Boiler System Expansion Tanks
For Hydronic Heating, Radiant, Solar & Chilled Water Systems
EXTROL® Expansion Tanks Amtrol Inc. designed and patented the first Extrol® diaphragm expansion tank to control system pressure and help reduce energy consumption in heating and chilled water systems. Over five decades later, Extrol is still the world’s leading expansion tank and
Invented the indirect-fired Hot Water Maker®
Invented the pre-pressurized well tank
1963
1946
• Eliminates the need for a separate, automatic fill valve. • Tank pressure controls system fill. • Fully adjustable up to a maximum working pressure of 100 psig.
AMTROL registered ISO 9001
1980
FILL-TROL® System
• Factory pre-charge: 12 psig.
still proudly made in the USA.
American Tube Products founded in West Warwick, Rhode Island
Special Application Expansion Tanks
1992
Spring-Loaded Check Valve
Launched HydroMax™ Hot Water Makers
Introduced CH-Series Hot Water Makers
2009
Removable Strainer Cold Water Supply
2012
1/2˝ Compression Fitting Connection
1954
1967
Invented the diaphragm expansion tank
1991
2005
Invented the thermal expansion tank
Invented the refrigerant gas cylinder
Invented the composite metal LP tank
EXTROL
Specifications
• Accepts expanded water as system temperature rises to reduce pressure build-up.
Model Number
Tank Volume (Gallons)
• Factory pre-charge: 12 psig.
EX-15 EX-30 EX-60 EX-90
2.0 4.4 7.6 14.0
• Maximum working pressure: 100 psig. • Maximum operating temperature: 240°F. Automatic Air Vent eliminates system air
Max. Accept. Volume (Gallons)
A Diameter (Inches)
B Height (Inches)
System Connection (NPTM)
Shipping Weight (lbs.)
0.9 2.5 2.5 11.3
8 11 11 15
13 16 23 21
12
⁄ 1⁄2 1⁄2 1⁄2
5 9 14 23
System connection sets the point of no pressure change Water-tight reservoir for expanded water Butyl/EPDM diaphragm Sealed air cushion — factory pre-charged and 100% tested
System Connection (NPTM)
EXTROL Model
Air Vent Model
Air Purger Model
Shipping Weight (lbs.)
EX-1500-100 EX-1500-125 EX-3000-100 EX-3000-125 EX-6000-125 EX-6000-150
1 1 1⁄4 1 1 1⁄4 1 1⁄4 1 1⁄2
EX-15 EX-15 EX-30 EX-30 EX-60 EX-60
700-C 700-C 700-C 700-C 700-C 700-C
443 444 443 444 444 445
10 10 14 14 19 19
Sizing
Typical Installation
System Supply Flow-Check Valve
Circulator
Air Purger
Shut-Off Valve
Backflow Preventer
Shut-Off Valve
PressureRelief Valve
Extrol Expansion Tank
Boiler
Water Supply System Return
System Purge
System Connection (NPTF)
Shipping Weight (lbs.)
FT-109 FT-110 FT-111 FT-112
2.0 4.4 7.6 14.0
0.9 2.5 2.5 11.3
8 11 11 15
13 16 23 21
12
⁄ ⁄ 1⁄2 1⁄2
6 10 15 24
Fill Gate Stem
Note: A standard EXTROL tank is not interchangeable with a FILL-TROL tank. FT-109 is equivalent to EX-15; FT-110 is equivalent to EX-30; FT-111 is equivalent to EX-60 and FT-112 is equivalent to EX-90.
Combination Packages System FILL-TROL Connection Model (NPTF)
Model Number
Pressure Plate
FT-109-100 FT-109-125 FT-110-100 FT-110-125 FT-111-125
Diaphragm
1 11⁄4 1 11⁄4 11⁄4
RADIANT EXTROL®
• For high-efficiency radiant systems. • Plastic liner is compatible with barrier and non-barrier tubing. • Suitable for use in glycol applications. • Non-ferrous system connection for corrosion resistance.
• Maximum operating temperature: 200°F.
12
109 109 110 110 111
Air Vent Model
Air Purger Model
Shipping Weight (lbs.)
700-C 700-C 700-C 700-C 700-C
443 444 443 444 444
10 10 14 14 18
Specifications Model Number
Tank Volume (Gallons)
Max. Accept. Volume (Gallons)
RX-15 RX-30 RX-60
2.0 4.4 10.3
0.9 3.2 10.3
A B Diameter Height (Inches) (Inches)
8 11 15
13 16 19
System Connection
Shipping Weight (lbs.)
⁄ ⁄ 3⁄4 NPTF
5 9 23
1 2 NPTM 1 2 NPTM
Sizing Nominal Pex Tubing Size
Feet of Tubing
3/8"
1/2"
5/8"
3/4"
1"
1,000 5,000 7,500 10,000 14,000 18,000 22,000 30,000
RX-15 RX-15 RX-15 RX-15 RX-15 RX-30 RX-30 RX-30
RX-15 RX-15 RX-15 RX-30 RX-30 RX-60 RX-60 RX-60
RX-15 RX-15 RX-30 RX-30 RX-60 RX-60 RX-60
RX-15 RX-30 RX-30 RX-60 RX-60 RX-60
RX-15 RX-30 RX-60 RX-60
Contact Amtrol
Sizing based on: Fill Pressure 12 psig; Relief Pressure 30 psig; Average Temperature 120°F; System filled with water. For glycol applications, consult AMTROL Technical Support.
