Data Sheet - Cooper Industries

Report 13 Downloads 43 Views
Quik-Spec™ Coordination Panelboard - Data Sheet 600A - 1200A Fusible Panelboards

Contents Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Enclosure Types and Voltages/Systems . . . . . . . . . . . . . . . . . .3 Main, Sub-Feed & Feed Through Lug Specifications . . . . . . . .4 Neutral and Ground Assemblies . . . . . . . . . . . . . . . . . . . . . . .5 Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10 Fuse & Disconnect Performance Data . . . . . . . . . . . . . . . . . .11 Low-Peak CUBEFuse Fuse Specifications . . . . . . . . . . . . . . .11

0212

BU-SB11645

Page 1 of 11

Data Sheet: 1171

Catalog Symbol: QSCP12 Description:

Panelboard Short-Circuit Current Ratings:

Fuseible panelboards for commercial/industrial branch or service entrance applications on systems up through 600Vac. The QSCP is specifically designed to address the NEC® Selective Coordination Requirements for Emergency, Legally Required Standby, Healthcare Essential Electrical and Critical Operation Power Systems (COPS) per NEC® 700.27, 701.18, 517.26 and 708.54. Not for applications requiring AFCI protected circuits. The QSCP is configured to order for the application. To confirm availability of options and constructions, contact your Cooper Bussmann distributor.

Ratings: Volts: 600Vac (or less), 125Vdc Amps: 600, 800, 1200A SCCR: 20kA or 100kA @125Vdc - See Panelboard Short-Circuit Current Ratings table for AC ratings

Agency Information: • UL 67 – Standard for panelboards • UL 50/UL 50E – Enclosures for electrical equipment • CSA 22.2, No. 29-M1989 – Panelboards and enclosed panelboards • UL Listed, Class CTL panelboard (meets 2002 NEC® 408.15 limit of 42 overcurrent devices per panel) • U.B.C. and C.B.C. Seismic Qualified, and I.B.C. Approved

Main Options: • Main Lug Only (MLO)

Branch Disconnect Options: • 1-, 2- and 3-Pole 15, 20, 30, 40, 50, 60, 70, 90, 100, 200, 400 and 600A rejecting branch disconnects (see table for details). Branch ampacity on 125Vdc panels limited to CCPB 80A or less.

Neutral Options: • Unbonded & Bonded 600, 800, 1200, 1600 and 2400A

Ground Options: • Isolated & Non-isolated

Enclosures: • NEMA 1

Spare Fuse Compartment: • Standard on all models

CCPB Horsepower Ratings: CCPB Disconnect CCPB-(Poles)-15CF CCPB-(Poles)-20CF CCPB-(Poles)-30CF CCPB-(Poles)-40CF CCPB-(Poles)-50CF CCPB-(Poles)-60CF CCPB-(Poles)-70CF CCPB-(Poles)-90CF CCPB-(Poles)-100CF CFD200J03 CFD400J03 CFD600J03

0212

BU-SB11645

Amp Rating 15 20 30 40 50 60 70 80 100 200 400 600

120 0.5 0.75 1.5 2 3 3 3 5 5 – – –

Hp Rating @ Vac 240 480 3 5 3 7.5 5 15 7.5 20 7.5 20 7.5 20 15 30 20 40 20 50 60 125 125 250 200 400

600 7.5 10 10 10 10 10 40 50 50 150 350 500

Panelboard Short-Circuit Current Ratings AC Main Options DC Main Main Lug Only Lug Only SCCR (MLO)* (MLO)* High 200kA 100kA Std. 50kA 20kA * For panelboards with subfeed main lugs, or panelboards with optional feed-through lugs, Class J, T or R fuses are required upstream – max amps = panel amps.

