STANDARD PANEL FEATURES NEMA 4X, Fiberglass Enclosure Pump Circuit Breaker(s) Control Circuit Breaker Motor Contactor(s) H-O-A Switch(es) (Hand-Off-Automatic switch) Through-Door Pump Run Light(s) External Motor Components (capacitors) High Level Alarm Circuit with Dry Contacts Flashing high-level red alarm light Alarm Horn, 101 db @ 10 feet Alternation on duplex panels All controls are UL and CUL Listed
SIMPLEX AND DUPLEX SINGLE PHASE PANELS FOR SINGLE PHASE PUMPS REQUIRING EXTERNAL MOTOR COMPONENTS
CentriPro Wastewater ADDITIONAL PANEL OPTIONS AVAILABLE Add option characters as order number suffixes in alphabetic order. C = Condensation heater, 115 volt (70 watt) prevents condensation inside the panel
L = Duplex cycle counters for (2) pumps, record On/ Off cycles for each pump
D = Single phase lightning arrestor
M = Simplex high temperature sensor circuit with pump shutdown
F = Simplex (1) elapsed time meter, shows run time in hours G = Duplex (2) elapsed time meters, show run time in hours K = Simplex cycle counter for (1) pump, records On/ Off cycles
Part number
Style
S1GD2
Simplex
D1GD2
Duplex
S1GD2H
Simplex
D1GD2J
Duplex
S1FGC2
Simplex
D1FGC2
Duplex
S1FGC3
Simplex
HP Rating
N = Duplex high temperature sensor circuits with pump shutdown S = Intrinsic safe T = Intrinsic safe
Seal Fail Style
Voltage
Pump Match
Not included
230/208
GWT 1GD less seal fail
Standard
230/208
GWT 1GD and B&G 12GDS
2
3
5.4 D1FGC3
Duplex
S1FGC5
Simplex
D1FGC5
Duplex
9.4
PAGE 2
GWT 1GA and B&G 15GDS
Minicas
230
GWT 1GA/2GA and B&G 15GDS/20GDS
GWT 2GA and B&G 20GDS
CentriPro Wastewater SAMPLE DUPLEX
START RELAY START START
RUN RUN R 25 A
S1
DL
1
PUMP 3 HP
W T B
START RELAY START START
RUN RUN R 25 A
S2
DL
2
L1
W T
SINGLE PHASE L2
B
230 VAC 60 HZ
PUMP 3 HP
N
RUN HAND
MINI CAS 1
OFF
10 A
1
AUTO
DL S1
3
RUN HAND
MINI CAS 2
OFF
1
AUTO
3
DL S2
TEST
R1
TEST
R2
MUTE
SILENCE
RESET
C
RESET OFF
LEAD
ALARM
N
L1 H L1 N
1
2
3
FOR SEPARATE 120 VAC CONTROL POWER SUPPLY, REMOVE JUMPER (J1) FROM TERMINALS (H) AND (L1). CONNECT 15 AMP MAX. PROTECTED 120 VAC SUPPLY TO TERMINALS (L1) AND (N). WITH THE NEUTRAL OF THE SUPPLY TO (N).
4
5
6
7
8
FLASHING
FLASH
SONALERT
HORN
9 10 11
DRY CONTACTS
J1
L1
LAG
J2 ALARM FLOAT FACTORY WIRED FOR (3) FLOAT OPERATION. FOR (4) FLOAT OPERATION, LAG FLOAT REMOVE JUMPER (J2) FROM TERMINALS (OPTIONAL) (6) AND (8), INSTALL LAG FLOAT ON LEAD FLOAT TERMINALS (5) AND (6). OFF FLOAT
N PAGE 3
SAMPLE DUPLEX (continued)
L1
N
Duplex Operation High Level Alarm: This float activates the alarm light and audible alarm when lifted. The audible alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The alarm light will remain on until the float is lowered. Lag Pump On: This float turns on the lag pump when lifted. The pump will continue to run until the Pumps Off float is lowered.
MINI CAS 1 11
PUMP NO. 1 SEAL FAILURE
9
MINI CAS 2 11
PUMP NO. 2 SEAL FAILURE
9
Lead Pump On: This float turns on the lead pump when lifted. The pump will continue to run until the Pumps Off float is lowered.
120 VAC
Pumps Off: This float turns off the pumps when lowered. Minicas: Minicas monitors the pump seals for water leakage and monitors the motor for over heating. If leakage is detected the seal failure light will be activated. In the event of motor over heating, the pump will be disabled. Once the over heat condition is corrected, operation will resume automatically.