Air stem for pre-charge adjustment
PressureReducing Valve
B Height (Inches)
Automatic Shut-Off Valve
• Maximum working pressure: 100 psig.
Model Number
Deep-drawn steel tank
Air Vent
A Diameter (Inches)
• Factory pre-charge: 12 psig.
Combination Packages
Air Purger separates air from water
Model Number
Max. Accept. Volume (Gallons)
Expansion Bypass
O-Ring Seal System Pressure Above Diaphragm
Tanks on Tour™ mobile education center
Automatic Shut-Off Valve Spring
Specifications Tank Volume (Gallons)
Boiler Net Output in 1000’S of BTU/Hr.
Finned Tube Baseboard or Radiant Panel
Convectors or Unit Heaters
Radiators Cast Iron
Baseboard Cast Iron
MBH
Use Model
Use Model
Use Model
Use Model
EX-15 EX-15 EX-30 EX-30 EX-30 EX-30 EX-60 EX-60 EX-60 EX-90 SX-30V SX-30V
EX-15 EX-15 EX-30 EX-30 EX-60 EX-60 EX-60 EX-60 EX-90 SX-30V SX-30V SX-40V
25 50 75 100 125 150 175 200 250 300 350 400
EX-15 EX-30 EX-30 EX-60 EX-60 EX-90 SX-30V SX-30V SX-30V SX-30V SX-40V SX-40V
Specifications
SOLAR EXTROL®
Type of Radiation
EX-15 EX-30 EX-60 EX-60 EX-90 EX-90 SX-30V SX-30V SX-40V SX-40V SX-60V SX-60V
Sizing based on: 12 psig Fill; 30 psig Relief Valve; 200°F Average Temperature. For sizing with fluids other than water, visit amtrol.com, download the AMTROL App or consult AMTROL Technical Support.
• For high-efficiency solar systems. • Suitable for use in glycol applications. • Factory pre-charge: 25 psig. • Maximum working pressure: 150 psig. • Maximum operating temperature: 250°F.
Model Number
Tank Volume (Gallons)
Max. Accept. Volume (Gallons)
A Diameter (Inches)
B Height (Inches)
System Connection (NPTM)
Shipping Weight (lbs.)
SE-15 SE-30 SE-60
2.0 4.4 7.6
0.9 2.5 2.5
8 11 11
13 16 23
12
⁄ ⁄ 1⁄2
5 9 14
12
For Precise Sizing, visit www.amtrol.com or consult AMTROL Technical Support.
Sizing System Volume (Gallons)
140°F
160°F
180°F
200°F
220°F
10 20 30 40 50
SE-15 SE-30 SE-30 SE-60 SE-60
SE-15 SE-30 SE-30 SE-60 SE-60
SE-15 SE-30 SE-60 SE-60
SE-15 SE-30 SE-60
SE-15 SE-30 SE-60
Average System Operating Temperature
Contact Amtrol
Sizing based on: 50% Water and Propylene Glycol Max; 25 psig Fill; 50 psig Releif Valve. For other applications, consult AMTROL Technical Support.
EXTROL® Floor-Standing Models Extrol floor-standing models are designed for large residential and light commercial applications. These non-ASME tanks are available in sizes up to 86 gallons and can be used with high output boilers up to 1,500,000 BTU's. ASME Commercial tanks are also available and can be found in catalog MC 2682.
EXTROL SX Series
Specifications
• Factory pre-charge: 12 psig. • Maximum working pressure: 100 psig. • Maximum operating temperature: 240°F.
Model Number
Tank Volume (Gallons)
Max. Accept. Volume (Gallons)
A Diameter (Inches)
B Height (Inches)
System Connection (NPTF)
Shipping Weight (lbs.)
SX-30V SX-40V SX-60V SX-90V SX-110V SX-130V SX-160V
14 20 32 44 62 81 86
11.3 11.3 11.3 34.0 34.0 34.0 46.0
15 15 15 22 22 22 26
25 33 48 36 47 56 47
1 1 1 11⁄4 11⁄4 11⁄4 11⁄4
25 33 43 69 92 103 123
Sizing Boiler
Type of Radiation and Piping System
Finned Tube Net Output in Baseboard or Radiant 1000’s of BTU Panels with Series Loop System
Typical Installation Air Vent
Air Separator
System Supply Flow-Check Valve
PressureReducing Valve
Backflow Preventer Shut-Off Valve
Shut-Off Valve
System Purge
System Return
Circulator PressureRelief Valve
Extrol Expansion Tank
Boiler
Water Supply
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1,000 1,100 1,200 1,300 1,400 1,500
SX- 30V SX- 30V SX- 30V SX-30V SX-30V SX-40V SX-40V SX-40V SX-40V SX-60V SX-60V SX-60V SX-60V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V
Convectors or Unit Heaters with One Pipe System
Radiators or One Pipe System
Cast Iron Radiators with Series Loop System
SX-30V SX-30V SX-30V SX-30V SX-40V SX-40V SX-40V SX-60V SX-60V SX-60V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-130V SX-130V
SX-30V SX-30V SX-40V SX-40V SX-60V SX-90V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V SX-110V SX-110V SX-110V SX-130V SX-160V SX-160V
SX-30V SX-40V SX-40V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V SX-110V SX-110V SX-110V SX-110V SX-130V SX-130V SX-160V SX-160V (2)SX-110V
Sizing based on: Average Boiler Water Volume; Average Water Volume; Fill Pressure 12 psig; Relief Pressure 30 psig For other boiler sizes or operating conditions, consult AMTROL Technical Support.