Fax Coversheet

Report 25 Downloads 247 Views
Submittal Comments

MEJ & ASSOC., INC. Consulting Engineers 811 Barton Springs Rd., Suite 700 Austin, TX 78704 (512) 457-8771 FAX (512) 457-8743 Email: [email protected]

Date:

May 18, 2016

By:

Jeni Hudgeons, P.E.

Project:

TARC, 201 W. 5th

MEJ #:

16-120

Submittal #:

15500.04

Submittal: Water Cooled DX Unit

   

No Exception Taken Make Corrections Noted Revise and Resubmit Not Required For Review

 Note: Checking is only for general conformance with the design concept of the project

and general compliance with the information given in the contract documents. Any action shown is subject to the requirements of the plans and specifications. Contractor is responsible for; dimensions, which shall be confirmed and correlated at the job site; fabrication processes and techniques of construction; coordination of his work with that of all other trades; and the satisfactory performance of his work.

 Comments: Make Corrections Noted. 1. Alternate Unit does not provide the sensible capacity of the scheduled unit, and is under by ~5%. 2. Coordinate exact MOP required with Electrical Contractor. 3. Verify EER at AHRI conditions exceed the scheduled requirement at 13.4 EER

SUBMITTAL Texas American Resource Center 4/19/2016

Contractor: TDIndustries, Inc. 2701 Gattis School Rd. Building A, Suite 101 Round Rock, Texas 78664 Project Manager: Janie Mendiola Phone: (512) 848-0074

Supplier / Subcontractor: HTS 6101 West Courtyard Drive, Bdlg #4 Austin, TX 78730 512-381-0091 512-381-0117

Specification Section: Water Cooled DX Unit

Remarks:

HTS Texas 6101 W. Courtyard Bldg #4 Austin, TX 78730 P 512.381.0091 F 832.328.1460

SUBMITTAL DATA APPROVAL REQUIRED PROJECT

: Texas American Resources

HTS JOB NUMBER

: 2161279

SOLD TO

: TD Industries

MECHANICAL CONSULTANT : MEJ & Associates SHIPPING ADDRESS

: TBD

HTS SALESPERSON

: Kyle Kramer, David Driggers

DATE

: 4/11/16

REVISION NUMBER SPECIFICATION SECTION STANDARD LEAD TIME

: 0 : N/A : 8-10 Weeks

TAG

QTY

DESCRIPTION

MODEL

MANUFACTURER

WCP16-1

1

Water Cooled DX Unit

WCCW

Daikin Applied

APPROVAL STAMPS

Certified Drawing

CCH-CCW-R410-060 Specs Group: WSHP

The Water Source Heat Pump product represented on this document will conform to the drawings and specifications set out below, in accordance with the express, written Limited Warranty. Purchaser’s acceptance of this drawing certifies that the conforming equipment meets the order specifications. No changes may be made to this document without the prior, express, written authorization of the manufacturer.

Type: Horizontal Date: April 2016

Daikin Horizontal WSHP Model CCH & CCW – Size 060

Left Hand Return, End and Straight Discharge (R-410A Refrigerant) Features

Electronically Commutated Motor (Optional) - The ECM fan motor offers higher efficiency than the standard fan motor as well as a constant volume of air being moved over the static pressure operating range of the WSHP.

Range of Operation - CCH-Standard (55º to 110ºF), CCW-Geothermal (30º to 110ºF). Cabinet - Heavy-gauge unpainted G-60 galvanized steel.

Electrical - The control box is accessible through a panel, and houses major electrical controls including the control circuit board, transformer, compressor relay and fan relay.

Insulation - 1/2" thick, 1-1/2 lb. dual density fiber glass. IAQ closed-cell foam insulation also available as an option.

MicroTech™ III Unit Controller – Designed for flexibility, the main control board is used in standalone applications. A separate LonWorks® or BACnet® communication module can be easily snapped onto the board to accommodate the building automation system of your choice.

Drain Pan - ABS plastic, corrosion-resistant, double-sloped, for positive draining to reduce standing water, microbial growth and promote good indoor air quality. Filter - 1" thick throwaway type, mounted in a combination filter rack/return air duct collar. Filters can be removed from the side or bottom. A 2" filter rack is available as a factory-installed selectable option to accept higher efficiency filters. Refrigerant Circuit - Includes a scroll compressor, reversing valve, water-to-refrigerant heat exchanger, TXV expansion device, airside coil, high/low side refrigerant access valves, and safety controls.

Overall unit dimensions = 28"W x 52"L x 23"H

Safety Controls - Low suction temperature sensor, electronic condensate overflow protection and high pressure switches to lock out compressor operation at extreme conditions.

Dimensions are approximate.