Branch Disconnects: Fuse Max Time-Delay Branch* Part Amp CCPB Non-Indicating Number Poles Range Ampacity Fuses CCPB-1-15CF 1 TCF1RN, TCF3RN, CCPB-2-15CF 2 1-15 15 TCF6RN, TCF10RN, CCPB-3-15CF 3 TCF15RN CCPB-1-20CF 1 1 ⁄2RN, TCF17CCPB-2-20CF 2 171⁄2-20 20 TCF20RN CCPB-3-20CF 3 CCPB-1-30CF 1 TCF25RN, CCPB-2-30CF 2 25-30 30 TCF30RN CCPB-3-30CF 3 CCPB-1-40CF 1 TCF35RN, CCPB-2-40CF 2 35-40 40 TCF40RN CCPB-3-40CF 3 CCPB-1-50CF 1 TCF45RN, CCPB-2-50CF 2 45-50 50 TCF50RN CCPB-3-50CF 3 CCPB-1-60CF 1 CCPB-2-60CF 2 60 60 TCF60RN CCPB-3-60CF 3 CCPB-1-70CF 1 CCPB-2-70CF 2 70 70 TCF70RN CCPB-3-70CF 3 CCPB-1-90CF 1 TCF80RN CCPB-2-90CF 2 80-90 90 TCF90RN CCPB-3-90CF 3 CCPB-1-100CF 1 CCPB-2-100CF 2 100 100 TCF100RN CCPB-3-100CF 3 LPJ-110SP, LPJ-125SP, CFD200J03 3*** 110-200 200 LPJ-150SP, LPJ-175SP, LPJ-200SP LPJ-225SP, LPJ-250SP, CFD400J03 3*** 225-400 400 LPJ-300SP, LPJ-350SP, LPJ-400SP LPJ-450SP, LPJ-500SP, CFD600J03 3*** 450-600 600 LPJ-600SP

Time-Delay Indicating Fuses** TCF6 TCF10, TCF15

Fast-Acting Non-Indicating Fuses FCF1RN, FCF3RN, FCF6RN, FCF10RN, FCF15RN

TCF17-1⁄2, TCF20

FCF20

TCF25, TCF30

FCF25RN, FCF30RN

TCF35, TCF40

FCF35RN, FCF40RN

TCF45, TCF50

FCF45RN, FCF50RN

TCF60

FCF60RN

TCF70

FCF70RN

TCF80 TCF90

FCF80RN FCF90RN

TCF100

FCF100RN

LPJ-110SPI, LPJ-125SPI, LPJ-150SPI, LPJ-175SPI, LPJ-200SPI LPJ-225SPI, LPJ-250SPI, LPJ-300SPI, LPJ-350SPI, LPJ-200SPI LPJ-450SPI, LPJ-500SPI, LPJ-600SPI

JKS-110, JKS-125, JKS-150, JKS-175, JKS-200 JKS-225, JKS-250, JKS-300, JKS-350, JKS-400 JKS-450, JKS-500, JKS-600

*CCPB disconnect can accept CUBEFuses with amp ratings less than or equal to the amp rating of the CCPB disconnect. **Correct fit with CCPB disconnect requires time-delay CUBEFuses with date code R38 or later. *** 3-Pole switch used for 1 and 2-pole applications

Page 2 of 11

Data Sheet: 1171

Enclosure Types

AC & DC Voltages & System Types

NEMA 1

AC Voltages

DC Voltage

1-Phase, 2 Wire • 120V 1-Phase, 2 Wire • 240V 1-Phase, 2 Wire

1-Phase, 2 Wire

• • • •

Floor mount Galvanized steel with blank end walls Box sizes: 27” W x 15” D x 65”/ 38˝ W x 15˝ D x 65˝ or 89˝ H Enclosure and chassis mounting instructions are found in literature supplied with unit • Chassis mounts directly onto studs in the enclosure • Trim finished with gray powder coat paint over phosphatized steel (ANSI 61) • Circuit directory card is located on the inside of the door

• 125Vdc, 2 Wire (Up to 125Vdc, MLO option only, CCPB 80A or less)

