Greengate Occupancy Sensor Guide

Report 30 Downloads 113 Views
Sensor Technologies Passive Infrared Relay (PIR) Technology • •

Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.

Using this paper versus standard paper produced the following environmental benefits.

Based on Environmental Defense Fund Paper Calculator

Dual Technology • • •

Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.

Self-Adaptive Technology • •

Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.

About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.

Number of Trees Saved

12

Total Energy Saved—Million BTU’s

7.9

Greenhouse Gas Reduction—lbs of CO2

4391

Gallons of Water Saved

4129

Solid Waste Reduction— lbs of Waste

683

Kilo-watt (kwh) Hours Saved

1702

North America Headquarters 203 Cooper Circle Peachtree City, GA 30269

Service & Support Center 6 Green Tree Drive South Burlington, VT 05403

P: 800-553-3879 F: 800-954-7016

P: 800-553-3879 F: 800-954-7016

Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com [email protected]

www.coopercontrol.com [email protected]

As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.

LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.

California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •

Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size

Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.

IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.

Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.

Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com

ACC101050

Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.

Printed in USA

Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049

10/11

Greengate Occupancy Sensor Guide

Occupancy Sensor Application Guide Commercial Wall Switch Sensors

Commercial Low Voltage Ceiling Sensors

Commercial Line Voltage Ceiling Sensors

PIR1500-120-347

US1500-120 or 277

US2000-120 or 277

DT2000-120 or 277

OXC-P-2MH0-R

OXC-P-1500-R

ODC-U-0100-H

ODC-U-0501-H

OMC-DT-0701-R

OMC-DT-2000-R

OMC-U-2000

OMC-U-1001

OMC-U-0501

OMC-P-1200-R

OMC-P-0450-R

VNLW-P-1001-MV-N-*

ONW-P-1001-RR7-*

ONW-P-1001-SP-*

ONW-P-1001-D347-*

ONW-P-1001-347-*

ONW-P-1001-DMV-*

ONW-P-1001-MV-*

ONW-D-1001-DMV-N*

ONW-D-1001-MV-N-*

ONW-D-1001-DMV-*

ONW-D-1001-MV-*

OSW-U-0721-24AC-R-*

OSW-U-0721-GERR7-*

Specification Grade

OSW-U-0721-SP-*

OSW-U-0721-MV-*

OSW-P-0451-D347-*

OSW-P-0451-347-*

OSW-P-0451-MV-*

OSW-P-0451-DMV-*

Commercial Grade

Specifications Technology

Passive Infrared

Ultrasonic

Dual Technology

Mounting Coverage (Sq ft)

450

1000

Ultrasonic

1200

347V

120 to 277V

Not Required

Photocell

10-30VDC

RR7 Relay

Required

RR7 Relay Required

Dual Technology

24 VAC Supply 24 VAC Required

120 to 277V

347

Environmental Operating Temperature/Humidity Available Colors

Not Required

Included

SP, 3-Way*, No Neutral Required

Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*, No Neutral Required

W, V Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*

SP

700

360° 8-12’

50 linear

10-30VDC

Required

RR7 Relay Required

24 VAC Required Not Included

SP, 3-Way*, Light Icon, EcoMeter

Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

Not Included

Internal OMC-U0501-R

Included

OMC-U1001-R

OMC-U2000-R

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

SP, 3-Way* Night Light

GOOD BEST

BEST

BEST

BEST

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD GOOD GOOD GOOD GOOD

GOOD BETTER

GOOD

GOOD

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BEST BEST

BEST BEST

BEST BEST

BEST BEST

GOOD BETTER

GOOD BETTER

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BEST BETTER

BEST BETTER

BEST BEST

BEST BEST

BEST BEST

BEST BEST

BETTER BETTER

BETTER BETTER

BETTER BETTER

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD

BETTER GOOD BEST BEST

BETTER GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BEST BETTER GOOD BEST BEST

BETTER BEST BETTER GOOD BEST BEST

BEST

GOOD BETTER

GOOD BETTER

GOOD BETTER

BETTER GOOD GOOD

BETTER GOOD GOOD

BETTER GOOD GOOD

GOOD

BETTER

BETTER

BETTER

BETTER

BEST

BEST

BEST

BEST

BETTER

BETTER

8-12’ Manual Adjustment

8-15’