1"

E

Y

1" 1"

Low Voltage

W

P

P1 - Bracket locations for units with non-fused disconnect (gray tint)

Water Supply

Water Return

Line Voltage

A

C

F

Removable Access Panel to Compressor

L

Z

Straight Discharge Position

K

Right and left hand return determined by facing the water connection side of the unit.

Fan Section - Direct drive centrifugal fan. The housing has a removable orifice ring to facilitate fan motor and fan wheel removal. The fan housing protrudes through the cabinet to facilitate field duct connection. Units have a straight-through or end discharge air arrangement, and can be field converted from one to the other without the use of additional parts. Blower Housing Assembly Converts from Straight Discharge to End Discharge

P1

1"

D

F M

H A

N

V

Return Air - Filters (2)

End Discharge View

G

J Removable Access Panel

T

R Condensate Drain Connection

Straight Discharge View

Dimensional data (in inches) Unit Size

A

060

14.68

B 4.89

C

D

1.45

19.43

E 5.76

F 13.43

G

H

8.06

1.95

J

K

L

3.60

23

17.43

M 5.60

N

P

P1

R

T

V

W

Y

Z

1.25

52

48.80

3.74

1.45

28

52

23

25.50

B

Daikin Horizontal WSHP Model CCH & CCW – Size 060 Right Hand Return, End and Straight Discharge (R-410A Refrigerant)

Overall unit dimensions = 28"W x 52"L x 23"H

P1

1"

1"

K

Dimensions are approximate. Z

Right and left hand return determined by facing the water connection side of the unit.

Water Supply C

Water Return

Low Voltage

1"

W

A

1"

P1 - Bracket locations for units with non-fused disconnect (gray tint)

E

F L

Y

F H

M

J T

P

Blower Housing Assembly Converts from Straight Discharge to End Discharge

Line Voltage

Removable Access Panel to Compressor

D

Straight Discharge Position

N R Condensate Drain Connection

G

V Return Air - Filter

A

B

End Discharge View

Removable Access Panel

Straight Discharge View

Dimensional data (in inches) Unit Size

A

060

14.68

B 4.89

C

D

1.45

19.43

E 5.76

F 13.43

G

H

1.95

8.06

J

K

L

3.60

30

17.43

M 5.60

N

P

P1

R

T

V

W

Y

Z

1.25

52

48.80

3.74

1.45

28

52

23

25.50

Physical Data (in inches)

Unit Size

Fan Wheel - D x W Standard PSC Motor Horsepower Coil Face Area (Sq. Ft.) Coil Rows Refrigerant Charge (oz.)





060 12.9 x 11.1

1-inch Filter, (Qty.) Size (In.)

3/4 6.11 3 74 oz. (2) 22H x 22W

Water Connections, FPT Condensate Connections, FPT Weight, Operate (Lbs.) Weight, Shipping (Lbs.) 2-inch Filter (Qty) Size (in.)

3/4 3/4 I.D. 332 351 (1)21.5H x 46.5W

© 2016 Daikin Applied • www.DaikinApplied.com • (800) 432–1342

CCH-CCW-R410-060 Specs

Filter Racks / Return Air Duct Collars Dimensions – Size 060 1" Standard Filter Rack Left Hand Return, End Discharge

Optional 2" Filter Rack

1.06"

1.66"

20.98"

44.20" 2.16"

1" Standard Filter Rack – Right Hand Return, End Discharge 1.06" 2.06" 2.60" 20.98"

1.66"

46.9" 46.9"

44.20"

21.54"

20.22"

2.16"

Hanger Kit Detail 3/8" (10 mm) Threaded Rod (By Others) Bolt and Lock Washer

Vibration Isolator Washer Hex Nuts (By Others)

© 2016 Daikin Applied • www.DaikinApplied.com • (800) 432–1342

CCH-CCW-R410-060 Specs

Ductwork and Sound Attenuation Considerations

Ductwork is normally applied to ceiling-mounted heat pumps on the discharge side of the unit. A discharge collar is provided on all horizontal unit models for fastening the ductwork. Use a flexible connector between the discharge collar and the duct transformation to help reduce vibration transmission from the cabinet and to simplify disconnection of the unit from the ceiling ductwork. If return ductwork is to be used, attach a flexible connector to the filter rack collar to help reduce vibration transmission and removal of the unit. Return plenum ducting should be at least 12 inches away from the coil so that the coil is evenly loaded with return air. As a general recommendation, duct interiors should have an acoustic / thermal lining at least 1/2 inch thick over the entire duct run. For better sound attenuation, line the last five diameters of duct before each register with a one-inch thick sound blanket. Elbows, tees and dampers can create turbulence or distortion in the airflow. Place a straight length of duct, 5 to 10 times the duct width, before the next fitting to smooth out airflow. Diffusers that are located in the bottom of a trunk duct can also produce noise. For this same reason, volume control dampers should be located several duct widths upstream from an air outlet. For Hotel, Motel, Dormitory or Nursing Home applications that use a single duct discharge, a velocity of 500 to 600 fpm is suggested. These applications typically have static pressures as low as 0.05 inches of water and duct lengths approximately six feet in length. The discharge duct must be fully lined and have a square elbow without turning vanes. Return air for these applications should enter through a “low” sidewall filter grille and route up the stud space to a ceiling plenum. For horizontal heat pumps mounted from the ceiling, an insulated return plenum is sometimes placed at the return air opening to further attenuate line-of-sight sound transmission through return openings.

