NFLnonmetallic fluorescent fixture

Report 40 Downloads 122 Views
NFL

dust

dirt

vapor

smoke

fumes

moisture

nonmetallic fluorescent fixture

IDEAL FOR FOOD PROCESSING PLANTS

UL Listed d cUL Liste s o d u for Hazar s Location

NEMA 4X

55°C AMBIENT Class I, Division 2, Groups A, B, C & D Class I, Zone 2, Groups IIC

NFL

nonmetallic fluorescent fixture

temperature performance data Ambient temperature range suitability: • Two lamp, 32 W T8, 4-ft fixture -18°C to 55°C • All others 0°C to 55°C Supply wire 75°C min. standard materials

application • Where dust, dirt, combustible vapors, smoke, fumes, moisture, corrosive and wet conditions are present, such as in waste water and sewage treatment plants. • Where lamps may be broken due to physical abuse or movable equipment, such as in manufacturing areas or warehouses. • Where cleanliness and sanitation are prime factors such as in dairies, canneries, food processing plants, bottling plants and laboratories. • In dock areas for protection against salt spray. • In areas where low mounting height and the even light distribution associated with a linear type light source are required. certifications and compliances • • • •

UL Listed 844 UL and cUL Wet locations NEMA 4X

130˚

120˚

110˚

100˚

90˚

80˚

100 200 70˚

300 400

CANDELAS

500

60˚

600 700 800

50˚

900 1000 1100

40˚



10˚

• Fiberglass Housing – white • Lens – clear options

suffix

• Fused . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • Factory assembled with lamps installed . . • Battery Backup Emergency Ballast† (NFL 2140 and NFL 4232 only) . . . . . . . . . • Increased Impact-Resistant Acrylic Lens . . • Polycarbonate Lens . . . . . . . . . . . . . . . . . . • Stainless Steel Latches . . . . . . . . . . . . . . . • Tamperproof Latches . . . . . . . . . . . . . . . . .

S658 FA



S799* DR1295046* DR1295306* S863* S861*

20˚

30˚

CelconTM is a trade name of Hoechst Celanese

For non-hazardous locations

Photometric data, developed using two (2) F32T8/35K (2850 lumens each lamp) represents the performance of all NFL series fixtures. • Coefficient of Utlization – These values are for all NFL series fixtures (Do not use multipliers). • Candlepower Distribution Curve (in candelas) and Zonal Lumens – These values are for all NFL series fixtures, adjusted by conversion factors (multipliers) below.

Fixture: All NFL Fixtures To determine number and placement of fixtures, see Lighting Selector Guide in Section L. 140˚

standard finishes

* Consult Cooper Crouse-Hinds for availability of these options

Photometric Data:

180˚ 170˚ 160˚ 150˚

• Housing – nonmetallic, one piece compression molded fiberglass-reinforced polyester • Latches/ External Hardware – Celcon™ acetal plastic • Crepe Pattern Lens – acrylic plastic • Gasket – seamless thermoset polyurethane • Mounting Bracket – stainless steel

CANDELAS Angle Along Across 0° 1049 1049 10° 1034 1056 20° 978 1071 30° 886 1075 40° 762 1027 50° 606 939 60° 416 838 70° 228 723 80° 92 549 90° 17 363 100° 19 243 110° 10 131 120° 5 46 130° 4 20 140° 4 9 150° 4 3 160° 4 0 170° 0 0 180° 0 0 ZONAL LUMENS Zone Lumens 0-30 862 0-40 1462 0-60 2778 0-90 4130 0-180 4499

Fixture Series

Quantity

Conversion Factor (multipliers)

Lamp Watts

Type (Lumens ea.)

32

F32T8/35K (2850) F40T12/RS (2650) T5 Long twin tube FT40W/2GII/RS (3150)

NFL4232

2

NFL4240

2

34

NFL2140

1

40

1.0 0.93 0.55

Example: • Candlepower at 20° across for NFL4232 using 2-F32T8/35K lamps (5700 lumen total) is 1071 candelas. • Candlepower at 20° across for NFL2140 using 1 T5 compact lamp (3100 lumen total) is 1071 x .55 = 589 candelas. Coefficient of Utilization: For all NFL Series Light Fixtures Effective Floor Cavity Reflectance 20% % REFLECTANCE Eff. Ceiling Wall 70 80 50 30 10 70 70 50 30 10 50 50 30 10 50 30 30 10 50 10 30 10 0 0

