D-Series Size 3
Catalog Number
LED Flood Luminaire
Notes
Type
Hit the Tab key or mouse over the page to see all interactive elements.
Introduction
Specifications EPA: Depth: Width:
W
The D-Series Size 3 Flood features precision optics to beautifully illuminate a variety of applications as its sleek, compact styling blends seamlessly with its environment.
D
1.4 ft2
The D-Series Flood reflector systems and cuttingedge chip-on-board LED technology produce low field-to-beam ratios for minimal spill light and incredible photometric performance. It’s the ideal long-life replacement for 250 - 400W metal halide floods, with typical energy savings of 67% and expected service life of over 100,000 hours.
(0.13 m2)
5” (12.7 cm)
H
13” (33.0 cm)
Height:
13-5/8”
Overall Height
17-1/2”
Weight:
21 lbs
OH
(34.6 cm) (44.5 cm) (9.5 kg)
Ordering Information
EXAMPLE: DSXF3 LED 8 A530/40K FL MVOLT THK DDBXD
DSXF3 LED Series DSXF3 LED
Light Engines 6 8
Six COB engines Eight COB engines
Performance Package
Distribution
530 mA options: A530/30K 3000K A530/40K 4000K A530/50K 5000K
NSP MSP MFL
Voltage
Narrow spot Medium spot Medium flood FL Flood WFL Wide flood WFR Wide flood, rectangular HMF Horizontal medium flood
MVOLT 1 120 1 208 1 240
1
277 1 347 480
Mounting Shipped included THK Knuckle with 3/4” NPT threaded pipe YKC62 Yoke with 16-3 SO cord IS Integral slipfitter (fits 2-3/8” O.D. tenon) Shipped separately 2 FTS CG6
FRWB DDBXD U
Radius wall bracket, 2-3/8” OD tenon (specify finish)
FSPB DDBXD U
Steel square pole bracket, 2-3/8” OD tenon (specify finish)
Shipped installed PER DMG DCR
DDBXD NEMA twist-lock receptacle only (no controls) 0-10V dimming driver (no controls) Dimmable and controllable via ROAM® (no controls) 3 Single fuse (120, 277, 347V) 4 Double fuse (208, 240, 480V) 4 Utility terminal block
DBLXD DNAXD DWHXD
Dark bronze Black Natural aluminum White
SF DF WTB Shipped separately 2 UBV Upper/bottom visor (universal) FV Full visor VG Vandal guard WG Wire guard SC
Shorting cap 5
DLL127F 1.5 JU DLL347F 1.5 CUL JU
Photocell - SSL twist-lock (120277V) 5 Photocell - SSL twist-lock (347V) 5
DLL480F 1.5 CUL JU
Photocell - SSL twist-lock (480V) 5
1
Ordered and shipped separately.
Slipfitter for 2-3/8” to 2-7/8” OD tenons; mates with yoke mount (specify finish)
Tenon slipfitter (fits 2-3/8” to 2-7/8” O.D. tenon. YKC62 required)
Finish (required)
NOTES
Accessories FTS CG6 DDBXD U
Options
DSXF3UBV DDBXD U Upper/bottom visor accessory (specify finish) DSXF3FV DDBXD U
Full visor accessory (specify finish)
DSXF3VG U
Vandal guard accessory
DSXF3WG U
Wire guard accessory
For more mounting options, visit our Floodlighting Accessories pages. For more control options, visit DTL and ROAM online.
2 3
4 5
MVOLT driver operates on any line voltage from 120-277V. Specify 120, 208, 240 or 277 options only when ordering with fusing (SF, DF options). Also available as separate accessories; see Accessories information at left. Specifies a ROAM® enabled luminaire with 0-10V dimming capability; PER option required. Not available with 347 or 480V. Additional hardware and services required for ROAM® deployment; must be purchased separately. Call 1-800-442-6745 or email:
[email protected]. Single fuse (SF) requires 120, 277 or 347 voltage option. Double fuse (DF) requires 208, 240 or 480 voltage option. Requires luminaire to be specified with PER option. Ordered and shipped as a separate line item.
One Lithonia Way • Conyers, Georgia 30012 • Phone: 800.279.8041 • Fax: 770.918.1209 • www.lithonia.com © 2012-2013 Acuity Brands Lighting, Inc. All rights reserved.
Performance Data Lumen Ambient Temperature (LAT) Multipliers
Lumen Output
Use these factors to determine relative lumen output for average ambient temperatures from 0-40°C (32-104°F).
Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown, within the tolerances allowed by Lighting Facts. Actual performance may differ as a result of end-user environment and application. Actual wattage may differ by +/- 8% when operating between 120-480V +/- 10%. Contact factory for performance data on any configurations not shown here.
Light Engines
Drive Current (mA)
6
Performance Package
530
8
530
Dist. Type
System Watts
A530/--K
°H
NSP MSP MFL FL WFL WFR HMF NSP MSP MFL FL WFL WFR HMF
115W
A530/--K
Field Angle
158W
40K (4000K, 70 CRI)
Beam Angle
Ambient
50K (5000K, 67 CRI)
°V
°H
°V
Max Cd
Lumens
LPW
Max Cd
Lumens
LPW
48 49 50 48 60 60 85 84 106 106 107 88 100 62 48 49 50 48 60 60 85 84 106 106 107 88 100 62
19 24 47 63 71 85 80 19 24 47 63 71 85 80
19 23 46 62 72 64 13 19 23 46 62 72 64 13
39,299 36,284 15,104 9985 7488 7460 6779 51,658 47,694 19,854 13,125 9843 9805 8911
7471 8373 8948 9730 10,230 10,461 3301 9820 11,006 11,761 12,790 13,448 13,751 4338
65 73 78 85 89 91 29 62 70 74 81 85 87 27
39,177 36,171 15,057 9954 7465 7436 6758 51,496 47,546 19,792 13,084 9812 9775 8883
7448 8347 8920 9700 10,199 10,429 3290 9790 10,971 11,725 12,750 13,406 13,708 4325
65 73 78 84 89 91 29 62 69 74 81 85 87 27
Lumen Multiplier
0°C
32°F
1.05
10°C 20°C 25°C 30°C 40°C
50°F 68°F 77°F 86°F 104°F
1.03 1.01 1.00 0.99 0.97
Projected LED Lumen Maintenance Data references the extrapolated performance projections for the DSXF LED 8 A530 platform in a 25°C ambient, based on 8400 hours of LED testing (tested per IESNA LM-8008 and projected per IESNA TM-21-11). To calculate LLF, use the lumen maintenance factor that corresponds to the desired number of operating hours below. For other lumen maintenance values, contact factory. Operating Hours
0
25,000
50,000
100,000
Lumen Maintenance Factor
1.0
0.94
0.90
0.84
Electrical Load Current (A)
Photometric Diagrams
Light Engines
Drive Current (mA)
System Watts
120
208
240
277
347
480
6
530
115W
1.06
0.61
0.53
0.46
0.37
0.27
8
530
158W
1.46
0.84
0.73
0.63
0.51
0.37
To see complete photometric reports or download .ies files for this product, visit Lithonia Lighting’s D-Series Flood Size 3 homepage.
-40°
-20°
0°
20°
40°
60°
80°
10%
60°
20%
40°
30%
20°
40%
0°
50%
-20°
60%
-40°
75%
-60°
90%
-80°
MSP
-80°
-60°
-40°
-20°
0°
20°
40°
60°
80°
80° 60° 40° 20° 0° -20° -40° -60°
FL
-80°
-80°
-60°
-40°
-20°
0°
20°
40°
60°
80°
80° 60° 40° 20° 0° -20° -40° -60° -80°
WFL
-80°
-60°
-40°
-20°
0°
20°
40°
60°
80° 60° 40° 20° 0° -20° -40° -60°
HMF
-80°
80°
Test No. LTL22159P12 tested in accordance with IESNA LM-79-08.
-60°
Test No. LTL22174P12 tested in accordance with IESNA LM-79-08.
-80° 80°
Test No. LTL22153P12 tested in accordance with IESNA LM-79-08.
(% Max cd)
Test No. LTL22173P12 tested in accordance with IESNA LM-79-08.
Isocandela plots for the DSXF3 LED 8 A530/40K. LEGEND
FEATURES & SPECIFICATIONS
CONSTRUCTION Die-cast aluminum housing has integral heat sink fins to optimize thermal management through conductive and convective cooling. The LED driver is mounted in direct contact with the casting to promote low operating temperature and long life. Housing is completely sealed against moisture and environmental contaminants (IP65). Low EPA (1.4 ft2) for optimized wind loading.
ELECTRICAL Light engines consist of chip-on-board (COB) LEDs directly coupled to the housing to maximize heat dissipation and promote long life (100,000 hrs at 25°C, L84). Class 1 electronic driver has a power factor >90%, THD