Series 1 to 3 tons of cooling capacity Air Cooled, Self-Contained Water Cooled Glycol Cooled Remote Air Cooled Condenser Air Handler with Remote Condensing Unit Chilled Water AeroSys, Inc. 929 Eldridge Drive Hagerstown, Maryland, 21740 Tel: 301-620-0002 Fax: 301-620-0685 www.aerosysinc.com AeroSys, Inc.

1

AeroSys, Inc.

Introduction AeroSys, Inc. is owned, managed and operated by a team with decades of experience in the air conditioning and refrigeration industry. AeroSys, Inc. is an independent equipment manufacturer, an EPA Certified Refrigerant Reclaimer and is DOT approved to re-qualify recovery cylinders. AeroSys, Inc. is comprised of two divisions: Air Conditioning Equipment Manufacturing, and Refrigerant Reclaim Services.

Air Conditioning Equipment The Air Conditioning Equipment division has designed and manufactured thousands of air conditioning systems: AeroCool Chilled Water Air Handlers AeroCon Thru-the-Wall Condensing Units & Heat Pumps CeilMate Ceiling Mounted Spot Coolers

Refrigerant Reclamation Services AeroSys is an EPA approved Certified Refrigerant Reclaimer under 40 CFR 82.164. AeroSys provides refrigerant reclamation and recertification services exclusively to HVAC wholesalers, and markets certified (ARI-700 ) reclaimed refrigerants under the AeroPure brand of refrigerant through our HVAC wholesale customers. AeroSys is also approved by the DOT for re-qualification of refrigerant cylinders under Title 49, Code of Federal Regulations, 49 CFR. We test, repair, repaint and re-certify refrigerant cylinders from 15# tanks up to 250# tanks.

Table of Contents Page Features 3-5 Air Cooled, Self-contained 6 Water Cooled 7 Glycol Cooled 8 Air Cooled, Remote Condenser 9

2

Page Air Handler, Remote Condensing 10 Chilled Water 11 Electrical Data 12-13 Outside Heat Exchangers, Condensing Units 14 Dimensional, Pump Package Data 15-16 AeroSys, Inc.

CeilMateTM Applications These systems are designed for commercial IAQ (Indoor Air Quality) applications where cooling, heating, humidifying, dehumidifying, ventilating and air conditioning solutions are required. CeilMateTM systems are ceiling mounted air conditioners, designed for reliable 24/7 operation. Typical critical applications include: Telecommunication switch-gear rooms Data centers Clean rooms Medical MRI and CAT scan rooms

Laboratories Bank and ATM kiosks Conference rooms LAN and data relay facilities

Product Nomenclature C M - 24 - AS CM = CeilMateTM

AS = Self-Contained Air Cooled W = Water Cooled Nominal Cooling Capacity G = Glycol Cooled (in thousands of BTU/H) AR = Remote Condenser, Air Cooled AH = Air Handling Unit CW = Chilled Water ( 2 ton self contained air cooled shown in above example)

System View Multi-speed Blower Motor

Oversized blower for low RPM and field flexibility

Electric Box Electrode Canister Humidifier

Scroll Compressor Thermal Expansion Valve

A-Frame Evaporator

Heater

Stainless Steel Condensate Drain Pan

Standard Features Refrigeration System

Cabinet The CeilMateTM is manufactured from aluminum for light weight, corrosion resistance and asthetics. The cabinet is structurally reinforced throughout to provide a stable and secure platform for the air conditioning components.

The unit’s evaporator section is insulated with high density, 2 lb/ft 2 thermal and acoustical insulation and sealed with self-extinguishing gasket material. Panels are fastened with quick release hardware to simplify internal access.

The CeilMateTM system includes all necessary components for safe and reliable operation. Easily accessible components include: thermal expansion valve, sight glass with moisture indicator, high and low pressure safety switches, refrigeration service access ports, and refrigerant drier/strainer. Self-contained air cooled, water and glycol cooled units are evacuated and shipped with a full refrigerant charge. Split systems include a refrigerant pump-down solenoid to prevent liquid slugging. Units are evacuated and charged with dry nitrogen.

