STT04 Quick Reference Card

Report 7 Downloads 193 Views
STT04 Quick Reference Card

STT04 Quick Reference Card 2600T (262/264, 266/268) & 600T Pressure Transmitters

2600T (262/264, 266/268) & 600T Pressure Transmitters

STT04 Quick Reference Card

Calibration Functions

Database Parameters Adjustment

Parameter Name Xmtr Tag Name

CONF Sequence Step Name STT04 CONFIGURATION SELECT MODE MESSAGE DESCRIPTOR DATE OUTPUT TYPE

Xmtr Mode Xmtr Message Xmtr Descriptor Xmtr Date Xmtr Transfer Function

Linear to Square LINEAR-SQ ROOT Root Transition Point POINT (10%-20%)

Parameter Value

Analog or Digital Selection Text entry, 32 chars. Text entry, 16 chars. Day, Month, & Year Entry Linear, SQR(x), SQR(x3), SQR(x5), 5th Order Poly, or Double Poly Numeric Entry in %

Xmtr Damping

DAMPING (0-16 SEC)

Numeric Entry in secs.

PV Pressure Engineering Units

PRESSURE UNIT

iH2O-68F, iHg-0C, ftH2O-68F, mmH2O-20C, mmHg-0C, PSI,

Pressure PV Lower & LOWER & UPPER Upper Range Values RANGE VAL

TEMPERATURE UNITS °C, °F, °R, or °K, Selection

Xmtr TV Static Pressure Units

STATIC PRESSURE UNIT ENGINEERING UNIT

Choose one from large Selction List LOWER & UPPER ENG Numeric entry in Engineering RANGE Units

Notes:

2

The linear square root transition pont is only required for the SQR(x) Xmtr transfer function 262/264 Xmtrs have a configurable QV. 266/268 and 600T Xmtrs do not have a configurable QV.

Adjustment Method

SENSOR TRIM FULL TRIM

Enter low and high calibration pressure values then apply those pressures and press 'Enter' when stable

Xmtr Sensor Zero Calibration

SENSOR TRIM ZERO TRIM

Apply zero pressure, press 'Enter' when stable

Xmtr Sensor Restore Factory Calibration

SENSOR TRIM FACTRY TRIM

The factory calibration immediately restored when FACTRY TRIM is selected.

Xmtr Sensor Static Pressure (TV) Calibration

SENSOR TRIM STATIC TRIM

The present static pressure (TV) value is displayed. Then the new static pressure value can be entered.

Xmtr DAC Trim

D-TO-A ADJUST

Arrow keys or mA current value entry

Reset Pressure Sensor (PV) Bias Set Pressure Sensor PV Bias Zero

PV BIAS RESET PV BIAS SET PV ZERO

Select 'YES' at the RESET PV SCALE CONDITION?

Set Pressure Sensor PV PV BIAS Bias Value SET PV VAL

1

1

The PV pressure value is displayed, press 'Enter' to enter a new pressure value, a PV bias will be applied which will produce the pressure value enetred.

SET PV OUTPUT % LOW

The PV pressure value range is adjusted such that the entered PV value is set by automatic adjustements of the URV and LRV

Single Point Re-range, maintains LRV but not URV or span

SET PV OUTPUT % HIGH

The PV pressure value range is adjusted such that the entered PV value is set by automatic adjustements to the URV

1

Note

The PV pressure value is displayed, press 'Enter' to apply a PV bias which zeroes the pressure reading.

Single Point Re-range, maintains span but not URV or LRV

Notes:

Requires additional equipment to properly perform the function

Additional Device Parameters

Parameter Name

Access Method MORE

Values/Adjustments

Sensor Information

SENSOR SETUP

Displays sensor and Xmtr URL, LRL, URV, LRV, MWP, temperature limits, and serial numbers

Xmtr Reset

MASTER RESET

Select to reset the Xmtr, Iout is momentarily effected but the Xmtr configuration is unaffected.