Suggested Supply & Return Ducting

Suggested Supply Ducting per ASHRAE and SMACNA Publications Flexible Connector

Ductwork Supported Independent of Unit

Acoustic/Thermal Lining 3ft. (.9m) to 5ft. (1.5m)

Acoustic/Thermal Lining

Diffuser

Two 90° Turns (Ductwork Sized Based on Airflow)

Diffuser

Suggested Return Ducting per ASHRAE and SMACNA Publications Two 90° Turns Prior to the Intake (Ductwork Sized Based on Airflow)

Flexible Connector

Acoustic/Thermal Lining Acoustic/Thermal Lining

Acoustic/Thermal Lining 10ft. (3 meters) Return Air Intake Located Away from the Unit Blower

© 2016 Daikin Applied • www.DaikinApplied.com • (800) 432–1342

Flexible Connector Ductwork Supported Independent of Unit

CCH-CCW-R410-060 Specs

ENFINITY™ Heat Pump Job Information Job Name Date Submitted By Software Version Unit Tag

Technical Data Sheet 1279 Texas American Resource Co 4/11/2016 David Driggers 04.30 WCP16-1

Unit Overview Model Number WCCW5060

Voltage

Air Flow

Fluid Flow

V/Hz/Phase

CFM

gpm

Cooling Capacity

Cooling Efficiency

Heating Capacity

Heating Efficiency

Btu/hr

460/60/3

1900

10.30

54187

EER @ design

Btu/hr

COP @ design

12.64

69188

4.47

Unit Model Number: Unit Type: Unit Construction: Approval:

WCCW5060 Enfinity - Ceiling Mounted, Geothermal Range Standard Construction ETL, CETL, ARI Refrigerant Type

Refrigerant Weight

R-410A

74.0

oz

Unit Performance Air & Water Flow Airflow

Total External Static Pressure

Fluid Flow

Fluid Type

1900 CFM

0.50 inH O

10.30 gpm / 2.06 gpm/ton

Water

Fluid Pressure Drop

8.31

ft H O

Cooling Performance Fluid Temperature Entering Leaving °F °F

86.0

Air Temperature Entering Leaving Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F

99.4

75.0

63.0

55.8

52.9

Total Btu/hr

Capacity Sensible Btu/hr

54187

39271

Heat of Rejection Btu/hr

EER @ design

68816

12.64

Heating Performance Fluid Temperature Entering Leaving °F °F

70.0

Air Temperature Entering Leaving Dry Bulb Dry Bulb °F °F

59.6

70.0

103.6

Capacity Total Btu/hr

Heat of Absorption Btu/hr

COP @ design

69188

53705

4.47

Electrical Unit Voltage

Minimum Voltage

Total Unit MCA

Total Unit Full Load Current

460/60/3

416 V

11.70 A

9.80 A

Compressor RLA

Compressor LRA

Motor FLA

Maximum Recommended Fuse Size / HACR Breaker Size

7.80 A

52.0 A

2.00 A

15 A

Page 1 of 2

www.DaikinApplied.com

ENFINITY™ Heat Pump Physical Unit Length

Height

52.00 in

Width

23.00 in

Weight

28.00 in

Shipping

Operating

Water, FPT

351 lb

332 lb

0.75

Connections Condensate, FPT

0.75 in

Cabinet Construction Type

Color

Standard Construction

Galvanized Fan

Type

Controls

Motor

DWDI Centrifugal

Type

Horsepower

Drive Type

Standard PSC

0.750 hp

Direct

Type

Microtech III Standalone

Airstream Air Discharge

Return

Filter (Quantity) Height x Width x Depth

End Discharge

Left Hand Return Air

(2) 22 in x 22 in x 1 in

Options Heating Heat Exchanger:

Copper Inner Tube / Steel Outer Tube Controls

Control Transformer:

50VA Control Transformer

Warranty Unit Warranty:

4 Year Extended Complete Unit Parts Warranty

AHRI Certification All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada.

Page 2 of 2

www.DaikinApplied.com