simplex and duplex single phase panels - Kleen-Rite

Report 2 Downloads 122 Views
TECHNICAL BROCHURE BCP5 R13

STANDARD PANEL FEATURES NEMA 4X, Fiberglass Enclosure Pump Circuit Breaker(s) Control Circuit Breaker Motor Contactor(s) H-O-A Switch(es) (Hand-Off-Automatic switch) Through-Door Pump Run Light(s) External Motor Components (capacitors) High Level Alarm Circuit with Dry Contacts Flashing high-level red alarm light Alarm Horn, 101 db @ 10 feet Alternation on duplex panels All controls are UL and CUL Listed

SIMPLEX AND DUPLEX SINGLE PHASE PANELS FOR SINGLE PHASE PUMPS REQUIRING EXTERNAL MOTOR COMPONENTS

CentriPro Wastewater ADDITIONAL PANEL OPTIONS AVAILABLE Add option characters as order number suffixes in alphabetic order. C = Condensation heater, 115 volt (70 watt) prevents condensation inside the panel

L = Duplex cycle counters for (2) pumps, record On/ Off cycles for each pump

D = Single phase lightning arrestor

M = Simplex high temperature sensor circuit with pump shutdown

F = Simplex (1) elapsed time meter, shows run time in hours G = Duplex (2) elapsed time meters, show run time in hours K = Simplex cycle counter for (1) pump, records On/ Off cycles

Part number

Style

S1GD2

Simplex

D1GD2

Duplex

S1GD2H

Simplex

D1GD2J

Duplex

S1FGC2

Simplex

D1FGC2

Duplex

S1FGC3

Simplex

HP Rating

N = Duplex high temperature sensor circuits with pump shutdown S = Intrinsic safe T = Intrinsic safe

Seal Fail Style

Voltage

Pump Match

Not included

230/208

GWT 1GD less seal fail

Standard

230/208

GWT 1GD and B&G 12GDS

2

3

5.4 D1FGC3

Duplex

S1FGC5

Simplex

D1FGC5

Duplex

9.4

PAGE 2

GWT 1GA and B&G 15GDS

Minicas

230

GWT 1GA/2GA and B&G 15GDS/20GDS

GWT 2GA and B&G 20GDS

CentriPro Wastewater SAMPLE DUPLEX

START RELAY START START

RUN RUN R 25 A

S1

DL

1

PUMP 3 HP

W T B

START RELAY START START

RUN RUN R 25 A

S2

DL

2

L1

W T

SINGLE PHASE L2

B

230 VAC 60 HZ

PUMP 3 HP

N

RUN HAND

MINI CAS 1

OFF

10 A

1

AUTO

DL S1

3

RUN HAND

MINI CAS 2

OFF

1

AUTO

3

DL S2

TEST

R1

TEST

R2

MUTE

SILENCE

RESET

C

RESET OFF

LEAD

ALARM

N

L1 H L1 N

1

2

3

FOR SEPARATE 120 VAC CONTROL POWER SUPPLY, REMOVE JUMPER (J1) FROM TERMINALS (H) AND (L1). CONNECT 15 AMP MAX. PROTECTED 120 VAC SUPPLY TO TERMINALS (L1) AND (N). WITH THE NEUTRAL OF THE SUPPLY TO (N).

4

5

6

7

8

FLASHING

FLASH

SONALERT

HORN

9 10 11

DRY CONTACTS

J1

L1

LAG

J2 ALARM FLOAT FACTORY WIRED FOR (3) FLOAT OPERATION. FOR (4) FLOAT OPERATION, LAG FLOAT REMOVE JUMPER (J2) FROM TERMINALS (OPTIONAL) (6) AND (8), INSTALL LAG FLOAT ON LEAD FLOAT TERMINALS (5) AND (6). OFF FLOAT

N PAGE 3

SAMPLE DUPLEX (continued)

L1

N

Duplex Operation High Level Alarm: This float activates the alarm light and audible alarm when lifted. The audible alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The alarm light will remain on until the float is lowered. Lag Pump On: This float turns on the lag pump when lifted. The pump will continue to run until the Pumps Off float is lowered.

MINI CAS 1 11

PUMP NO. 1 SEAL FAILURE

9

MINI CAS 2 11

PUMP NO. 2 SEAL FAILURE

9

Lead Pump On: This float turns on the lead pump when lifted. The pump will continue to run until the Pumps Off float is lowered.

120 VAC

Pumps Off: This float turns off the pumps when lowered. Minicas: Minicas monitors the pump seals for water leakage and monitors the motor for over heating. If leakage is detected the seal failure light will be activated. In the event of motor over heating, the pump will be disabled. Once the over heat condition is corrected, operation will resume automatically.

24 VAC

MINI CAS 1 2

RESET

10

6 7+ TAS

5– LK

12

13

PUMP NO. 1 SEAL FAIL/HIGH TEMP

MINI CAS 2 2

RESET

10

6 7+ TAS 14

5– LK 15

PUMP NO. 2 SEAL FAIL/HIGH TEMP

Xylem Inc. 2881 East Bayard Street Ext., Suite A Seneca Falls, NY 13148 Phone: (866) 325-4210 Fax: (888) 322-5877 www.centripro.com CentriPro is a trademark of Xylem Inc. or one of its subsidiaries. © 2015 Xylem Inc. BCP5 R13 August 2015