1 .83 .78 .74 .71 .80 .76 .72 .69 .71 .68 .66 .67 .65 .62 .63 .61 .59 .57

2 .75 .67 .61 .56 .72 .65 .60 .55 .61 .57 .53 .58 .54 .51 .54 .51 .48 .46

ROOM CAVITY RATIO 3 4 5 6 .68 .62 .56 .51 .59 .52 .45 .40 .52 .44 .38 .33 .46 .39 .32 .28 .65 .59 .54 .49 .57 .50 .44 .39 .51 .43 .37 .32 .46 .38 .32 .27 .54 .47 .42 .37 .48 .42 .35 .31 .44 .37 .31 .26 .51 .45 .39 .35 .46 .40 .34 .30 .42 .36 .30 .26 .48 .42 .37 .33 .44 .38 .33 .29 .41 .35 .29 .25 .39 .33 .27 .23

7 .47 .36 .29 .24 .46 .35 .28 .23 .33 .27 .23 .32 .26 .22 .30 .25 .22 .20

8 .44 .32 .25 .20 .42 .31 .25 .20 .30 .24 .20 .28 .23 .19 .27 .22 .18 .17

9 .40 .29 .22 .17 .39 .28 .22 .17 .27 .21 .17 .25 .20 .16 .24 .19 .16 .14

10 .37 .26 .20 .15 .36 .26 .19 .15 .24 .19 .15 .23 .18 .14 .22 .17 .14 .12

NFL

key features and benefits

UL, cUL Listed for Class I, Division 2, Groups A, B, C, D areas with ambient suitability of 40°C (104°F) and 55°C (131°F) – Exceeds the 25˚C (77˚F) ambient suitability of ordinary location lighting fixtures. Molded-in-place mounting studs – Wet location and dusttight integrity is not compromised. Aging or deteriorated bracket gaskets are eliminated. Energy efficient, cold-weather, electronic ballast – Highly cost-effective. Ideal for cold weather start up (4' F32 T8). Full metal fixture interior – Improves photometrics while concealing ballast and wiring. Pendant mount drill mark – Field application and installation flexibility.

1

NEMA 4X, corrosion-resistant enclosure with continuous form-in-place gasket – Ideal for outdoor locations. Insures dusttight, moisture-tight and wet location integrity.

2

Stainless steel combination ceiling and chain mounting bracket – Universal mounting bracket offers superior corrosion resistance.

3

Two 1/2" Myers® hubs for end or feed-through wiring – Fast and simple installation and wiring.

3

2 1

NFL

nonmetallic fluorescent fixture

NFL2140

NFL4232

NFL4240

ordering information Fixture Cat # NFL2140/120 NFL2140/277 NFL2140/347 NFL4232/120 NFL4232/277 NFL4232/347 NFL4232/230 NFL4240/120 NFL4240/277 NFL4240/347

Lamp

Description

(1) 2-ft lamp

40 W, T5, single-ended, 4-pin long twin tube (FT40W/2GII/RS)

(2) 4-ft lamps

32 W, T8, rapid start

(2) 4-ft lamps

34 W, T12, “F40 Style,” rapid start

Voltage/Hz 120 V, 60 Hz 277 V, 60 Hz 347 V, 60 Hz 120 V, 60 Hz 277 V, 60 Hz 347 V, 60 Hz 220-240 V, 50-60 Hz 120 V, 60 Hz 277 V, 60 Hz 347 V, 60 Hz

Fixture Weight (lb) 9.1

14.3

14.3

temperature performance data Basic Cat #

Watts

Ambient Temp °C

Lamp Type

Supply Wire Temp °C

Class I, Div. 2 Temp. Rating

Class II Temp. Rating

Simultaneous Presence Class 1, Div. 2

NFL4232

32

40

T8

60

T6





NFL4232

32

55

T8

75

T5





NFL4240

34

40

T12

60

T6





NFL4240

34

55

T12

75

T5





NFL2140

40

40

T12

60

T6





NFL2140

40

55

T12

75

T5





dimensions FOUR FOOT 24 7/8"

TYPICAL FOR FOUR FOOT AND TWO FOOT

TWO FOOT 49 3/4"

26" 14 3/4" 7 3/8"

25 1/8"

4 1/8" 8 1/4"

8 1/4" 4 1/8" 9 1/2" 19 3/8" 38 3/4"

13"

1 1/2" 7 1/8"

13 1/4"

Ø1/4"

For more information:

In the U.S.:

In Canada:

Contact an authorized Cooper CrouseHinds Distributor, Sales Office or Customer Service Department:

Cooper Crouse-Hinds P.O. Box 4999 Syracuse, NY 13221 (315) 477-5531 FAX: (315) 477-5179 [email protected]

Cooper Crouse-Hinds Canada (905) 507-4187 FAX: (905) 568-7048

Distributed by:

3 1/4" 5 1/4"

For office locations outside of North America or for additional product information, visit our website at: www.crouse-hinds.com

Mexico • Latin America/Caribbean • Germany • Australia • Asia • Dubai • India

Solutions.Worldwide.

TM

4696-0705

Crouse-Hinds is a registered trademark of Cooper Industries, Inc. © 2005 Cooper Industries, Inc.

Printed in U.S.A.