120 to 347V

Not Required Internal ODC-U0051-R-H

Included

ODC-U0100-R-H

Not Included

Included

Internal

Not Included

-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing

32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing

W

W

Up to 5 sensors can be used per switchpack

No switchpack required

Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST

Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD

GOOD BEST

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BEST BETTER GOOD

BETTER BETTER BEST BEST BEST BEST BEST

BETTER

BETTER

BEST

BEST

BEST

BETTER

BEST BEST BEST

BEST BEST BEST

BETTER BETTER BETTER

GOOD BEST BETTER BEST BETTER GOOD

BEST

BEST

BETTER BETTER

BEST BEST

BEST

BEST

BETTER

BETTER

BEST BETTER BETTER

BEST BETTER BETTER

BEST BETTER BETTER

GOOD GOOD

BETTER GOOD GOOD

BEST BEST

GOOD GOOD

GOOD BETTER

BETTER BETTER

BEST BEST

BEST BEST BETTER

BETTER BETTER BEST

BETTER BETTER BETTER

BEST BEST BEST

BETTER

BEST

BEST

BETTER BETTER BETTER

BEST BETTER BETTER

BEST

GOOD BEST BEST

BEST

BETTER

BETTER

GOOD

GOOD BEST

GOOD

BEST BEST BETTER BETTER

GOOD GOOD GOOD

BEST BEST BETTER

BEST GOOD BEST BEST

GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD

3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black

1500

15 sec to 30 min

BEST BEST BEST

2000

up to 25’ Self-Adjust

GOOD GOOD BETTER

BETTER BEST

2MHO

120 or 277V

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing

SP, Light Icon, EcoMeter

Passive Infrared

Ultrasonic

360°

Not Included

W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

1500

Required Internal

Commercial Wall Switch Sensors

BETTER BEST

Dual Technology

360° Manual Adjustment

15 sec to 30 min

Included

100 linear

180°

120 to 277V

W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode

2000

15 sec to 2 hr

32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode

1000 180°

RR7 Relay

Not Included

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A

Passive Infrared

Ceiling

10-30VDC

Internal

Not Included

Ultrasonic

Self-Adjust

Not Included

BAS/HVAC Relay

500

360°

15 sec to 30 min 120 or 277V

Power Pack

Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General

450

180° 4’ Self-Adjusting

Time Delay

Feature

Passive Infrared

Ceiling

720

Pattern Mounting Height (ft) Adjustment

Voltage

Passive Infrared

Wall Switch

BETTER

BETTER

BETTER

BETTER

GOOD

GOOD

BETTER

BETTER

BETTER

BEST

BEST

GOOD

BEST BEST

Occupancy Sensor Application Guide Commercial Wall Switch Sensors

Commercial Low Voltage Ceiling Sensors

Commercial Line Voltage Ceiling Sensors

PIR1500-120-347

US1500-120 or 277

US2000-120 or 277

DT2000-120 or 277

OXC-P-2MH0-R

OXC-P-1500-R

ODC-U-0100-H

ODC-U-0501-H

OMC-DT-0701-R

OMC-DT-2000-R

OMC-U-2000

OMC-U-1001

OMC-U-0501

OMC-P-1200-R

OMC-P-0450-R

VNLW-P-1001-MV-N-*

ONW-P-1001-RR7-*

ONW-P-1001-SP-*

ONW-P-1001-D347-*

ONW-P-1001-347-*

ONW-P-1001-DMV-*

ONW-P-1001-MV-*

ONW-D-1001-DMV-N*

ONW-D-1001-MV-N-*

ONW-D-1001-DMV-*

ONW-D-1001-MV-*

OSW-U-0721-24AC-R-*

OSW-U-0721-GERR7-*

Specification Grade

OSW-U-0721-SP-*

OSW-U-0721-MV-*

OSW-P-0451-D347-*

OSW-P-0451-347-*

OSW-P-0451-MV-*

OSW-P-0451-DMV-*

Commercial Grade

Specifications Technology

Passive Infrared

Ultrasonic

Dual Technology

Mounting Coverage (Sq ft)