A-Frame Coil The unit has a large face area coil to increase cooling efficiency and reduce power consumption. The copper tube, aluminum fin coil is mounted in a stainless steel condensate pan; a condensate safety switch guards against condensate overflow. Blower and Blower Motor The CeilMateTM incorporates a three speed direct drive blower motor in a draw-thru configuration for even air distribution across the coil . The large blower runs at a low rpm to minimize air noise and motor horse power consumption. The blower assembly is mounted to an internal chamber to further reduce noise levels. Electrical System The unit has a Class 2, 24VAC control circuit, all necessary contactors, fuses and/or circuit breakers for full operation. 24 VAC field connections and high voltage connections are provided through separate termination blocks in the electric box.

Compressor All D.X. systems, 1-1/2 ton and larger (CM18 thru CM-36) incorporate scroll compressors for high reliability, high efficiency and low noise. CM-12, one refrigerant ton, systems include the latest generation in reciprocating compressors. Compressors are mounted on vibration isolators to minimize noise transmission to the cabinet. Chilled Water Units Chilled water CeilMateTM systems are completely piped, wired and factory tested. Units include a 24 volt motorized zone valve for chilled water control. Water Regulating Valves All Water and Glycol cooled systems are delivered with factory installed, tested and adjusted 2-way water regulating valves, rated for 150 psi w.w.p, to maintain proper refrigerant head pressure.

Optional Features Ducted System The system is available in three air patterns: ducted return and supply, ducted return and “free” air discharge, or “free” return and ducted discharge. “Free” air is through the bottom of the unit the supply or return air pattern.

4

Ultra Violet Sterilization Light The unit incorporates a high intensity UV light to sterilize the air passing through the coil. As airborne mold bacteria are exposed to the UV light they are killed, preventing them from depositing active contaminants on the coil surface, the condensate pan and other internal surfaces. As the air is changed several times in the conditioned room, the contaminants are constantly being reduced in number.

AeroSys, Inc.

Optional Features CeilStat I

Electrode Canister Humidifier Integrated with the CeilStat, the humidifier provides humidification to your facility. An optional electrode canister is available providing state-of-the-art humidity control. The humidifier senses cylinder current draw, automatically flushing and filling the cylinder to control the mineral content of the water and humidity output The output is field adjustable from 1 to 5 lbs/hr. A “Change Cylinder” light alerts service personel when the humidifier output requires service. Electric Heat/Reheat Electric reheat is designed to offset the cooling effect of the dehumidification cycle; electric heat provides resistance heat regardless of the dehumidification cycle. The unit incorporates a factory installed, wired and tested nichrome wire heater. The heater has low voltage thermal safety cutouts, one pilot duty automatic resettable and a second power line fuselink (overtemperature) safety device for each bank of heat.

Electronic Thermostat/Humidistat The CeilStat I temperature and humidity controller incorporates temperature and humidity control in an attractive, wall mounted unit. This line powered, backlit system incorporates several salient features: * Manual override * 7 day programming * Programmable Fan * Adjustable Differential * Compressor Short Cycle Protection * Air Filter Monitor * 4 Hour reserve for settings * Status Indicators * Humidification in heat or air circulation modes * Hidden Service Level * Condensation Control CeilStat II Internet Accessible Thermostat/Humidistat The CeilStat II temperature and humidity controller incorporates temperature and humidity control in an attractive, wall mounted unit. This line powered, backlit system incorporates several salient features:

Condensate Pump options: External: The condensate pump is factory mounted, wired and integrated into the moisture removal system of the unit. In the event the condensate pump can not remove the water fast enough, an emergency shut-off switch locks out the compressor and humidifier until the condensate pump has emptied its sump. Internal: The condensate pump is factory mounted in the stainless steel condensate pan, wired and integrated into the moisture removal system of the unit. In the event the condensate pump can not remove the water fast enough, an emergency shut-off switch locks out the compressor and humidifier until the condensate pump has emptied its sump.

* Internet Connectivity for monitoring, management and configuration capability (requires secure customer internet access) * Easy installation * Backlit Graphic LCD display * EnergyStar Compliant * FCC Class B Compliant * Failsafe Temperature Switch * Adjustable Differential * Compressor Short Cycle Protection * E-Mail or Text Messaging Fault reporting * Status Indicators * Independent humidify and dehumidify control in cooling and heating modes * Hidden Service Level Alarms * Air Filter Monitor * Over/Under Temperature Alarm * High Humidity alarm * Customer selected contact closure

High Pressure Glycol/Water Systems Water cooled systems are available with factory installed, tested and adjusted 2way water regulating valves, rated for 350 psi w.w.p, to maintain proper refrigerant head pressure. 500 psi valves are also available.