2

Reset Configuration Changed Flag

RST CFG CHANGED Select to reset the Xmtr 'configuration changed flag' FLAG

2

Xmtr 4-20mA Loop Test FIX/CANCEL OUTPUT

PSI, BAR, or Mpa Selection

STORE THIS CONFIGURATION? (NO/YES)

1

1

BAR, mBAR, g/cm2, kg/cm2, Pa, kPa, torr-0C, ATM, Mpa, iH2O4C, or mmH2O-4C Selection Numeric entry in Engineering Units

Xmtr SV Sensor Temperature Units

Xmtr QV Free Variable Unit Free Variable QV Lower & Upper Range Values

Note

Text entry, 8 chars.

Access Method CALIB

Xmtr Sensor Full Calibration

Note

Select FIX or CANCEL. When FIX is selected a value in mA can be entered

Xmtr HART Preambles

# RESP PREAMBLES

Numeric entry of the number of HART communications preambles, usually 5

Integral Digital LCD Setup

LCD SETUP

Select PV, %, Iout, or Local Value for display. For Local Value select units, ranges, and transfer function

Xmtr Local Keys Enable/Disable

LOCAL KEYS CNTRL Select to enable or disable the local Xmtr Keys

1,2,3

Safety Xmtr Proof Test

PROOF TEST

Select to perform Xmtr proof test. Xmtr must be in maintenance mode.

4

Safety Xmtr maintenance mode operation Safety Xmtr - operate mode operation

ENTER MAINT MODE

Select to place the Xmtr in maintenance mode

4

ENTER OPERATE MODE

Select to place the Xmtr in operate mode.

4

Notes: 1 2 3 4

600T Xmtrs have different LCD options; ie, PV, %, & Iout 2600T 266/268 Xmtrs do not support the integral display option Does not apply to the Cometer or Prometer Only applies to the 2600T 266/268 Safety Xmtr

For: TH02 Temperature Transmitter, 2600T (262/264, 266/268) & 600T Pressure Transmitters

STT04 Quick Reference Card

STT04 Quick Reference Card

TH02 Temperature Transmitter

TH02 Temperature Transmitter

STT04 Key

Name Power Off

Database Parameters

CONF Sequence Step Name

Parameter Name Xmtr Tag Name

Parameter Value

Xmtr Mode Xmtr Message Xmtr Descriptor Xmtr Date Xmtr Sensor Type

STT04 CONFIGURATION SELECT MODE MESSAGE DESCRIPTOR DATE SENSOR TYPE

RTD Sensor Type

RTD TYPE

t/c Sensor Type

THERMOCOUPLE TYPE

B, C, D, E, J, K, L, N, R, S, T, OR U Selection

t/c Cold Junction Compensation RTD Sensor Factor

REFERENCE JUNCTION SENSOR FACTOR

t/c Sensor Factor

SENSOR FACTOR

Xmtr Measurement Type RTD & Ω, Number of Wires RTD & Ω Sensor Monitor Xmtr Failure Signal

TYPE OF MEASUREMENT NUMBER OF WIRES

NONE, EXTERNAL, INTERNAL Selecton 0.1, 0.2, 0.5, 1, 1.2, 2, 3, 4, 5, 6, 7, 8, 9, or 10 Selection 1, 2, 3, 4, 5, 6, 7, 8, 9, or 10 Selection Single Channel, Differential, or Averaging Selection 2, 3, or 4 Selection

Calibration Functions

Note

Text entry, 8 chars.

