CONTEMPLATED CHANGE ORDER

138 West 8th Avenue Vancouver, BC, V5Y 1N2 T. 778.330.1139 F. 778.327.6844 OWNER

DATE

December 18, 2015 WORK

McKesson / CBRE CONTRACTOR

Turner Construction ARCHITECT

Thibodeau Architecture + Design

McKesson Tenant Improvement Phase 2 Richmond, BC

CCO NO

002 R1

ARCHITECT'S REFERENCE NO

BC-1163

This Contemplated Change Order forms part of the Contract Documents and is to be read, interpreted and coordinated with all other parts. Work related to this Contemplated Change Order shall not proceed until written authorization is issued. Provide a detailed breakdown of the additional cost or savings including, material costs, labour times and rates, along with all applicable taxes, permits, licensing fees, bonding, and any additional costs as maybe affected by this change.

Description:

In response to RFI #001 - Existing Ductwork Conflict 1. Revise Cubby layout as per ASK-005 R1. The western duct is to be located in Cubby 251. Ensure access to the western duct is maintained in east and south walls with paint grade plywood access panel. Ensure that eastern duct enclosure aligns with edge of workstation desk. 2. Revise accent carpet layout and paint walls of eastern duct P-2 as per ASK-006 R1. 3. Revise gypsum ceiling and pot light locations for Cubbies as per ASK-007 R1. Change fixture south of eastern duct from a 2x4 fixture to a 2x2 fixture as per ASK-007 R1 and ECCN 03. 4. Revise Cubby Elevations as per ASK-008 R1. 5. Add Booth banquette section detail #4 and fabric specification as per ASK-008 R1. 6. Revise lighting and electrical as per attached ECCN 03. 7. Revise all Type S pendant lights in all Zones per attached ECCN 03.

Attachments:

ASK-005, ASK-006, ASK-007, ASK-008 ECCN 03 (2 pages) Requested by: Contractor Reason: Site Conditions End of CCO

10

11 ZONE B

ZONE A

B

4'-0"

5 A-801

1 ASK-008 6'-11"

2'-6"

6'-11"

6'-11"

W2a

W2a

6'-11"

6'-11"

W2a

W2a

W2a

2

2

1

3

250 Cubby

W2a 5'-3"

W2a

10'-11"

1

3

W2a

249 Cubby

2 W2a 3

3

W5a

ASK-008

W2a

200a Open Office

W2a

251 Cubby

W5a

10'-11"

2

12'-10"

8'-10"

W2a

W5a 4'-10"

4'-6"

1

ALIGN

W2a

6'-7"

200b Open Office

9'-6"

ASK-008

W5a W5a

7'-9"

ALIGN

5'-5"

W5a

KEYNOTES: 1

- ASK-005

2 3

seal

Install 4' x 4' plywood backing in wall to support wall mounted equipment. Center along length of wall, horizontal C.L. at 5'-0" A.F.F. Computer monitor Collaborative seating - supplied and installed by furniture consultant

project name

drawing title

Cubby Plan

McKesson T.I. - Phase 2 This drawing is the property of J. Robert Thibodeau Architecture + Design. A written approbal by J.R.T.A.D. is required priot to any use of this drawing. Contractors must verify all dimensions on site and immediately immediately inform the Architect of all errors and missions.

#:

Date:

Description:

Rev:

138 W 8th Avenue Vancouver (British Columbia) V5Y 1N2 t.778.330.1139 f.778.327.6844 www.goTAD.ca

project no.:

Vancouver Winnipeg Montréal

issued date:

date:

11/26/15

BC-1163

checked by:

Checker 11/26/15

scale:

drawn by:

1/4" = 1'-0" Author rev:

1

ASK-005

1 Cubby Plan ASK-005 Scale: 1/4" = 1'-0"

10

11 ZONE B

ZONE A

F-1

F-1

B

F-2

P-1

F-2

CPT-2 P-1

F-1

P-1

P-1

F-1

CPT-3 P-1

F-2

P-1

P-1

F-2

CPT-2 P-1

P-1

CPT-3

P-1

P-1

F-2

P-1

P-1

F-2

CPT-2

P-1

1'-1 3/4" 1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

P-1 P-1

P-1 P-2

251 Cubby

P-2 P-1

P-1

6'-0"

P-1

4'-6"

250 Cubby

P-1

5'-6"

P-1

249 Cubby

P-1

7'-9"

P-1

P-1

F-1

P-1 P-1

P-1

P-1

P-1

200a Open Office

CPT-3 7'-0"

P-1 P-3

9'-0"

P-1 P-2

P-1

P-2 P-1

P-1 P-1 P-2 P-1

P-2 P-1

200b Open Office

Plan - ASK-006

seal

project name

drawing title

Cubby Finish Plan

McKesson T.I. - Phase 2 This drawing is the property of J. Robert Thibodeau Architecture + Design. A written approbal by J.R.T.A.D. is required priot to any use of this drawing. Contractors must verify all dimensions on site and immediately immediately inform the Architect of all errors and missions.