450

1000

Ultrasonic

1200

347V

120 to 277V

Not Required

Photocell

10-30VDC

RR7 Relay

Required

RR7 Relay Required

Dual Technology

24 VAC Supply 24 VAC Required

120 to 277V

347

Environmental Operating Temperature/Humidity Available Colors

Not Required

Included

SP, 3-Way*, No Neutral Required

Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*, No Neutral Required

W, V Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*

SP

700

360° 8-12’

50 linear

10-30VDC

Required

RR7 Relay Required

24 VAC Required Not Included

SP, 3-Way*, Light Icon, EcoMeter

Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

Not Included

Internal OMC-U0501-R

Included

OMC-U1001-R

OMC-U2000-R

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

SP, 3-Way* Night Light

GOOD BEST

BEST

BEST

BEST

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD GOOD GOOD GOOD GOOD

GOOD BETTER

GOOD

GOOD

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BEST BEST

BEST BEST

BEST BEST

BEST BEST

GOOD BETTER

GOOD BETTER

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BEST BETTER

BEST BETTER

BEST BEST

BEST BEST

BEST BEST

BEST BEST

BETTER BETTER

BETTER BETTER

BETTER BETTER

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD

BETTER GOOD BEST BEST

BETTER GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BEST BETTER GOOD BEST BEST

BETTER BEST BETTER GOOD BEST BEST

BEST

GOOD BETTER

GOOD BETTER

GOOD BETTER

BETTER GOOD GOOD

BETTER GOOD GOOD

BETTER GOOD GOOD

GOOD

BETTER

BETTER

BETTER

BETTER

BEST

BEST

BEST

BEST

BETTER

BETTER

8-12’ Manual Adjustment

8-15’