1-Phase, 3 Wire • 120/240V 1-Phase, 3 Wire

N

1-Phase, 2 Wire, Wye • 277V 1-Phase, 2 Wire

A

+125Vdc

B N C

1-Phase, 2 Wire, Delta • 480V 1-Phase, 2 Wire

A

B

C

1-Phase, 3 Wire, Delta • 240/480V 1-Phase, 3 Wire

A N C

3-Phase, 4 Wire, Wye • 208Y/120V 3-Phase, 4 Wire • 480Y/277V 3-Phase, 4 Wire • 600Y/347V 3-Phase, 4 Wire

B A B N

C

3-Phase, 4 Wire, Delta • 240/120V 3-Phase, 4 Wire • 480/240V 3-Phase, 4 Wire

A B N C

3-Phase, 3 Wire, Delta • 240V 3-Phase, 3 Wire • 480V 3-Phase, 3 Wire • 600V 3-Phase, 3 Wire • 240V 3-Phase, 3 Wire, Grounded B • 480V 3-Phase, 3 Wire, Grounded B • 600V 3-Phase, 3 Wire, Grounded B 1-Phase, 3 Wire, Wye • 208Y/120V 1-Phase, 3 Wire • 480Y/277V 1-Phase, 3 Wire

A B C

A

B N

Busing

C

Tin-plated copper with sufficient cross section to meet UL 67 temperature rise requirements.

Distributed 1- & 3-Phase Busing All CCPB branch disconnects can be mounted in any branch circuit position.

Single-Phase

0212

BU-SB11645

Page 3 of 11

Three-Phase

Data Sheet: 1171

600 Amp Main Lugs

800-1200 Amp Main Lugs

Main Mechanical Lugs Main Barrier Cover Open

Main Mechanical Lugs Wire Range / Torque Lb-In (N•m) • 300kcmil-1AWG / 375 (42) • 2-6AWG / 275 (31) Wire Rating: 60/75°C, Cu-Al

Wire Range / Torque Lb-In (N•m) • 600kcmil-4AWG / 500 (56) Wire Rating: 60/75°C, Cu-Al

Main Sub-Feed Mechanical Lugs Main Barrier Cover Open Wire Range / Torque Lb-In (N•m) • 600kcmil-2AWG/375(42) Wire Rating: 60/75°C, Cu-Al

Main Sub-Feed Mechanical Lugs Wire Range / Torque Lb-In (N•m) • 300kcmil - 6AWG / 275 (31) Wire Rating: 60/75°C, Cu-Al

Main Compression (Crimp) Lugs* Main Barrier Cover Open Wire Range • 600-250kcmil Wire Rating: 60/75°C, Cu-Al

Main Compression (Crimp) Lugs* Wire Range • 300kcmil-4AWG Wire Rating: 60/75°C, Cu-Al

Feed-Through Lugs Compression, mechanical and double (sub-feed) lugs are all available as feed-through lugs. Lug ampacity ratings will be based upon panelboard ampacity rating.

Main Mechanical Lugs

Main Sub-Feed Mechanical Lugs

Main Compression (Crimp) Lugs*

* Versa-Crimp® VC-6 crimp tool recommended for wire crimping.

0212

BU-SB11645

Page 4 of 11

Data Sheet: 1171

Neutral Assemblies 600A Unbonded Wire Range / Torque Lb-In (N•m) • Main Terminal 600kcmil-2 AWG / 275 (31) • Branch Connections - See table below Wire Rating: 60/75°C, Cu-Al Bar Material: Copper, Tin-plated Lug Material: Aluminum, Tin-plated

600A Bonded Wire Range / Torque Lb-In (N•m) • Main Terminal 600kcmil-2 AWG / 275 (31) • Branch Connections - See table below Wire Rating: 60/75°C, Cu-Al Bar Material: Copper, Tin-plated Lug Material: Aluminum, Tin-plated

Ground Assemblies Isolated / Non-isolated Wire Range / Torque Lb-In (N•m) • Main Terminal 600kcmil-2 AWG / 275 (31) • Branch Connections - See table below Wire Rating: 60/75°C, Cu-Al Bar Material: Copper, Tin-plated Lug Material: Aluminum, Tin-plated

