STT04 Quick Reference Card
STT04 Quick Reference Card 2600T (262/264, 266/268) & 600T Pressure Transmitters
2600T (262/264, 266/268) & 600T Pressure Transmitters
STT04 Quick Reference Card
Calibration Functions
Database Parameters Adjustment
Parameter Name Xmtr Tag Name
CONF Sequence Step Name STT04 CONFIGURATION SELECT MODE MESSAGE DESCRIPTOR DATE OUTPUT TYPE
Xmtr Mode Xmtr Message Xmtr Descriptor Xmtr Date Xmtr Transfer Function
Linear to Square LINEAR-SQ ROOT Root Transition Point POINT (10%-20%)
Parameter Value
Analog or Digital Selection Text entry, 32 chars. Text entry, 16 chars. Day, Month, & Year Entry Linear, SQR(x), SQR(x3), SQR(x5), 5th Order Poly, or Double Poly Numeric Entry in %
Xmtr Damping
DAMPING (0-16 SEC)
Numeric Entry in secs.
PV Pressure Engineering Units
PRESSURE UNIT
iH2O-68F, iHg-0C, ftH2O-68F, mmH2O-20C, mmHg-0C, PSI,
Pressure PV Lower & LOWER & UPPER Upper Range Values RANGE VAL
TEMPERATURE UNITS °C, °F, °R, or °K, Selection
Xmtr TV Static Pressure Units
STATIC PRESSURE UNIT ENGINEERING UNIT
Choose one from large Selction List LOWER & UPPER ENG Numeric entry in Engineering RANGE Units
Notes:
2
The linear square root transition pont is only required for the SQR(x) Xmtr transfer function 262/264 Xmtrs have a configurable QV. 266/268 and 600T Xmtrs do not have a configurable QV.
Adjustment Method
SENSOR TRIM FULL TRIM
Enter low and high calibration pressure values then apply those pressures and press 'Enter' when stable
Xmtr Sensor Zero Calibration
SENSOR TRIM ZERO TRIM
Apply zero pressure, press 'Enter' when stable
Xmtr Sensor Restore Factory Calibration
SENSOR TRIM FACTRY TRIM
The factory calibration immediately restored when FACTRY TRIM is selected.
Xmtr Sensor Static Pressure (TV) Calibration
SENSOR TRIM STATIC TRIM
The present static pressure (TV) value is displayed. Then the new static pressure value can be entered.
Xmtr DAC Trim
D-TO-A ADJUST
Arrow keys or mA current value entry
Reset Pressure Sensor (PV) Bias Set Pressure Sensor PV Bias Zero
PV BIAS RESET PV BIAS SET PV ZERO
Select 'YES' at the RESET PV SCALE CONDITION?
Set Pressure Sensor PV PV BIAS Bias Value SET PV VAL
1
1
The PV pressure value is displayed, press 'Enter' to enter a new pressure value, a PV bias will be applied which will produce the pressure value enetred.
SET PV OUTPUT % LOW
The PV pressure value range is adjusted such that the entered PV value is set by automatic adjustements of the URV and LRV
Single Point Re-range, maintains LRV but not URV or span
SET PV OUTPUT % HIGH
The PV pressure value range is adjusted such that the entered PV value is set by automatic adjustements to the URV
1
Note
The PV pressure value is displayed, press 'Enter' to apply a PV bias which zeroes the pressure reading.
Single Point Re-range, maintains span but not URV or LRV
Notes:
Requires additional equipment to properly perform the function
Additional Device Parameters
Parameter Name
Access Method MORE
Values/Adjustments
Sensor Information
SENSOR SETUP
Displays sensor and Xmtr URL, LRL, URV, LRV, MWP, temperature limits, and serial numbers
Xmtr Reset
MASTER RESET
Select to reset the Xmtr, Iout is momentarily effected but the Xmtr configuration is unaffected.