AeroSys, Inc.

5

Air Cooled, Self-Contained Systems Model CM-( )-AS Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity

(12)

(18)

(24)

(30)

(36)

15,660 11,940

19,970 16,300

24,090 18,700

29,890 24,870

36,730 27,990

14,530 11,860

18,430 16,010

22,290 18,490

27,790 24,520

31,220 27,550

13,770 11,560

17,650 15,640

21,250 18,100

26,680 24,060

29,550 26,840

5.0 kW 17,500

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

750 1/6 20x20

800 1/4 20x20

1,200 1/2 20x20

1,400 1/2 20x20

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 Motor Horsepower 1/8 Filter, 1” deep throw away, Qty. 1 20x20

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm

2/2.7 185

2/3.2 234

2/3.2 250

2/3.7 324

2/3.7 378

1/4 750

1/2 1,000

1/2 1,200

1/2 1,400

1/2 1,600

------

------

Speed Control

------

------

Condenser Blower, DWDI, Direct Drive, 3 speed Motor Horsepower CFM @0.3” esp Condenser Coil, Aluminum Fin, Copper Tube Head Pressure Control (std)

Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)

1 Hp Recip. 20,100

1.5 Hp Scroll 25,750

2 Hp Scroll 31,160

2.5 Hp Scroll 38,980

3.0 Hp Scroll 43,800

3/4 1/4

3/4 1/4

3/4 1/4

3/4 1/4

3/4 1/4

215

220

245

260

270

Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper

Physical Data Dimensions-- see page 15 for details Approximate weight

6

AeroSys, Inc.

Water Cooled Systems Model CM-( )-W

(12)

(18)

(24)

(30)

(36)

18,090 13,030

21,850 17,160

26,520 19,910

33,260 26,520

38,380 30,200

16,600 12,810

20,180 16,870

24,450 19,530

31,230 26,290

36,010 29,950

15,530 12,430

18,980 16,390

23,010 19,000

29,380 25,540

33,880 29,110

5.0 kW 17,500

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

750 1/6

800 1/4

1,200 1/2

1,400 1/2

Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower

500 1/8

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) 2/2.7 2/3.2 Face Velocity, fpm 185 234 Filter, 1” deep throw away, Qty. 1 20x20 20x20

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

2/3.2 250 20x20

2/3.7 324 20x20

2/3.7 378 20x20

2 Hp Scroll

2.5 Hp Scroll

3.0 Hp Scroll

Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type

1 Hp Recip.

1.5 Hp Scroll

Water Cooled Condenser, Coaxial type, with 2 way water regulating valve GPM @ 85oF EWT Unit Pressure Drop (ft of H2O) Total Heat of Rejection (@75/62.5)

3.5 2.5 19,700

4.7 4.6 23,980

5.6 6.5 29,150

7.5 11.5 37,270

8.6 15.1 43,420

3/4 1/4 1/2

3/4 1/4 1/2

3/4 1/4 1/2

3/4 1/4 3/4

3/4 1/4 3/4

195

200

225

245

250

Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Condenser In/Out, Sweat OD

Physical Data Dimensions-- see page 15 for details Approximate weight

AeroSys, Inc.

7

Glycol Cooled Systems Model CM-( )-G Cooling Capacity, BTU/H 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity

(12)

(18)

(24)

(30)

(36)

15,850 12,160

19,800 16,470

23,930 18,840

30,280 25,390

35,550 29,340

14,350 11,860

18,020 15,910

22,340 18,630

28,500 25,110

33,340 28,860

13,280 11,410

17,610 15,730

20,990 18,090

26,780 24,250

31,760 28,150

5.0 kW 17,500

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

750 1/6

800 1/4

1,200 1/2

1,400 1/2

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower

500 1/8

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm Filter, 1” deep throw away, Qty. 1

2/2.7 185 20x20

2/3.2 234 20x20

2/3.2 250 20x20

2/3.7 324 20x20

2/3.7 378 20x20

1.5 Hp Scroll

2 Hp Scroll

2.5 Hp Scroll

3.0 Hp Scroll

Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type

1 Hp Recip.

Glycol Cooled Condenser, Coaxial type, with 2 way glycol regulating valve GPM @ 105oF EWT 3.5 4.0 5.3 6.9 Unit Pressure Drop (ft of H2O) 5.7 6.4 6.8 9.3 Total Heat of Rejection (@75/62.5) 17,540 22,790 28,230 36,080 Fluid Cooler size, 95oF Ambient FC-012 FC-018 FC-024 FC-030 Pump Package--See pages 15 and 16 for dimensional information and pump selection

8.8 15.6 42,470 FC-036

Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Condenser In/Out, Sweat OD

3/4 1/4 1/2

3/4 1/4 1/2

3/4 1/4 1/2

3/4 1/4 3/4

3/4 1/4 3/4

195

200

225

245

250

Physical Data Dimensions-- see page 15 for details Approximate weight

8

AeroSys, Inc.