Adjustment Xmtr DAC Trim Sensor Input Calibration Sensor Restore Factory Sensor Input Calibration Sensor Lead Balance

Analog or Digital Selection Text entry, 32 chars. Text entry, 16 chars. Day, Month, & Year Entry Linear Wide, Linear Small, Free Style, RTD, or Thermocouple S l tiα = 0.00385, 0.003916 or Pt100

Access Method CALIB D TO A INPUT CAL

Adjustment Method

Back Note 1 1

RESET TRIM

Arrow keys or mA current value entry Value entry in °C, °F, °R, °K, mV, or Ω configured units Selection

LEAD BALANCE

Selection

1

SENSOR MONITOR FAILURE SIGNAL

None, Break Mon, Short Ckt Mon, or Break/Short Ckt Selection Over Range, Under Range, Default Value, or Hold Last Selection Numeric entry in mA

Xmtr Underange & Overange Values

UNDERRANGE & OVERRANGE VALUES

RTD & t/c Engineering Unit Free Style Engineering Unit Linear Wide & Linear Small Engineering Unit Sensor Filter Xmtr Sensor Xmtr Lower & Upper Range Values Xmtr Threashold 1 & 2 Values

ENGINEERING UNIT

°C, °F, °R, or °K, Selection

ENGINEERING UNIT

°C, °F, °R, °K, or Spcl Selection

MEASUREMENT

OHMS OR mV Selection

MAINS FILTER DAMPING LOWER & UPPER RANGE VAL THRESHOLD 1& 2 VALUES

50 Hz, or 60 Hz Selection Numeric Entry in secs. Numeric entry in Engineering Units Numeric entry in %

1

Escape

Escape from current operation and return to READY state.

Name

2

Additional Device Parameters

1 2 3 4 5

For EXTERNAL a fixed temperature offset is entered The Sensor Factor in most cases is 1 Differential & Averaging requires 2 sensors 3 & 4 wires is avaiable only for single channel For DEFAULT Value a fixed value in % is entered

Turns on STT04.

Description Language Communications Format Battery STT04 Name STT04 Rev Auto Shut-Off Keypad Layout

2 3

Parameter Name 4

5

Sensor Operative Limits Xmtr Minimum Sensor Span Xmtr Serial Number

Access Method MORE

Values/Adjustments

SENSOR SETUP

Sensor Limits are displayed

SENSOR SETUP

Sensor minimum span is diplayed

SENSOR SETUP

Xmtr serial number is displayed

SENSOR SETUP

Xmtr assembly identifcation is displayed Xmtr reset Selection

Xmtr Assemby Identification Xmtr Master Reset

MASTER RESET

Xmtr HART Preambles

# RESP PREAMBLES Numeric entry of the number of HART communications preambles, usually 5

Xmtr Configuration Changed Flag Xmtr Self Test

RST CFG CHANGED FLAG DEVICE SELF TEST

Xmtr 4-20mA Loop Test

FIX/CANCEL OUTPUT Select FIX or CANCEL. When FIX is selected a value in mA can be entered

Xmtr reset configuration changed flag Selection Xmtr self test Selection

Xmtr Factory Initialize FACTORY PRESET

Select to delete all configuration data. Restores device to factory default state

Xmtr Piecewise Linear Transfer Function

Enter values for up to 32 FREE STYLE transfer function breakpoints

STORE THIS CONFIGURATION? (NO/YES) Notes:

STT04 Options

Requires additional equipment to properly perform the function

1

Moves back one step in a menu sequence. STT04 Options Configuration Menu.

0.00392, Ni100 or Cu100 Selection

Notes:

Turns off STT04.

Options

Power On

STT04 Key

Description

CHARACTERIST. CURVE

Note

HART Devices: ABB Pressure Transmitters: ABB Temperature ABB Multivariable ABB Positioners: ABB Magmeters: ABB Analytic Transmitters: Generic Type:

Bailey-FSK Devices: ABB Pressure Transmitters: ABB Remperature ABB Positioners: ABB Analytic Transmitters:

262/264, 266/268,263/265, 267/269, 600T, 2000T, AS800, & PTH TH02-202, TS11/TS01, EBTH, TEU211, 267/269 TZID-C, TZID/AZH 50XE4, 50XM2, & 50SM1 82PH, 82EC, 82TE, & 82TC HART Universal & popular HART Common Practice commands

PTS, & BCN EQS, & EQN AVS TBN480, TBN580, & TBN581

© 2004 ABB. All Rights Reserved. PN25086

Recommend Documents