2
Reset Configuration Changed Flag
RST CFG CHANGED Select to reset the Xmtr 'configuration changed flag' FLAG
2
Xmtr 4-20mA Loop Test FIX/CANCEL OUTPUT
PSI, BAR, or Mpa Selection
STORE THIS CONFIGURATION? (NO/YES)
1
1
BAR, mBAR, g/cm2, kg/cm2, Pa, kPa, torr-0C, ATM, Mpa, iH2O4C, or mmH2O-4C Selection Numeric entry in Engineering Units
Xmtr SV Sensor Temperature Units
Xmtr QV Free Variable Unit Free Variable QV Lower & Upper Range Values
Note
Text entry, 8 chars.
Access Method CALIB
Xmtr Sensor Full Calibration
Note
Select FIX or CANCEL. When FIX is selected a value in mA can be entered
Xmtr HART Preambles
# RESP PREAMBLES
Numeric entry of the number of HART communications preambles, usually 5
Integral Digital LCD Setup
LCD SETUP
Select PV, %, Iout, or Local Value for display. For Local Value select units, ranges, and transfer function
Xmtr Local Keys Enable/Disable
LOCAL KEYS CNTRL Select to enable or disable the local Xmtr Keys
1,2,3
Safety Xmtr Proof Test
PROOF TEST
Select to perform Xmtr proof test. Xmtr must be in maintenance mode.
4
Safety Xmtr maintenance mode operation Safety Xmtr - operate mode operation
ENTER MAINT MODE
Select to place the Xmtr in maintenance mode
4
ENTER OPERATE MODE
Select to place the Xmtr in operate mode.
4
Notes: 1 2 3 4
600T Xmtrs have different LCD options; ie, PV, %, & Iout 2600T 266/268 Xmtrs do not support the integral display option Does not apply to the Cometer or Prometer Only applies to the 2600T 266/268 Safety Xmtr
For: TH02 Temperature Transmitter, 2600T (262/264, 266/268) & 600T Pressure Transmitters
STT04 Quick Reference Card
STT04 Quick Reference Card
TH02 Temperature Transmitter
TH02 Temperature Transmitter
STT04 Key
Name Power Off
Database Parameters
CONF Sequence Step Name
Parameter Name Xmtr Tag Name
Parameter Value
Xmtr Mode Xmtr Message Xmtr Descriptor Xmtr Date Xmtr Sensor Type
STT04 CONFIGURATION SELECT MODE MESSAGE DESCRIPTOR DATE SENSOR TYPE
RTD Sensor Type
RTD TYPE
t/c Sensor Type
THERMOCOUPLE TYPE
B, C, D, E, J, K, L, N, R, S, T, OR U Selection
t/c Cold Junction Compensation RTD Sensor Factor
REFERENCE JUNCTION SENSOR FACTOR
t/c Sensor Factor
SENSOR FACTOR
Xmtr Measurement Type RTD & Ω, Number of Wires RTD & Ω Sensor Monitor Xmtr Failure Signal
TYPE OF MEASUREMENT NUMBER OF WIRES
NONE, EXTERNAL, INTERNAL Selecton 0.1, 0.2, 0.5, 1, 1.2, 2, 3, 4, 5, 6, 7, 8, 9, or 10 Selection 1, 2, 3, 4, 5, 6, 7, 8, 9, or 10 Selection Single Channel, Differential, or Averaging Selection 2, 3, or 4 Selection
Calibration Functions
Note
Text entry, 8 chars.