120 to 347V

Not Required Internal ODC-U0051-R-H

Included

ODC-U0100-R-H

Not Included

Included

Internal

Not Included

-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing

32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing

W

W

Up to 5 sensors can be used per switchpack

No switchpack required

Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST

Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD

GOOD BEST

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BEST BETTER GOOD

BETTER BETTER BEST BEST BEST BEST BEST

BETTER

BETTER

BEST

BEST

BEST

BETTER

BEST BEST BEST

BEST BEST BEST

BETTER BETTER BETTER

GOOD BEST BETTER BEST BETTER GOOD

BEST

BEST

BETTER BETTER

BEST BEST

BEST

BEST

BETTER

BETTER

BEST BETTER BETTER

BEST BETTER BETTER

BEST BETTER BETTER

GOOD GOOD

BETTER GOOD GOOD

BEST BEST

GOOD GOOD

GOOD BETTER

BETTER BETTER

BEST BEST

BEST BEST BETTER

BETTER BETTER BEST

BETTER BETTER BETTER

BEST BEST BEST

BETTER

BEST

BEST

BETTER BETTER BETTER

BEST BETTER BETTER

BEST

GOOD BEST BEST

BEST

BETTER

BETTER

GOOD

GOOD BEST

GOOD

BEST BEST BETTER BETTER

GOOD GOOD GOOD

BEST BEST BETTER

BEST GOOD BEST BEST

GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD

3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black

1500

15 sec to 30 min

BEST BEST BEST

2000

up to 25’ Self-Adjust

GOOD GOOD BETTER

BETTER BEST

2MHO

120 or 277V

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing

SP, Light Icon, EcoMeter

Passive Infrared

Ultrasonic

360°

Not Included

W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

1500

Required Internal

Commercial Wall Switch Sensors

BETTER BEST

Dual Technology

360° Manual Adjustment

15 sec to 30 min

Included

100 linear

180°

120 to 277V

W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode

2000

15 sec to 2 hr

32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode

1000 180°

RR7 Relay

Not Included

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A

Passive Infrared

Ceiling

10-30VDC

Internal

Not Included

Ultrasonic

Self-Adjust

Not Included

BAS/HVAC Relay

500

360°

15 sec to 30 min 120 or 277V

Power Pack

Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General

450

180° 4’ Self-Adjusting

Time Delay

Feature

Passive Infrared

Ceiling

720

Pattern Mounting Height (ft) Adjustment

Voltage

Passive Infrared

Wall Switch

BETTER

BETTER

BETTER

BETTER

GOOD

GOOD

BETTER

BETTER

BETTER

BEST

BEST

GOOD

BEST BEST

Occupancy Sensor Application Guide Commercial Wall Switch Sensors

Commercial Low Voltage Ceiling Sensors

Commercial Line Voltage Ceiling Sensors

PIR1500-120-347

US1500-120 or 277

US2000-120 or 277

DT2000-120 or 277

OXC-P-2MH0-R

OXC-P-1500-R

ODC-U-0100-H

ODC-U-0501-H

OMC-DT-0701-R

OMC-DT-2000-R

OMC-U-2000

OMC-U-1001

OMC-U-0501

OMC-P-1200-R

OMC-P-0450-R

VNLW-P-1001-MV-N-*

ONW-P-1001-RR7-*

ONW-P-1001-SP-*

ONW-P-1001-D347-*

ONW-P-1001-347-*

ONW-P-1001-DMV-*

ONW-P-1001-MV-*

ONW-D-1001-DMV-N*

ONW-D-1001-MV-N-*

ONW-D-1001-DMV-*

ONW-D-1001-MV-*

OSW-U-0721-24AC-R-*

OSW-U-0721-GERR7-*

Specification Grade

OSW-U-0721-SP-*

OSW-U-0721-MV-*

OSW-P-0451-D347-*

OSW-P-0451-347-*

OSW-P-0451-MV-*

OSW-P-0451-DMV-*

Commercial Grade

Specifications Technology

Passive Infrared

Ultrasonic

Dual Technology

Mounting Coverage (Sq ft)

450

1000

Ultrasonic

1200

347V

120 to 277V

Not Required

Photocell

10-30VDC

RR7 Relay

Required

RR7 Relay Required

Dual Technology

24 VAC Supply 24 VAC Required

120 to 277V

347

Environmental Operating Temperature/Humidity Available Colors

Not Required

Included

SP, 3-Way*, No Neutral Required

Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*, No Neutral Required

W, V Dual Relay, 3-Way*, No Neutral Required

SP, 3-Way*

SP

700

360° 8-12’

50 linear

10-30VDC

Required

RR7 Relay Required

24 VAC Required Not Included

SP, 3-Way*, Light Icon, EcoMeter

Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

Not Included

Internal OMC-U0501-R

Included

OMC-U1001-R

OMC-U2000-R

SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter

SP, 3-Way* Night Light

GOOD BEST

BEST

BEST

BEST

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BEST BETTER BETTER BEST

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

BETTER BEST GOOD GOOD

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD BEST BETTER

GOOD GOOD GOOD GOOD GOOD GOOD

GOOD BETTER

GOOD

GOOD

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BEST BEST

BEST BEST

BEST BEST

BEST BEST

GOOD BETTER

GOOD BETTER

GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BETTER BETTER

BEST BETTER

BEST BETTER

BEST BEST

BEST BEST

BEST BEST

BEST BEST

BETTER BETTER

BETTER BETTER

BETTER BETTER

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD GOOD

GOOD

BETTER GOOD BEST BEST

BETTER GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BEST

GOOD BEST BEST

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BETTER BEST BETTER BETTER BETTER BETTER

BETTER BEST BETTER GOOD BEST BEST

BETTER BEST BETTER GOOD BEST BEST

BEST

GOOD BETTER

GOOD BETTER

GOOD BETTER

BETTER GOOD GOOD

BETTER GOOD GOOD

BETTER GOOD GOOD

GOOD

BETTER

BETTER

BETTER

BETTER

BEST

BEST

BEST

BEST

BETTER

BETTER

8-12’ Manual Adjustment

8-15’

120 to 347V

Not Required Internal ODC-U0051-R-H

Included

ODC-U0100-R-H

Not Included

Included

Internal

Not Included

-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing

32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing

W

W

Up to 5 sensors can be used per switchpack

No switchpack required

Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST

Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD

GOOD BEST

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BETTER BEST BETTER BEST BETTER