Remote Air Cooled Systems Model CM-( )-AR

(12)

(18)

(24)

(30)

(36)

21,200 14,400

26,400 18,900

31,600 21,900

38,700 28,400

41,300 31,000

16,100 12,600

20,100 16,800

23,900 19,300

29,300 25,200

31,400 27,700

12,800 11,200

17,500 15,700

20,200 17,800

25,700 23,700

27,800 26,000

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

800 1/4 20x20

1,200 1/2 20x20

1,400 1/2 20x20

Cooling Capacity, BTU/H @ 125oF Condensing 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

5.0 kW 17,500

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 750 Motor Horsepower 1/8 1/6 Filter, 1” deep throw away, Qty. 1 20x20 20x20

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm

2/2.7 185

2/3.2 234

2/3.2 250

2/3.7 324

2/3.7 378

Remote Air Cooled Condenser, 95oF Ambient, fan cycling control standard Model (see page 14 for details)

ACC-018

ACC-023

ACC-032

ACC-032

ACC-049

1 Hp Recip. 17,500

1.5 Hp Scroll 25,750

2 Hp Scroll 31,160

2.5 Hp Scroll 38,980

3.0 Hp Scroll 43,800

3/4 1/4 1/2 3/8

3/4 1/4 1/2 3/8

3/4 1/4 1/2 3/8

3/4 1/4 3/4 3/8

3/4 1/4 3/4 3/8

175

180

205

210

220

Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)

Connection Sizes Condensate drain, PVC Humidifier Inlet, 1/4” copper Liquid line, Sweat OD Hot Gas line, Sweat OD

Physical Data Dimensions-- see page 15 for details Approximate weight

AeroSys, Inc.

9

Air Handler for Remote Condensing Systems Model CM-( )-AH

(12)

(18)

(24)

(30)

(36)

21,200 14,400

26,400 18,900

31,600 21,900

38,700 28,400

41,300 31,000

16,100 12,600

20,100 16,800

23,900 19,300

29,300 25,200

31,400 27,700

12,800 11,200

17,500 15,700

20,200 17,800

25,700 23,700

27,800 26,000

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

800 1/4 20x20

1,200 1/2 20x20

1,400 1/2 20x20

Cooling Capacity, BTU/H @ 45oF Suction 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

5.0 kW 17,500

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge 500 750 Motor Horsepower 1/8 1/6 Filter, 1” deep throw away, Qty. 1 20x20 20x20

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr 1-5 lbs/hr Power consumption 1.8 kW 1.8 kW 1.8 kW 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm

2/2.7 185

2/3.2 234

2/3.2 250

2/3.7 324

2/3.7 378

Remote Air Cooled Condensing Unit, 95oF Ambient, fan cycling control standard Model (see page 14 for details)

THDC-12

THDC-18

THDC-24

THDC-30

THDC-036

1 Hp Recip. 17,500

1.5 Hp Scroll 25,750

2 Hp Scroll 31,160

2.5 Hp Scroll 38,980

3.0 Hp Scroll 43,800

3/4 1/4 1/2 7/8

3/4 1/4 1/2 7/8

3/4 1/4 1/2 7/8

3/4 1/4 3/4 7/8

3/4 1/4 3/4 7/8

125

125

150

155

155

Compressor, Heat pump duty rated, R-22 system Nominal Horsepower Compressor type Total Heat of Rejection (Btu/h)

Connection Sizes Condensate drain Humidifier Inlet Liquid line connection, OD Suction line connection, OD

Physical Data Dimensions-- see page 15 for details Approximate weight, lbs.

10

AeroSys, Inc.

