PRODUCT DIMENSIONS 1.62 in. (41mm)

3.25 in. (82mm)

2.25 in. (57mm)

STANDARD SINGLE OUTLET BOX NOTE: TO MOUNT STOPPER STATION SS-2000F ON A STANDARD OUTLET BOX SUB-102722-R IS REQUIRED

INSERT TERMINAL BLOCK NOTCH AS SHOWN AND ROTATE UPWARD.

INSTALLATION OF TERMINAL BLOCKS

TO PROVIDE ADEQUATE CLEARANCE FOR INSTALLATION TO ANY STANDARD SINGLE GANG OUTLET BOX, THE SUB-102722-R SPACER IS REQ

4.87 in. (124mm)

SUB-102722-R PLASTIC SPACER MOLDED IN RED (OPTIONAL) TERMINAL BLOCK ASSEMBLY 10197H CONTACT HOLDER BACKPLATE ASSEMBLY WITH STAINLESS STEEL GROUND PLATE AND LUG SCREWS (2) PROVIDED 19010 #6-32 x 1 in. WITHOUT SUB-102722-R 19045 #6-22 x 1 1/2 in. WITH SUB-102722-R

.69 in. (17mm)

MOLDED BUTTON WITH KEY RESET BUTTON LOCK NUT

P

REMOVAL OF TERMINAL BLOCKS

MOLDED POLYCARBONATE FACEPLATE

US

h

HERE

A

E F I R

PRY BACK LEVER 'A' IN DIRECTION OF ARROW THEN USING A FLATHEAD SCREW DRIVER, INSERT AS SHOWN AND ROTATE UPWARD.

TURN CLOCKWISE ONE QUARTER TURN TO RESET

19001 HOUSING RETENTION SCREW #8-32 x 3/8 in. (1) PROVIDED

19030 KEY (2) PROVIDED

19015 3/32 in. ALLEN WRENCH (1) PROVIDED

Electronic warranty form at www.sti-usa.com/wc14

INSTALLATION OF SS-2000 FIRE SERIES STOPPER® STATION All specifications and information shown were current as of publication, and are subject to change without notice.

ADA

SHEET 1 10277IS JAN99

compliant

12-18 AWG IF LAST STATION ON CIRCUIT, CONNECT E.O.L. RESISTOR

CLOSE ON ALARM CAUTION AN UNINSULATED SECTION OF A SINGLE CONDUCTOR SHOULD NOT BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO CONNECTIONS. THE WIRE MUST BE SEVERED, THEREBY PROVIDING SUPERVISION OF THE CONNECTION IN THE EVENT THE WIRE BECOMES DISLODGED FROM THE DEVICE.

BE SURE ALL ELECTRICAL POWER IS DISCONNECTED BEFORE STARTING THE INSTALLATION. NOTE: JUMPER NOT PROVIDED

SINGLE DEVICE

12-18 AWG

CLOSE ON ALARM

CLOSE ON ALARM INCOMING

10196 N.O. TERMINAL BLOCK (2) PROVIDED UP TO 3 TERMINALS MAY BE USED FOR EACH STATION ASSEMBLY.

OUTGOING

A

DIAGRAM DEPICTING MULTIPLE DEVICES

SUPERVISED LOOP (SEE CAUTION NOTE)

ALL TERMINALS ACCEPT TWO 12 TO 18 (AWG) VOLTAGE

RATED AVERAGE CURRENT

250 VDC 24 VAC

1 AMP 3 AMP

BUTTON LOCK NUT METAL WASHER

TO SEPARATE TERMINAL AND BUTTON ASSEMBLY GRASP TERMINAL HOUSING, USING THUMB APPLY PRESSURE DOWNWARD, REMOVE TERMINAL HOUSING AS SHOWN.

TERMINAL BLOCK RELEASE LEVER MUST FACE UPWARD AS SHOWN FOR SWITCH TO FUNCTION CORRECTLY.

REMOVAL OF TERMINAL BLOCK FROM TERMINAL HOUSING INSERT SMALL SCREWDRIVER AS SHOWN AND PRY UPWARD, REMOVE TERMINAL.

STRIP 1/4 in. OF WIRE INSULATION, INSERT IN TERMINAL (AS SHOWN). THEN USING A PHILLIPS SCREWDRIVER TURN CLOCKWISE UNTIL TIGHT.

ELECTRICAL TERMINAL 1, 2, OR 3 TERMINALS MAY BE USED VIEW IN DIRECTIONS OF ARROW

BACKPLATE ASSEMBLY VIEW IN DIRECTIONS OF ARROW

A

INSTALLATION OF ELECTRICAL WIRE INTO TERMINAL BLOCK

INSERT NOTCH AS SHOWN THEN ROTATE UPWARD

A

INSTALLATION AND REMOVAL OF TERMINAL BLOCKS AND TERMINAL BLOCK ASSEMBLY FROM BUTTON ASSEMBLY

SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • INFO @ www.sti-usa.com

SHT. 2 10277IS JAN99