honeywell zone valves are designed and tested for silent operation in properly designed and installed systems. However, water noises may occur as a result of excessive water velocity or piping noises may occur in high temperature (over 212° F [100° C]) systems with insufficient water pressure. NOTE: These hydronic valves are not suitable for use in open loop systems where there is air exposure.
B OUT CLOSED POSITION B
M5951
Fig. 30. V8043 operation for normally closed valve.
95-6983—11
10
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
11
95-6983—11
V4043, V4044 VALVES; V8043, V8044 ZONE VALVES