Chilled Water Air Handler Model CM-( )-CW

(12)

(18)

(24)

(30)

(36)

Cooling Capacity, BTU/H @ 45oF Entering Water Temperature 80oF DB/67oF WB, 50%RH Total Capacity Sensible Capacity 75oF DB/62.5oF WB, 50%RH Total Capacity Sensible Capacity 72oF DB/60oF WB, 50%RH Total Capacity Sensible Capacity GPM Rating (point flow water rate)

15,500 12,100

22,040 17,180

25,200 19,400

33,200 27,000

42,600 33,200

12,500 11,100

17,600 16,800

20,100 17,800

27,000 24,800

34,000 30,400

10,120 9,100 2.5 gpm

14,260 13,770 4.0 gpm

16,280 15,410 4.5 gpm

21,870 20,340 5.0 gpm

27,610 24,930 8.0 gpm

Heating Capacity, BTU/H, 60oF EAT, EWT= Entering Water Temperature, LAT= Leaving Air Temperature BTU/H @120oF EWT (oF LAT) GPM Rating BTU/H @150oF EWT (oF LAT) GPM Rating BTU/H @180oF EWT (oF LAT) GPM Rating

22,700 (101oF) 1.8 gpm 34,400 (123oF) 1.8 gpm 41,070 (136oF) 1.6 gpm

28,800 (98oF) 2.3 gpm 43,600 (117oF) 2.3 gpm 58,700 (137oF) 2.3 gpm

30,600 (95oF) 2.0 gpm 46,500 (113oF) 2.0 gpm 62,500 (131oF) 2.0 gpm

49,200 (98oF) 52,400 (94oF) 3.6 gpm 3.6 gpm 74,800 (117oF) 79,600 (112oF) 3.6 gpm 3.6 gpm 100,600(136oF) 107,200 (130oF) 3.6 gpm 3.6 gpm

5.0 kW 17,500

5.0 kW 17,570

7.0 kW 24,540

7.0 kW 24,690

750 1/6 20x20

800 1/4 20x20

1,200 1/2 20x20

1,400 1/2 20x20

Heating Capacity, Nichrome wire element, optional Heater kW @220/1/60 BTU/H, @220/1/60

3.0 kW 10,760

Evaporator Blower, DWDI, Direct Drive, 3 speed CFM, Free Discharge Motor Horsepower Filter, 1” deep throw away, Qty. 1

500 1/8 20x20

Humidification, Electrode Canister Humidifier with adjustable cycling output, optional Steam Output, lbs/hr Power consumption

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

1-5 lbs/hr 1.8 kW

Evaporator Coil, Aluminum Fin, Copper Tube, A-frame design Rows/Face Area (ft2) Face Velocity, fpm

3/1.5 333

3/1.5 500

3/2.0 400

3/3.0 400

3/3.0 467

3/4 1/4 1/2

3/4 1/4 3/4

3/4 1/4 3/4

3/4 1/4 3/4

3/4 1/4 3/4

125

125

150

155

155

Connection Sizes Condensate drain Humidifier Inlet Chilled water connection, OD

Physical Data Dimensions-- see page 15 for details Approximate weight, lbs.

AeroSys, Inc.

11

Electrical Data Power Consumption at 208/1/60

Model

(12)

(18)

(24)

(30)

(36)

11.7 17.5 25

13.6 19.8 30

18.0 24.9 35

19.8 28.0 40

36.1 41.9 50

38.0 44.2 55

42.3 49.3 60

44.2 52.4 60

19.8 25.6 35

21.7 28.0 35

26.1 33.0 45

27.9 36.1 50

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

7.0 13.5 20

8.8 15.8 25

12.9 20.9 35

14.6 24.0 40

31.3 37.9 45

33.2 40.2 50

37.3 45.3 60

39.0 48.4 60

15.1 21.6 30

16.9 24.0 35

21.0 29.0 40

22.7 32.1 50

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

8.6 13.5 20

10.5 15.8 25

15.2 20.9 35

17.3 24.0 40

32.9 37.9 45

34.9 40.2 50

39.6 45.3 60

41.7 48.4 60

16.7 21.6 30

18.6 24.0 35

23.3 29.0 40

25.4 32.1 50

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

Air Cooled Self Contained, CM-( )-AS series Cooling only Full Load Amps 10.1 Minimum Circuit Amps 14.5 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 22.3 Minimum Circuit Amps 26.6 Maximum Overcurrent Protection 35 Humidification option only (and cooling mode) Full Load Amps 18.2 Minimum Circuit Amps 22.6 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

Water Cooled, CM-( )-W series Cool only Full Load Amps 7.5 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 19.7 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 15.6 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

Glycol Cooled, CM-( )-G series Cool only Full Load Amps 8.2 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 20.4 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 16.3 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

12

AeroSys, Inc.