Ground and Neutral Bars Connection Wire Torques Wire* AWG 14 AWG - 4 AWG 3 AWG - 2/0 AWG 6 AWG - 1/0 AWG 2/0 AWG - 350 kcmil 4 AWG - 3/0 AWG 4/0 AWG 250 kcmil - 600 kcmil 2 AWG - 3/0 AWG 4/0 AWG 250 kcmil - 600 kcmil

Torque Max. No. Wires Per Opening Lb-In (N•m) Neut. GND ≤100A Branch 20-35 (2.3-3.9) 2 2 35-80 (4.5-9.0) 1 1 110 - 200A Branch 35-200 (3.9-22.6) 2 2 200-375 (22.6-42.0) 1 1 225 - 400A Branch 35-200 (3.9-22.6) 2 2 200 (22.6) 1 1 275-500 (31.0-56.5) 1 1 450 - 600A Branch 35-200 (3.9-22.6) 2 2 200 (22.6) 1 1 275-500 (31.0-56.5) 1 1

*60/75ºC, Cu-Al.

0212

BU-SB11645

Page 5 of 11

Data Sheet: 1171

GROUND Three-Phase, 3 Wire Main Lug Only

GROUND

GROUND

NEUTRAL

Single-Phase, 22Wire Single-Phase, Wire Main Lug Only Main Lug Only

Three-Phase, 4 Wire Main Lug Only

Single-Phase, 3 Wire Main Lug Only

0212

BU-SB11645

NEUTRAL

NEUTRAL

GROUND

Typical Wiring

Page 6 of 11

Data Sheet: 1171

NEMA 1 Enclosures & Interior

0212

BU-SB11645

Page 7 of 11

Data Sheet: 1171

NEMA 1 Enclosure Dimensions Panel Ampacity Base Unit

600A

800A

1200A

0212

BU-SB11645

Branch Configuration (18) 1-100A (18) 1-100A + 200A single (18) 1-100A + 200A twin 200A single + 200A single 200A single + 200A twin 200A twin + 200A twin (2) 300A single (18) 1-100A + 200A single (18) 1-100A + 200A twin (2) 200A twin (18) 1-100A + 400A single 200A twin + 400A single (2) 400A single (18) 1-100A + 600A single (3) 200A twin 200A twin + 600A single (2) 200A twin + 400A single (3) 400A single 600A single + 400A single + 200A single 600A single + 400A single + 200A twin (2) 600A single

H 65

Dimensions W D 27 15

65

38

15

89

38

15

65

38

15

89

38

15

89

38

15

102

38

15

Page 8 of 11

Data Sheet: 1171

Quik-Spec Coordination Panelboard Replacement Parts See list on following page for part numbers.

C G F A

I

B

D

E

0212

BU-SB11645

Page 9 of 11

Data Sheet: 1171

Replacement Parts A & B - Main Devices and Feed-Through Lugs 2A2575-1 2A2575-2 2A2575-3 2A2575-4 2A2575-5 2A2575-6 2A2575-7 2A2575-8 2A2575-9 2A2575-10 2A2575-11 2A2575-12 2A2575-13 2A2575-14 2A2575-15 2A2575-16 2A2575-17 2A2575-18

Kit, compression lug 3 phase 600A Kit, mechanical lug 3 phase 600A Kit, double/sub-feed lug 3 phase 600A Kit, compression lug 1 phase, 3 wire 600A Kit, mechanical lug 1 phase, 3 wire 600A Kit, double/sub-feed lug 1 phase, 3 wire 600A Kit, compression lug 1 phase, 2 wire 600A Kit, mechanical lug 1 phase, 2 wire 600A Kit, double/sub-feed lug 1 phase, 2 wire 600A Kit, compression lug 3 phase 800A & 1200A Kit, mechanical lug 3 phase 800A & 1200A Kit, double/sub-feed lug 3 phase 800A & 1200A Kit, compression lug 1 phase, 3 wire 800A & 1200A Kit, mechanical lug 1 phase, 3 wire 800A & 1200A Kit, double/sub-feed lug 1 phase, 3 wire 800A & 1200A Kit, compression lug 1 phase, 2 wire 800A & 1200A Kit, mechanical lug 1 phase, 2 wire 800A & 1200A Kit, double/sub-feed lug 1 phase, 2 wire 800A & 1200A