BEST BETTER GOOD

BETTER BETTER BEST BEST BEST BEST BEST

BETTER

BETTER

BEST

BEST

BEST

BETTER

BEST BEST BEST

BEST BEST BEST

BETTER BETTER BETTER

GOOD BEST BETTER BEST BETTER GOOD

BEST

BEST

BETTER BETTER

BEST BEST

BEST

BEST

BETTER

BETTER

BEST BETTER BETTER

BEST BETTER BETTER

BEST BETTER BETTER

GOOD GOOD

BETTER GOOD GOOD

BEST BEST

GOOD GOOD

GOOD BETTER

BETTER BETTER

BEST BEST

BEST BEST BETTER

BETTER BETTER BEST

BETTER BETTER BETTER

BEST BEST BEST

BETTER

BEST

BEST

BETTER BETTER BETTER

BEST BETTER BETTER

BEST

GOOD BEST BEST

BEST

BETTER

BETTER

GOOD

GOOD BEST

GOOD

BEST BEST BETTER BETTER

GOOD GOOD GOOD

BEST BEST BETTER

BEST GOOD BEST BEST

GOOD BEST BEST

GOOD BEST BEST

BEST

GOOD

3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black

1500

15 sec to 30 min

BEST BEST BEST

2000

up to 25’ Self-Adjust

GOOD GOOD BETTER

BETTER BEST

2MHO

120 or 277V

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing

SP, Light Icon, EcoMeter

Passive Infrared

Ultrasonic

360°

Not Included

W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter

1500

Required Internal

Commercial Wall Switch Sensors

BETTER BEST

Dual Technology

360° Manual Adjustment

15 sec to 30 min

Included

100 linear

180°

120 to 277V

W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode

2000

15 sec to 2 hr

32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing

Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode

1000 180°

RR7 Relay

Not Included

60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A

Passive Infrared

Ceiling

10-30VDC

Internal

Not Included

Ultrasonic

Self-Adjust

Not Included

BAS/HVAC Relay

500

360°

15 sec to 30 min 120 or 277V

Power Pack

Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General

450

180° 4’ Self-Adjusting

Time Delay

Feature

Passive Infrared

Ceiling

720

Pattern Mounting Height (ft) Adjustment

Voltage

Passive Infrared

Wall Switch

BETTER

BETTER

BETTER

BETTER

GOOD

GOOD

BETTER

BETTER

BETTER

BEST

BEST

GOOD

BEST BEST

Sensor Technologies Passive Infrared Relay (PIR) Technology • •

Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.

Using this paper versus standard paper produced the following environmental benefits.

Based on Environmental Defense Fund Paper Calculator

Dual Technology • • •

Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.

Self-Adaptive Technology • •

Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.

About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.

Number of Trees Saved

12

Total Energy Saved—Million BTU’s

7.9

Greenhouse Gas Reduction—lbs of CO2

4391

Gallons of Water Saved

4129

Solid Waste Reduction— lbs of Waste

683

Kilo-watt (kwh) Hours Saved

1702

North America Headquarters 203 Cooper Circle Peachtree City, GA 30269

Service & Support Center 6 Green Tree Drive South Burlington, VT 05403

P: 800-553-3879 F: 800-954-7016

P: 800-553-3879 F: 800-954-7016

Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com [email protected]

www.coopercontrol.com [email protected]

As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.

LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.

California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •

Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size

Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.

IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.

Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.

Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com

ACC101050

Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.

Printed in USA

Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049

10/11

Greengate Occupancy Sensor Guide

Sensor Technologies Passive Infrared Relay (PIR) Technology • •

Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.

Using this paper versus standard paper produced the following environmental benefits.

Based on Environmental Defense Fund Paper Calculator

Dual Technology • • •

Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.

Self-Adaptive Technology • •

Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.

About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.

Number of Trees Saved

12

Total Energy Saved—Million BTU’s

7.9

Greenhouse Gas Reduction—lbs of CO2

4391

Gallons of Water Saved

4129

Solid Waste Reduction— lbs of Waste

683

Kilo-watt (kwh) Hours Saved

1702

North America Headquarters 203 Cooper Circle Peachtree City, GA 30269

Service & Support Center 6 Green Tree Drive South Burlington, VT 05403

P: 800-553-3879 F: 800-954-7016

P: 800-553-3879 F: 800-954-7016

Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com [email protected]

www.coopercontrol.com [email protected]

As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.

LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.

California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •

Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size

Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.

IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.

Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.

Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com

ACC101050

Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.

Printed in USA

Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049

10/11

Greengate Occupancy Sensor Guide