#:

Date:

Description:

Rev:

138 W 8th Avenue Vancouver (British Columbia) V5Y 1N2 t.778.330.1139 f.778.327.6844 www.goTAD.ca

project no.:

Vancouver Winnipeg Montréal

issued date:

date:

11/27/15

BC-1163

checked by:

Checker 11/27/15

scale:

drawn by:

1/4" = 1'-0" Author rev:

1

ASK-006

1 Cubby Finish ASK-006 Scale: 1/4" = 1'-0"

P-1 P-2

10

11 ZONE B

ZONE A

B

EQ

EQ

EQ

7'-9"

6'-11" EQ

EQ

7'-9"

6'-11" EQ

8'-10"

EQ

7'-9"

EQ 7'-9"

4'-10"

EQ

3'-0"

250 Cubby 7'-9"

251 Cubby 7'-9"

5'-0"

7'-9"

43'-7"

4'-10" 5'-0"

200b Open Office

- ASK-007

seal

project name

drawing title

Cubby RCP

McKesson T.I. - Phase 2 This drawing is the property of J. Robert Thibodeau Architecture + Design. A written approbal by J.R.T.A.D. is required priot to any use of this drawing. Contractors must verify all dimensions on site and immediately immediately inform the Architect of all errors and missions.

#:

Date:

Description:

Rev:

138 W 8th Avenue Vancouver (British Columbia) V5Y 1N2 t.778.330.1139 f.778.327.6844 www.goTAD.ca

project no.:

Vancouver Winnipeg Montréal

issued date:

date:

11/27/15

BC-1163

checked by:

Checker 11/27/15

scale:

drawn by:

1/4" = 1'-0" Author rev:

1

ASK-007

1 Cubby RCP ASK-007 Scale: 1/4" = 1'-0"

200a Open Office

9'-4"

2'-6"

249 Cubby

3'-8"

7'-9"

EQ

7'-9"

EQ EQ

5 A-801

EQ

6'-11"

3'-0"

EQ

6'-11"

1'-2"

6'-11"

3'-0"

5'-3"

8"

2'-2"

2'-4"

1'-2"

9"

2'-3"

2'-2"

1'-2"

8"

2'-6"

3 A-800

2'-8"

1'-4"

2"

2'-5"

2'-7"

2'-6"

2'-4"

1'-5"

2'-4"

2'-10"

10"

6"

#:

1'-1"

1'-4"

1'-5"

11" 6"

F-1

8"

P-1

4 ASK-008

3"

4"

8"

1'-7"

6"

7"

2'-3"

1'-10"

11"

1'-5"

3'-1"

1'-4"

1'-9"

2'-1"

1'-10"

2'-3"

11"

2'-0"

1'-6"

1'-9"

2'-8"

5 A-801 8" 8"

P-1

Description: Rev:

This drawing is the property of J. Robert Thibodeau Architecture + Design. A written approbal by J.R.T.A.D. is required priot to any use of this drawing.

F-1 P-1

P-1

F-1

P-1

3'-5"

3'-11"

PL-1

PL-1

F-2

PL-1

F-2 4'-5"

F-1

3'-9"

P-1

4'-1"

F-1

F-2 4'-1"

P-1 4'-6"

Date:

revisions

PL-1

PL-1

Contractors must verify all dimensions on site and immediately immediately inform the Architect of all errors and missions.

4 ASK-008

client

PL-1 PL-1 project manager

2 A-800

B-1

B-1

B-1

B-1

B-1

B-1

mechanical/electrical engineer

1 Cubbies - North ASK-008 Scale: 1/2" = 1'-0"

2 Cubbies - East ASK-008 Scale: 1/2" = 1'-0"

- ASK-008

- ASK-008

Suite 180 - 200 Granville Street Vancouver BC Canada V6C 1S4 T 604.687.1800 www.integralgroup.com

3"

1'-6"

mechanical/electrical engineer

10'-6" EQ

EQ

12'-5" EQ

2'-4"

5'-0"

3/4" PLYWOOD BACKING 5'-0" 1'-6"

EQ

10'-6"

HIGH DENSITY FOAM BACKING FABRIC AS SCHEDULED WITH INTEGRATED NON-POROUS MOISTURE BARRIER

P-2

P-2 2"

P-3

SEAT WITH ELASTIC WEBBING COVERED WITH MINIMUM OF 2" MEDIUM OR FIRM DENSITY FOAM

6"

3'-6"

3 A-800

P-2

McKesson T.I. - Phase 2 Unit 130 - 10711 Cambie Road, Richmond BC

5 A-801

1'-6"