Electrical Data Power Consumption at 208/1/60

Model

(12)

(18)

(24)

(30)

(36)

7.7 13.5 20

9.6 15.8 25

14.0 20.9 35

15.8 24.0 40

32.1 37.9 45

34.0 40.2 50

38.3 45.3 60

40.2 48.4 60

15.8 21.6 30

17.7 24.0 35

22.1 29.0 40

23.9 32.1 50

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

Air Cooled Remote Condenser, CM-( )-AR series Cool only Full Load Amps 7.9 Minimum Circuit Amps 12.3 Maximum Overcurrent Protection 20 Heat/Reheat option only (in dehumidification mode) Full Load Amps 20.1 Minimum Circuit Amps 24.4 Maximum Overcurrent Protection 30 Humidification option only (and cooling mode) Full Load Amps 16.0 Minimum Circuit Amps 20.4 Maximum Overcurrent Protection 30 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

Air Handler with Remote Condensing Unit, CM-( )-AH series Cool only Full Load Amps 1.5 Minimum Circuit Amps 1.9 Maximum Overcurrent Protection 5 Heat/Reheat option only (in dehumidification mode) Full Load Amps 13.7 Minimum Circuit Amps 14.1 Maximum Overcurrent Protection 15 Humidification option only (and cooling mode) Full Load Amps 9.6 Minimum Circuit Amps 10.0 Maximum Overcurrent Protection 10 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

1.5 1.9 5

2.2 2.8 6

4.0 5.0 8

4.0 5.0 8

21.8 22.2 25

26.6 27.1 30

28.4 29.4 35

28.4 29.4 35

9.6 10.0 10

10.3 10.9 15

12.1 13.1 15

12.1 13.1 15

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

1.5 1.9 5

2.2 2.8 6

4.0 5.0 8

4.0 5.0 8

21.8 22.2 25

26.6 27.1 30

28.4 29.4 35

28.4 29.4 35

9.6 10.0 10

10.3 10.9 15

12.1 13.1 15

12.1 13.1 15

34.0 34.4 35

34.7 35.3 35

36.5 37.5 40

36.5 37.5 40

Chilled Water Air Handler, CM-( )-CW series Cool only Full Load Amps 1.5 Minimum Circuit Amps 1.9 Maximum Overcurrent Protection 5 Heat/Reheat option only (in dehumidification mode) Full Load Amps 13.7 Minimum Circuit Amps 14.1 Maximum Overcurrent Protection 15 Humidification option only (and cooling mode) Full Load Amps 9.6 Minimum Circuit Amps 10.0 Maximum Overcurrent Protection 10 Heat/Reheat, Humidification options combined (no cooling) Full Load Amps 21.8 Minimum Circuit Amps 22.2 Maximum Overcurrent Protection 25

AeroSys, Inc.

13

Outside Heat Exchangers 9

Header

A

Electric Box

15 in 9

E Model ACC-014 ACC-018 ACC-023 ACC-032 ACC-049

/16 Mounting Mounting Legs (4)

F

Motor Data (208/1/60) # @ fan dia. Hp Amps 1@ 18 in 1/3 3.2 1@ 18 in 1/3 3.2 1@ 18 in 1/3 3.2 1@ 22 in 1/3 3.2 1@ 22 in 1/3 3.2

Model ACC-014 ACC-018 ACC-023 ACC-032 ACC-049

/16 Lifting

A 16-1/4 16-1/4 16-1/4 18-1/8 18-1/8

Ref. Charge R-22 (lbs.) 0.45 0.45 0.90 1.20 1.95

Cabinet Dimensions B C E 28 25-9/16 26-5/8 9 28 25- /16 26-5/8 9 28 25- /16 26-5/8 9 33 30- /16 31-5/8 9 33 30- /16 31-5/8

F 26-13/16 26-13/16 26-13/16 31-13/16 31-13/16

Net 78 80 86 107 116

THR @ oF ITD 20oF 25oF 13.5 16.8 17.8 22.3 22.8 28.6 31.2 39.0 48.9 60.5 Weight Shipping 97 99 105 128 137

