SCP Part Number: LUTRON-QS-LSZH - AWS

Report 0 Downloads 19 Views
www.scpcat5e.com

SCP Part Number: LUTRON-QS-LSZH REV.A

Cross Section

Performance Electrical Characteristics:[@68°F.(20℃.)]

Description QUANTUM SYSTEM CABLE, LUTRON SERIES Lutron Equivalent Part Number: QSH-CBL-M-500

Marking STRUCTURED CABLE PRODUCTS EXXXXXX (UL) OR c(UL) CM CL3 75C MM/YY --- P/N: LUTRON-QS-LSZH --- QUANTUM SYSTEM --2C/16 AWG + 2C/22 AWG SHIELDED PLUS DRAIN - LOW SMOKE ZERO HALOGEN JKT CE EU RoHS EC ZONE/DEVICE A B C D E 0 1 2 3 4 5 6 7 8 9 XXXM

Construction Component 1: 16AWG X2 core Conductor 16AWG stranded bare copper Size 26 X 30AWG Dia.(in/mm) 0.057/1.46 Insulate FR-PVC Insulation Dia.(in/mm) 0.083/2.10 Color Black,Red Component 2: 1Pair 22AWG Conductor 22AWG stranded bare copper Size 7 X 30AWG Dia.(in/mm) 0.030/0.76 Insulate Foam PE Insulation Dia.(in/mm) 0.075/1.90 Color 1 Natural, 2 outer skin is purple Drain wire 7X32AWG stranded Tinned copper Dia.(in/mm) 0.023/0.60 Cabling Two 22AWG and drain wire Shield AL foil Wrapping Overlap(%) 25 Final assembly Cabling Two 16AWG and 1Pair 22AWG Ripcord Cotton Out jacket White LSZH Nom. Thickness(in/mm) 0.031/0.80 0.252/6.40 Cable Dia.(in/mm) Packing Length(ft/m) Gross Weight(lbs/kg)

Component 1: 18AWG Conductor DCR@ 20oC (ohms/kft)

4.46

Component 2: 1P 22AWG Conductor DCR@ 20oC (ohms/km)

16.2

Drain wire Conductor DCR@ 20oC (ohms/km)

25.4

Mechanical Characteristics: Test Object: Test Material Before Tensile strength Aging Elongation Aging Condition After Tensile strength Aging Elongation

(psi) (%) (℃_hrs) (%) (%)

Cold Bend Jacket Longitudinal Shrinkage Operating Temperature Range

(-20±2oC/4hrs) (%) (℃)

Jacket >=1500 150 100_168 >=85%unaged >=50%unaged No crack >=5 -20~75

Standards *Lutron®, Homeworks®, Sivoia®, Grafik Eye®, and Quantum Systems® are registered trademarks of Lutron Electronics Co., Inc. UL, CE, RoHS UL Listed: Type CL3 or CM c(UL)us RoHS Compliant

Wooden spool 500/152.5 22.05/10.0

Rev Date: 05/2013