B-1

3 Cubbies - South ASK-008 Scale: 1/2" = 1'-0"

B-1

B-1

3/4" PLYWOOD LID, HPDL FINISH PL-1 3/4" PLYWOOD FRONT, HPDL FINISH PL-1 3/4" PLYWOOD BOTTOM, HPDL FINISH PL-1

3"

4"

3'-0"

2 A-800

2'-9"

3'-0"

2'-9"

3'-0"

2'-9"

1"

3/4" PLYWOOD BASE, HPDL FINISH PL-1

B-1

- ASK-008

4 Banquette Bench ASK-008 Scale: 1 1/2" = 1'-0"

architect

FABRIC TYPE LEGEND F-1

F-2

FABRIC - MOMENTUM - ODYSSEY - COLOUR: INK. FINISH: SOIL AND STAIN RESISTANT. DURABILITY: 200,000 DOUBLE RUBS. FLAME RESISTANCE: CA BULLETIN 117 2013; UFAC CLASS 1; NFPA 260 CLASS 1; ASTM E84. MAINTENANCE: WS - WATER-BASED CLEANING AGENTS OR FOAM. LIGHTFASTNESS: GRADE 4 AT 40 HOURS.

138 W 8th Avenue Vancouver (British Columbia) V5Y 1N2 t.778.330.1139 f.778.327.6844 www.goTAD.ca Vancouver Winnipeg Montréal

seal

FABRIC - MOMENTUM - ODYSSEY - COLOUR: LIVELY. FINISH: SOIL AND STAIN RESISTANT. DURABILITY: 200,000 DOUBLE RUBS. FLAME RESISTANCE: CA BULLETIN 117 2013; UFAC CLASS 1; NFPA 260 CLASS 1; ASTM E84. MAINTENANCE: WS - WATER-BASED CLEANING AGENTS OR FOAM. LIGHTFASTNESS: GRADE 4 AT 40 HOURS.

project number

BC-1163

drawing title

Cubby Elevations

date scale

sheet number

11/27/15

As indicated drawn by Author checked by Checker

ASK-008 R: 1

MMM Group Limited 1045 Howe Street, Suite 700 Vancouver, BC V6Z 2A9 t: 604.685.9381 | f: 604.683.8655 www.mmm.ca

NOTICE OF CHANGE # 03 Date: To:

Tel #: File #:

Julia Baker

From:

Cameron Ballard

For Your

Information

(YY.MM.DD)

Fax #:

Thibodeau Architecture

Attn:

15.12.18

ECCN#03

E-Mail: Transmitted by: Review

Comments

E-Mail

As Requested

Page 1 of 2 As Discussed

Distribution

This is not an authorization for extra work. Contractor is to prepare an estimate of the change to the amount of the contract and submit it to the Engineer as soon as possible. Unless authorized by Change Order, if work proceeds, it is at Contractor’s own risk.

RE:

McKesson Phase 2 TI

Reason for change: Architectural changes to Cubby Rooms. Overview of Changes: - Delete one (1) booth at the West side of Cubby 249. - Add one (1) booth at North wall of Cubby Rooms. New booth to be typical power and lighting layout as adjacent booths. - Change one 2’x4’ fixture to 2’x2’ in Open Office area to accommodate mechanical ducts. - Revise ceiling at East side of Cubby 254 to extend drywall further east. Update pot light layout to suit revised ceiling. Description of Changes: Zone A: Lighting: -

Change one light type A to type D. Light to be changed is middle fixture the Westmost row of the Open Office Area closest to the Cubby Room 251. Revise locations of four (4) type E1 pot lights East of Cubby Room 251 to be spaced 4’10” East to West and 3’0” North to South in a rectangular layout centered on the revised drywall ceiling.

Zone B: Lighting: -

Revise location of one (1) type E1 pot light west of Cubby 249 to the new booth along North wall of the Cubby Rooms.

n:\2015\5015785-110 mckesson ti phase 2\electrical\engineering\construction\change orders\eccn 03 - cubby room changes\5015785 eccn 03 (dec 18, 2015).doc

MMM Group Limited

Page 2

Power: -

Delete rough-in for data/tel outlet on West wall of Cubby 249 Add one (1) duplex receptacle in the new booth along North wall of the Cubby Rooms. Revise location of one (1) rough-in data/tel outlet on the West wall of Cubby 249 to the new booth along North wall of the Cubby Rooms.

All Zones: Type S light to be Tech Lighting Soraa Piper Pendant 700 MP Series with 3000k, 8W LED, 48 degree distribution, 0-10V dimming, stem mounted Satin Nickel pedant. Provide all required transformers and wiring for connection to line voltage.

CC:

Per:

Cameron Ballard. EIT MMM Group Limited

n:\2015\5015785-110 mckesson ti phase 2\electrical\engineering\construction\change orders\eccn 03 - cubby room changes\5015785 eccn 03 (dec 18, 2015).doc