Fire Alarm Systems | D291 Series Detector Bases (24 VDC)
D291 Series Detector Bases (24 VDC) ▶ Low‑profile six‑inch diameter base with interchangeable detector heads ▶ Easy head removal for cleaning and servicing without circuit interruption ▶ Supervised 24 VDC power circuit ▶ Simplified point addressing by DIP switches ▶ Standard screw terminal connections ▶ Form C relay option
The D291 series detector bases are used with the Bosch D9124 Addressable Fire Alarm Control Panel (FACP) as a replacement item for the D290 Series Addressable Detector Bases. The D291 series bases are fully compatible with any D290 addressable application and can mix with D290 Series Bases in an existing system. They are an ideal application for systems that are upgraded to increase address point capacity. They are compatible with a number of Bosch smoke and heat detector heads.
The D291M offers connections for a supervised 24 VDC slave circuit containing up to 19 D250 detector bases. The 24 VDC power circuit wires can run in the same conduit as the Zonex expansion circuit. When so configured, the D291M and the devices in its slave circuit report alarm, trouble, and restoral conditions to the control panel as a single point address.
The D291 bases are wired in the Zonex expansion circuit. Each device (or device and slave circuit) has a specific point address, which is set using the DIP switch on the device. The point address is independent of the device location in the wiring. When so configured, these devices report alarm, trouble, and restoral conditions to the FACP over the Zonex bus. Removing the detector head from the base for cleaning or service initiates a trouble signal but does not interrupt the polling circuit.
Certifications and Approvals
Both the D291S and the D291M can use a D299 Relay Module to provide a pair of relay points for Form C dry contact applications.
Region
Certification
USA
UL
UQGS: Heat - Automatic Fire Detectors (UL521), UROX: Smoke - Automatic Fire Detectors (UL268 and A)
CSFM
7300-1615: 160
Installation/Configuration Notes Compatible Products The following products are compatible with both the D291M Master Detector Base and the D291S Detector Base:
www.boschsecurity.com
2 | D291 Series Detector Bases (24 VDC)
Category
Product ID
Product Description
Mechanical Properties
Control Panels
D9124
Addressable FACP
Color:
Bone white
Detector Bases
D291M
Addressable master detector base
Dimensions (diameter x D):
6 in. x 1 in. (15.2 cm x 2.5 cm))
Detector Heads
D254
Fixed‑temperature heat detector (+135°F [+57°C])
Power Requirements
D255
Fixed‑temperature heat detector (+190°F [+88°C])
Current (alarm):
D291M: 50 mA maximum D291S: 15 mA maximum
D256A
Rate‑of‑Rise and fixed‑temperature heat detector (+135°F [+57°C])
Current (standby):
D291M: 15 mA D291S: 1.3 mA
D257A
Rate‑of‑Rise and fixed‑temperature heat detector (+190°F [+88°C])
Voltage (operating):
20.4 VDC to 28.0 VDC
D281A
Ionization smoke detector head
D282A
Photoelectric smoke detector head
D283A
Photoelectric smoke detector head with fixed‑temperature (+135°F [+57°C]) heat sensor
D299
Relay module
Modules
The following products are also compatible with the D291M Master Detector Base: Category
Product ID
Product Description
Detector Bases
D250A
Two‑wire addressable detector base
Ordering Information D291M Master Detector Base Fully compatible with any D290 addressable application, this base can mix with D290 Series Bases in an existing system. It offers connections for a supervised 24 VDC slave circuit containing up to 19 D250 detector bases.
D291M
D291S Detector Base Used in a slave circuit with the D291M as the master base.
D291S
Mounting The D291M and D291S bases mount directly on single‑gang switch boxes or on four‑inch octagonal back boxes. They can mount on four‑inch square boxes with an adaptor plate. Wiring Wiring connections are accessible with the base mounted on the back box. Two separate wiring circuits connect the D291 series detector bases with the FACP. A supervised UL‑listed power supply provides 24 VDC on one circuit, and a data expansion loop allows the FACP to poll each address point on the other circuit. Polling occurs every 150 ms to 300 ms.
Parts Included Quant.
Component
1
D291M or D291S detector base
1
Hardware pack
1
Literature pack
Technical Specifications Environmental Considerations Temperature (operating):
Americas: Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180
[email protected] www.boschsecurity.us
+32°F to +100°F (0°C to +38°C)
Europe, Middle East, Africa: Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330
[email protected] www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1439631627 | Cur: en-US, V5, 4 Jul 2010