C - Ground Assemblies 2A2576-1 2A2576-2 2A2576-3 2A2576-4 2A2576-5 2A2576-6 2A2576-7 2A2576-8 2A2576-9 2A2576-10 2A2576-11 2A2576-12

Kit, ground non-isolated 600A Kit, ground isolated 600A Kit, ground non-isolated 800A Kit, ground isolated 800A Kit, ground non-isolated 800A Kit, ground isolated 800A Kit, ground non-isolated 800A Kit, ground isolated 800A Kit, ground non-isolated 1200A Kit, ground isolated 1200A Kit, ground non-isolated 1200A Kit, ground isolated 1200A

D - Neutral Assemblies 2A2577-1 2A2577-2 2A2577-3 2A2577-4 2A2577-5 2A2577-6 2A2577-7 2A2577-8 2A2577-9 2A2577-10 2A2577-11 2A2577-12 2A2577-13 2A2577-14 2A2577-15 2A2577-16 2A2577-17 2A2577-18 2A2577-19 2A2577-20

0212

Kit, neutral unbonded 600A for 600A panel Kit, neutral bonded 600A for 600A panel Kit, neutral unbonded 1200A for 600A panel Kit, neutral bonded 1200A for 600A panel Kit, neutral unbonded 800A for 800A panel Kit, neutral bonded 800A for 800A panel Kit, neutral unbonded 1600A for 800A panel Kit, neutral bonded 1600A for 800A panel Kit, neutral unbonded 800A for 800A panel Kit, neutral bonded 800A for 800A panel Kit, neutral unbonded 1600A for 800A panel Kit, neutral bonded 1600A for 800A panel Kit, neutral unbonded 800A for 800A panel Kit, neutral bonded 800A for 800A panel Kit, neutral unbonded 1600A for 800A panel Kit, neutral bonded 1600A for 800A panel Kit, neutral unbonded 1200A for 1200A panel Kit, neutral bonded 1200A for 1200A panel Kit, neutral unbonded 2400A for 1200A panel Kit, neutral bonded 2400A for 1200A panel

BU-SB11645

D - Neutral Assemblies - (continued) 2A2577-21 2A2577-22 2A2577-23 2A2577-24 2A2577-25 2A2577-26 2A2577-27 2A2577-28

Kit, neutral unbonded 1200A for 1200A panel Kit, neutral bonded 1200A for 1200A panel Kit, neutral unbonded 2400A for 1200A panel Kit, neutral bonded 2400A for 1200A panel Kit, neutral unbonded 600A for 600A panel Kit, neutral bonded 600A for 600A panel Kit, neutral unbonded 1200A for 600A panel Kit, neutral bonded 1200A for 600A panel

E - Enclosures (Box only, does not include doors) 2A2400-1 2A2400-2 2A2400-3 2A2400-4

NEMA 1, 38x65x15 NEMA 1, 38x89x15 NEMA 1, 27x65x15 NEMA 1, 38x102x15

F - Dead Fronts - Branch Enclosure (1-100A Branches) 2A2578-1 2A2578-2

Kit, branch enclosure 38" wide panels Kit, branch enclosure 27" wide panels

G - Latch for Spare Fuse Compartment 2A1910-5

Kit, Spare Fuse Compartment Latch

Lockout/Tagout Devices 2A1912-1 2A1912-3

Kit, lockout 200A - 400A branch Kit, lockout 1-100A branch

Miscellaneous 2A1914 2A1915 2A1917-2 2A1917-3 2A1918-1 2A1918-2 2A1919 2A1961-1

Page 10 of 11

Kit, circuit directory card and sleeve Kit, circuit number and fuse rating labels (1-100A branches) Kit, CCPB hardware (10 screws) Kit, panelboard hardware Kit, branch filler plates 1-60A Kit, branch filler plates 70-100A Kit, touch up paint Kit, Spare Fuse Compartment TCF1-100A

Data Sheet: 1171

Branch Disconnects and Fuse Replacement Parts

Fuse & Disconnect Performance Data

I - CCPB Branch Disconnects

For details and specifications, access the following data sheets online at www.cooperbussmann.com/DatasheetsEle.