Adjustment Xmtr DAC Trim Sensor Input Calibration Sensor Restore Factory Sensor Input Calibration Sensor Lead Balance
Analog or Digital Selection Text entry, 32 chars. Text entry, 16 chars. Day, Month, & Year Entry Linear Wide, Linear Small, Free Style, RTD, or Thermocouple S l tiα = 0.00385, 0.003916 or Pt100
Access Method CALIB D TO A INPUT CAL
Adjustment Method
Back Note 1 1
RESET TRIM
Arrow keys or mA current value entry Value entry in °C, °F, °R, °K, mV, or Ω configured units Selection
LEAD BALANCE
Selection
1
SENSOR MONITOR FAILURE SIGNAL
None, Break Mon, Short Ckt Mon, or Break/Short Ckt Selection Over Range, Under Range, Default Value, or Hold Last Selection Numeric entry in mA
Xmtr Underange & Overange Values
UNDERRANGE & OVERRANGE VALUES
RTD & t/c Engineering Unit Free Style Engineering Unit Linear Wide & Linear Small Engineering Unit Sensor Filter Xmtr Sensor Xmtr Lower & Upper Range Values Xmtr Threashold 1 & 2 Values
ENGINEERING UNIT
°C, °F, °R, or °K, Selection
ENGINEERING UNIT
°C, °F, °R, °K, or Spcl Selection
MEASUREMENT
OHMS OR mV Selection
MAINS FILTER DAMPING LOWER & UPPER RANGE VAL THRESHOLD 1& 2 VALUES
50 Hz, or 60 Hz Selection Numeric Entry in secs. Numeric entry in Engineering Units Numeric entry in %
1
Escape
Escape from current operation and return to READY state.
Name
2
Additional Device Parameters
1 2 3 4 5
For EXTERNAL a fixed temperature offset is entered The Sensor Factor in most cases is 1 Differential & Averaging requires 2 sensors 3 & 4 wires is avaiable only for single channel For DEFAULT Value a fixed value in % is entered
Turns on STT04.
Description Language Communications Format Battery STT04 Name STT04 Rev Auto Shut-Off Keypad Layout
2 3
Parameter Name 4
5
Sensor Operative Limits Xmtr Minimum Sensor Span Xmtr Serial Number
Access Method MORE
Values/Adjustments
SENSOR SETUP
Sensor Limits are displayed
SENSOR SETUP
Sensor minimum span is diplayed
SENSOR SETUP
Xmtr serial number is displayed
SENSOR SETUP
Xmtr assembly identifcation is displayed Xmtr reset Selection
Xmtr Assemby Identification Xmtr Master Reset
MASTER RESET
Xmtr HART Preambles
# RESP PREAMBLES Numeric entry of the number of HART communications preambles, usually 5
Xmtr Configuration Changed Flag Xmtr Self Test
RST CFG CHANGED FLAG DEVICE SELF TEST
Xmtr 4-20mA Loop Test
FIX/CANCEL OUTPUT Select FIX or CANCEL. When FIX is selected a value in mA can be entered
Xmtr reset configuration changed flag Selection Xmtr self test Selection
Xmtr Factory Initialize FACTORY PRESET
Select to delete all configuration data. Restores device to factory default state
Xmtr Piecewise Linear Transfer Function
Enter values for up to 32 FREE STYLE transfer function breakpoints
STORE THIS CONFIGURATION? (NO/YES) Notes:
STT04 Options
Requires additional equipment to properly perform the function
1
Moves back one step in a menu sequence. STT04 Options Configuration Menu.
0.00392, Ni100 or Cu100 Selection
Notes:
Turns off STT04.
Options
Power On
STT04 Key
Description
CHARACTERIST. CURVE
Note
HART Devices: ABB Pressure Transmitters: ABB Temperature ABB Multivariable ABB Positioners: ABB Magmeters: ABB Analytic Transmitters: Generic Type:
Bailey-FSK Devices: ABB Pressure Transmitters: ABB Remperature ABB Positioners: ABB Analytic Transmitters:
262/264, 266/268,263/265, 267/269, 600T, 2000T, AS800, & PTH TH02-202, TS11/TS01, EBTH, TEU211, 267/269 TZID-C, TZID/AZH 50XE4, 50XM2, & 50SM1 82PH, 82EC, 82TE, & 82TC HART Universal & popular HART Common Practice commands
PTS, & BCN EQS, & EQN AVS TBN480, TBN580, & TBN581
© 2004 ABB. All Rights Reserved. PN25086