30oF 20.2 26.7 34.3 46.8 72.5

Connections Liquid/Gas 7/8” OD 7/8” OD 7/8” OD 7/8” OD 7/8” OD

Remote Condensing Units BTU/H’s

Electrical Data

Dimensions

Weight

Connections

FLA/MCA/MOP

H x W x D (in)

net/ship (lb)

Liquid/Suction

10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45

23x291/2x181/2 23x291/2x181/2 23x291/2x181/2 23x291/2x181/2 23x291/2x181/2

70/75 75/81 79/85 91/102 70/75

3

12,500 20,300 25,500 30,000 35,400

10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45

285/8x26x181/2 285/8x26x181/2 285/8x26x181/2 285/8x26x181/2 285/8x26x181/2

70/75 75/81 79/85 91/102 70/75

3

12,500 19,900 25,400 30,000 35,900

10.2/17.2/25 10/17.2/25 12/19.7/30 15.9/24.7/35 17.7/28.3/45

32x233/4x181/2 32x233/4x181/2 32x233/4x181/2 32x233/4x181/2 32x233/4x181/2

70/75 75/81 79/85 91/102 70/75

3

“R” (Runt) Series THDC-12-R THDC-18-R THDC-24-R THDC-30-R THDC-36-R

12,500 20,200 25,200 30,000 35,300

“S” (Short) Series THDC-12-S THDC-18-S THDC-24-S THDC-30-S THDC-36-S

“T” (Tall) Series THDC-12-T THDC-18-T THDC-24-T THDC-30-T THDC-36-T ARI 210/240 conditions

14

AeroSys, Inc.

/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3

/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3

/8”ODS / 3/4”ODS /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3 /8”ODS / 3/4”ODS 3

Dimensional Data Self-Contained Air Cooled CM-( )AS Series Units 511/2

237/8

17 211/8

101/4

81/4

451/8 473/4 22

CM-( )-W, G, CW, AR, AH Series Units

511/2

203/8 237/8

Field Connection Area for Condenser and Chilled Water Pipes

451/8 473/4

DUCTED Self-Contained Air Cooled CM-( )AS Series Units

14.1

10.0

10.3

6.9 8.3

16

.5

AeroSys, Inc.

Pump Package Performance Curves Head

PA_-005 (1/2 HP)

(ft)

1.25x1x5 @ 3500 rpm

Head

120

PA_-007 (3/4 HP)

(ft) 5.00 in

100

31

42

50

1.25x1x5 @ 3500 rpm

Head

120 57

5.00 in

63 64

80

100

63

31

42

50

57

61

5.00 in

63 57

64

3 hp

60

100

63

80

50

20

40

16

32

64

63 61 57

2 hp

40

0.75 hp 20

48

64

Flow (usgpm)

Ethylene Glycol: 40%, sg = 1.06

1.5 hp

3.25 in

1 hp

0.5 hp

80

0.333 hp 0.25 hp

System

0.75 hp

20

0 0

3 hp 50

60 3.88 in

1.5 hp

3.25 in 1 hp

0.333 hp 0.25 hp

System

61

2 hp

0.5 hp

0

57

80

50

3.56 in

1 hp

50

3 hp

60

0.75 hp

42

63

2 hp

3.30 in 40 3.25 in

31

61 57

1.5 hp

1.25x1x5 @ 3500 rpm 120

61

0

PA_-010 (1 HP)

(ft)

61

16

32

48

64

80

System

0

Flow (usgpm)

Ethylene Glycol: 40%, sg = 1.06

0.5 hp 0.333 hp 0.25 hp

0

16

32

48

64

Single and Dual Pump Packages L S PANE ACCES Electrical) ps &

tlet Pump Ou outs)

24"

(Knock

(Pum

let Pump Ints) ou (Knock

5"

36"

20"

38" 3/4"

REAR / RIGHT / TOP VIEW

FRONT / LEFT / TOP VIEW

Other AeroSys Products AeroCon THDC Series contrifugal condensing in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCon THHP Series heat pumps in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCool DDX Series D.X. air handlers in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroCon Centrifugal condensing units from 3 to 5 tons AeroCool DCW Series chilled water air handlers in sizes from 1-1/2 ton to 2-1/2 ton capacities. AeroPure Refrigerants, certified to ARI 700.

Represented by:

Accepted for Use City of NY Dept. of Bldgs

MEA-371-05-E Specifications are subject to change without notice

16

Form CM-1208 Rev.0

AeroSys, Inc.

80

Flow (usgpm)

Ethylene Glycol: 40%, sg = 1.06