Hard Wired 30 Ampere GFCI - NEMA 4X

Report 1 Downloads 89 Views
Ground Fault Products

Hard Wired 30 Ampere GFCI - NEMA 4X Applications Power Generators Submersible Pumps Textile

Agricultural Equipment Cement Cutting Equipment Food Processing

Production Assembly Equipment Spa and Hot Tubs Vending Equipment

Circuit Guard® Hard Wired 30A GFCI - UL Type 4X Rated

Automatic Reset GFCI

Description

Voltage

Alarm

Manual Set

Automatic Set

Hard wired, manual set and automatic set GFCIs.

120V AC 120V AC 240V AC 240V AC 120/240V AC 3Ø 250V AC 3Ø 120/208V AC

None Audible None Audible Audible None None

GFHW13005 GFHW13015 GFHW23005 GFHW23015 GFHW33015 GFHW530 GFHW430

GFHW13105 GFHW13115 GFHW23105 GFHW23115 GFHW33115 GFHW531 GFHW431

Note: All units above are stock items.

Specifications Manual Reset GFCI

Electrical Ratings

Rated Voltage Operating Voltage Range Current Frequency Trip Level Phase Response Time Dielectric Withstand Surge Withstand Let Go Line Voltage Grounded Neutral Detection Power Up

120V AC, 240V AC and 120/240V, 3Ø 250V AC, 3Ø 120/208V AC. 85% to 110%. Up to 30A or device rating. 60 Hz. 4-6 mA. Single. .025 sec. Max. 1500 VRMS across contact, 4000 VRMS between conductors and enclosure. 6000V impulse, 0.5 microseconds rise time 100kHz ringing frequency with 40% decay per cycle. 60% of rated. 6 Ohms or less. Manual or automatic reset.

3.37" (85.6)

4.80" (121.9)

2.82" (12.9)

Environmental Ratings

Housing Rating Construction Type Operating Temperature Leakage Current @ 93% Humidity

UL Type 4X. Industrial grade design. Class A GFCI. -35°C to 66°C, -30°F to 150°F. Zero.

.20 x 4

¾" N.P.T.

Dimensional Drawing

Features

Life (Endurance) Grounded Neutral Protection Power On Indicator Power Off Indicator Wiring Application Switch Interface Latching Mechanism

10,000 cycles (6000 with load and 4000 without load). Open neutral protection Trips upon loss of neutral. Trips if ground and neutral touch at load side. Green light on. Red blinking light plus optional audible alarm. 3 Wire Single Phase (Hot, Neutral and Ground), 4 Wire Single Phase (Line 1,Line 2, Neutral and Ground). Double Insulated. Electromagnetic.

2.64" (67.1)

5.75" (146.0)

Physical Specifications

Wire Leads Unit Color Label Color on Portable and Hard Wired Units Weight

#10 AWG, 24" long. Gray with black cover. Automatic reset: yellow background with black lettering. Manual reset: black background with yellow lettering. 1.40 lbs.

Related Code Confined Space Construction Sites Commercial Garages Fountains Spas and Hot Tubs Marinas

www.hubbell-wiring.com

24.00" (609.6)

OSHA 29 CFR 1926.404 (b) (1) (ii) OSHA 29 CFR 1926.405 (a) (2) (ii) (G) NEC 590.6 NEC 511.12 NEC 680.5B NEC 680.40 NEC 555.3

Side View Dimensions in Inches (mm) ®

Wiring Device-Kellems

K-17