Spec Sheet - Villa Lighting

Report 17 Downloads 103 Views
lun

Enclosed and Gasketed Fiberglass Industrial / 1, 2, or 3-Lamp T5, T8, or T12 Project Information Project Name

Type

Catalog No.

Date

Ballasts

Features • Non-metallic enclosure resists the destructive effects of most corrosive agents • Smooth surfaces of housing and diffuser lens make cleaning easy. Housing and lens have no seams or crevices to trap dirt and dust • Fixture housing has an inverted “U” slot which allows the diffuser to nest tightly, shedding water • Neoprene gasketing is sandwiched between housing and diffuser forming an effective seal • Diffuser lens is secured to the housing with captive, nonmetallic, snap-action cam latches • Full steel liner for ballast heat dissipation and maximum reflectivity • Ballast cover plates snap-lock without tools; eliminates loose hardware or fasteners • UL listed 1958, cUL or CSA. Wet Location standard

Liner

Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated A, unless otherwise specified. CEE NEMA Premium compliant.

Heavy gauge die-formed steel. Finish

Housing - Cream tone fiberglass. Liner - Pre-painted high gloss baked white enamel, minimum 86% reflectance.

Electrical

Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CECcompliant ballast disconnect is standard.

Certification

All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. Wet location labeling is standard. Emergency-equipped fixtures labeled UL 924.

Housing

One-piece, high-impact, molded polyester fiberglass with a cast waterproof hub (1⁄2" thread). Factory installed neoprene gasketing. Diffuser

One-piece, impact-resistant 15% DR, molded acrylic. Smooth outside, prismatic pattern inside. Retained by molded ABS thermoplastic latches.

Ordering Information LUN



Model



No. of Lamps in Cross section

LUN Enclosed and Gasketed Fiberglass Industrial

1 One 2 Two 3 Three

Size 2 2' 4 4' 8 8'

Example LUN4-232-EU

Lamp Type 17 28 32 96 96T8

2', T8, 17 Watt 4', T5: 28 Watt 4', T8: 32, 30, 28 or 25 Watt 8', T12: 75 or 60 Watt 8', T8: 59 Watt

– Ballast

E EP 3E 4E 3EP 4EP

Electronic, T8, Instant Start (Std.) Electronic, Programmed Start 3-lamp Electronic, Instant Start (T8) 4-lamp Electronic, Instant Start (T8) 3-lamp Electronic, Programmed Start 4-lamp Electronic, Programmed Start

Options

Voltage U 120V-277V 347 347V

GLR PP DR TP SSL SSLTP EL

Fast Blow Fuse Prismatic Polycarbonate Lens 50% DR Acrylic Lens Tamper Resistant Latches Stainless Steel Latches Tamper Resistant Stainless Steel Latches Emergency Battery Pack (Not Available with Wet Location) NYC NYC Compliant NYCU NYC Compliant, Union Label

Accessories (Order Separately) HUBK LUNHK PEBU PEBA

Page 1/3 Rev. 07/25/12

Stem Hanging Hubs Stainless Steel Hanging Kit For 1/2" Hubs, Chain Not Included End Bracket Universal Surface Mount Kit Adjustable Surface Mount Bracket Kit

Extreme Environment / lun

© 2012 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Tech Support 864.678.1668 / Website www.columbialighting.com

lun

Enclosed and Gasketed Fiberglass Industrial / 1, 2, or 3-Lamp T5, T8, or T12

Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet

LUN4-232 LUN Industrial 8" × 50" 2-Lamp with Clear Stippled Plastic Wrap Enclosure B232I120RH-A 0.88 F32T8 3100

0.0 45 11575 55 10639 65 9171 75 8045 85 8870

45.0

90.0

14869 15887 18635 25490 41277

17027 19086 24245 30149 54642 RCR

Luminaire

Test 3067 Test Date 11/18/09

AVG. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) Avg. Luminence Angle

Photometric Data Luminaire Data

Zonal Lumen Summary

56 N/A 0º = 1.30  90º = 1.60 Length = 4.11 Width = 0.58 Height = 0.00

Zone

Lumens

Lamp

Fixt.

