E-Z-Ground® Grounding Connectors

Report 1 Downloads 111 Views
E-Z-Ground Grounding Connectors ®

DB

H

MEETS

IEEE

L Dimension (in.) main

tap

h

L

Dies for TBM14M 13100A or TBM15I *

crimps

#6 Sol.–#2 Str. #1 Str.–2/0 Str. #1 Str.–2/0 Str. 3/0 Str.–250 kcmil 3/0 Str.–250 kcmil 300–500 kcmil 300–500 kcmil 300–500 kcmil

#6 Sol.–#2 Str.** #6 Sol.–#2 Str.** #1 Str.–2/0 Str. #6 Sol.–2/0** 3/0 Str.–250 kcmil #6 Sol.–2/0** 3/0 Str.–250 kcmil 300–500 kcmil

1.16 1.41 1.54 1.97 2.06 2.42 2.67 2.91

.75 .75 .75 .75 .88 .88 .88 1.10

HBKC 15501A 15501A 15G86R 15G86R 15G121R 15G121R 15G121R

1 1 1 1 1 2 2 3

Cat. No. CTP22 CTP202 CTP2020 CTP25020 CTP250250 CTP50020 CTP500250 CTP500500

837 REQUIREMENTS

Material: High-Conductivity Copper. * Cat. No. 15500 adapter required if using TBM15I and 155XX series dies. ** #6 AWG branch must be doubled.

Copper C-Crimps ††

Connectors & Grounding — Blackburn® Grounding Systems

C-Taps

L

H

DB run

tap

die index

installing die tbm14m 13100a, tbm151

#6 Sol.–#4 Str. #6 Sol.–#4 Str. #6 Sol.–#4 Str. #2 Sol.–#2 Str. #2 Sol.–#2 Str. 1/0 Sol.–2/0 Str. 1/0 Sol.–2/0 Str. 3/0 Str.–4/0 Str. 3/0 Str.–4/0 Str. 3/0 Str.–4/0 Str.

#8 Sol.–#8 Str. #6 Sol.–#6 Str. #4 Sol.–#4 Str. #8 Sol.–#4 Str. #2 Sol.–#2 Str. #8 Sol.–#2 Str. 1/0 Str.–2/0 Str. #6 Sol.–#2 Str. 1/0 Sol.–2/0 Str. 3/0 Sol.–4/0 Str.

BG or 5⁄8 BG or 5⁄8 BG or 5⁄8 C C E or O E or O F or D3 F or D3 F or D3

B58CS B58CS B58CS HBKC HBKC HO HO HD HD HD

Cat. No. BC48 BC46-BB BC44 BC24 BC22 BC202 BC2020-BB BC402 BC4020 BC4040 ††

Dimension (in.) h

L

⁄64 41 ⁄64 41 ⁄64 3 ⁄4 3 ⁄4 15 ⁄16 15 ⁄16 11⁄16 11⁄16 11⁄16

⁄16 ⁄4 51 ⁄64 63 ⁄64 13⁄64 15⁄16 111⁄32 15⁄8 15⁄16 15⁄16

41

9

3

Does not meet IEEE 837.

Material: High-Conductivity Copper. UL 467 Listed. Tooling: pp. F-80–F-100. Die Selector Chart: pp. F-101–F-104.

www.tnb.com

United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354

Technical Services Tel: 888.862.3289

F-261