Poles 1-Pole 2-Pole 3-Pole 3-Pole 3-Pole 3-Pole

Applicable Fuse Ampacities 15A, 20A, 30A, 40A, 50A, 60A, 70A, 90A, 100A 110A, 125A, 150A, 175A, 200A 225A, 250A, 300A, 250A, 400A 450A, 500A, 600A

Part Number CCPB-1-(amp)CF CCPB-2-(amp)CF CCPB-3-(amp)CF CFD200J03* CFD400J03* CFD600J03*

*3-pole switch for 1- and 2-pole applications

Product Low-Peak Time-Delay CUBEFuse Fast-Acting CUBEFuse Low-Peak LPJ-_SPI Class J fuses Limitron JKS Class J Fuses CCPB Branch Disconnect

Data Sheet Number 9000 2147 1063 1026 & 1027 1161

Additional Reference Additional information is available online at: • Selective Coordination (www.cooperbussmann.com/SelectiveCoordination)

J - Branch Fuses for CCPB Disconnects

For CCPB** Part Number CCPB-(# of Poles)-15CF CCPB-(# of Poles)-20CF CCPB-(# of Poles)-30CF CCPB-(# of Poles)-40CF CCPB-(# of Poles)-50CF CCPB-(# of Poles)-60CF CCPB-(# of Poles)-70CF CCPB-(# of Poles)-90CF CCPB-(# of Poles)-100CF

Non-Indicating Indicating* Fast-Acting Time-Delay Time-Delay Non-Indicating TCF(amps)RN TCF(amps) FCF(amps)RN TCF1RN, TCF3RN, TCF6 FCF1RN, FCF3RN, TCF6RN, TCF10RN TCF10 FCF6RN, FCF10RN TCF15RN TCF15 FCF15RN TCF17-1/2RN TCF17-1/2 FCF20RN TCF20RN TCF20 TCF25RN TCF25 FCF25RN TCF30RN TCF30 FCF30RN TCF35RN TCF35 FCF35RN TCF40RN TCF40 FCF40RN TCF45RN TCF45 FCF45RN TCF50RN TCF50 FCF50RN TCF60RN TCF60 FCF60RN TCF70RN TCF70 FCF70RN TCF80RN TCF80 FCF80RN TCF90RN TCF90 FCF90RN TCF100RN TCF100 FCF100RN

J - Branch Fuses for Class J Disconnects Class J Disconnect Part Number

CFD200J03*

CFD400J03*

CFD600J03*

Non-Indicating Time-Delay LPJ-110SP, LPJ-125SP, LPJ-150SP. LPJ-175SP, LPJ-200SP LPJ-225SP, LPJ-250SP, LPJ-300SP. LPJ-350SP, LPJ-400SP LPJ-450SP, LPJ-500SP, LPJ-600SP.

Indicating Time-Delay LPJ-110SPI, LPJ-125SPI, LPJ-150SPI, LPJ-175SPI, LPJ-200SPI LPJ-225SPI, LPJ-250SPI, LPJ-300SPI, LPJ-350SPI, LPJ-400SPI LPJ-450SPI, LPJ-500SPI, LPJ-600SPI,

Non-Indicating Fast-Acting JKS-110, JKS-125, JKS-150, JKS-175, JKS-200 JKS-225, JKS-250, JKS-300, JKS-350, JKS-400 JKS-450, JKS-500, JKS-600,

*3-Pole switch used for 1- and 2-pole applications.

* Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

0212

BU-SB11645

Page 11 of 11

Data Sheet: 1171