0-30 0-40 0-60 0-90 90-180 0-180

976 1665 3209 4857 637 5494

15.7 26.9 51.8 78.3 10.3 88.6

17.8 30.3 58.4 88.4 11.6 100.0

RC RW 1 2 3 4 5 6 7 8 9 10

70 91 82 74 67 62 57 52 49 45 42

80 50 30 86 82 74 67 64 55 56 47 49 41 44 36 40 31 36 28 33 25 30 23

10 77 61 49 41 34 30 26 23 20 18

70 50 30 83 79 71 65 61 54 54 46 48 40 43 35 38 31 35 28 32 25 29 23

70 88 79 71 64 59 54 50 47 43 41

10 75 59 48 40 34 29 25 22 20 18

50 77 66 57 50 45 40 36 33 30 28

Indoor Candela Plot

50 30 74 61 51 43 38 33 29 26 24 22

10 71 56 46 38 32 28 24 22 19 17

90˚

0 0 60 48 39 32 27 24 21 18 16 15

75˚ 450 60˚

900 45˚

1350 0˚ LEGEND: 0-deg: 45-deg: 90-deg:

RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance

0.0 22.5 45.0 67.5 90.0

Total Luminaire Efficiency

88.6%

Luminaire Efficacy Rating (LER) IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens

84 Non-Compliant $4.21 based on 3000 hrs. and $0.08 per KWH

111 N/A

0 30 40 45 50 55 60 65 70 75 80 85

4675 4538 4387 4256 4076 3828 3542 3246 2965 2765 2669 2843

4675 4813 4854 4876 4886 4879 4859 4853 4950 5407 6513 8712

4675 5261 5651 5836 5992 6123 6318 6850 8096 9528 10991 15372

4675 5618 6178 6437 6674 6959 7543 8718 10061 11195 13092 19241

4675 5722 6328 6605 6874 7231 7960 9239 10490 11585 13713 20452

Zonal Lumen Summary

0º = 1.26  90º = 1.59 Length = 8.09 Width = 0.58 Height = 0.00

Zone

Lumens

Lamp

Fixt.

0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180

1696 2895 5557 8335 407 449 482 487 8821

14.6 25.0 47.9 71.9 3.5 3.9 4.2 4.2 76.0

19.2 32.8 63.0 94.5 4.6 5.1 5.5 5.5 100.0

Test 11253 Test Date 1/8/03

Coefficients of Utilization (%)

RCR

Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet

LUN8-232 LUN Industrial 8" × 98" 2-Lamp Tandem with Clear Stippled Plastic Wrap Enclosure B432I120RH 0.88 F32T8 2900

Average Luminance Angle

Luminaire

30˚

Energy Data

AVG. Luminance (Candela/Sq. M.) Luminaire Data

15˚

RC RW 1 2 3 4 5 6 7 8 9 10

70 79 71 64 58 54 49 46 42 39 37

80 50 30 75 71 64 58 55 48 48 41 43 35 38 31 35 27 31 25 29 22 26 20

10 67 53 43 35 30 26 22 20 18 16

70 77 69 62 56 52 47 44 41 38 36

70 50 30 73 69 62 56 54 47 47 40 42 35 37 30 34 27 31 24 28 22 26 20

10 66 52 42 35 29 25 22 20 17 16

50 69 59 51 45 40 35 32 29 27 25

50 30 66 54 45 39 33 29 26 23 21 19

10 63 50 41 34 29 25 22 19 17 15

Indoor Candela Plot

0 0 55 44 36 30 25 22 19 17 15 13

90

75 1100 60

2200 0

15

45

30 Horiz 0-180

RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance

0.0

45.0

90.0

Energy Data Total Luminaire Efficiency

76.0%

Luminaire Efficacy Rating (LER) IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens

70 Non-Compliant $3.43 based on 3000 hrs. and $0.08 per KWH

Dimensional Data D B 11/16" K.O.

7/8" K.O. E

C A

Catalog Number

A

B

C

D

E

LUN2 LUN4 LUN8

61/8" 59/16" 59/16"

65/8" 79/16" 79/16"

3" 3" 3"

171/2" 411/2" 891/2"

2513/16" 4913/16" 9713/16"

NOTE: Fixtures are designed for ceiling mounting only. All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.

Page 2/3 Rev. 07/25/12

Extreme Environment / lun

© 2012 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Tech Support 864.678.1668 / Website www.columbialighting.com

lun

Surface Mounting Details For LUN, FNPV, FNPS, LU

PEBU Accessory

0.31" × 1.75" SLOT

D 0.312" E 4.50"

3.12"

1.00"

PEBA Accessory G

0.31" × 1.69" SLOT 0.22"

3.12"

90° Adjustments

F

D

E

F

G

2'

25.75" (654 mm)

0" (0 mm)

25.75" (654 mm)

2.38" (60 mm)

4'

49.75" (1264 mm)

0.38 (10 mm)

49.75" (1264 mm)

2.75" (70 mm)

8'

97.75" (2483 mm)

0.38" (10 mm)

97.75" (2483 mm)

2.75 (70 mm)

NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.

Page 3/3 Rev. 07/25/12

Extreme Environment / lun

© 2012 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Tech Support 864.678.1668 / Website www.columbialighting.com