ES-ST-WarmWire

For Residential and Commercial Applications Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative

–––––––––––––––––––––––––––––––––––––––––––––

––––––––––––––––––––––––––––––––––––––––

SunTouch® WarmWire® 120 and 240 Voltages SunTouch WarmWire is a series resistance heating cable assembly installed over plywood, backerboard, or concrete slab (according to ANSI or TCNA guidelines), and then embedded in 3/8" (9.5 mm) or greater self-leveling or polymer-modified thin-set mortar. WarmWire is approved for installation in shower applications.

Specifications 120 VAC, 1-phase 240 VAC, 1-phase

Supply Voltage

Maximum Circuit Load

20 amps (15 amps with SunStat control) 2.5" (63.5 mm) o.c. 3" (76 mm) o.c. 3.5" (89 mm) o.c.

Wire Spacing

Less than 1 milligauss at 1/2" (12.7 mm) above surface

EMF

Oxygen-free copper or nickel-copper

Heating Elements Insulation

ETFE Fluoropolymer

Ground

Copper

Minimum Allowable Bend Radius

1" (25 mm)

Power Lead Length

10' (2.7 m)

Watt Density Minimum Polymer-modified Thinset

√ 2

Installation Parameters • Measure and certify the correct wire resistance (ohms) value for the heating cables, record these readings in the chart provided in the installation manual. • Use of manufacturer’s alarm meter (LoudMouth™ meter) is recommended during installation. • Clean the subfloor. • Secure sections of the CableStrap™ to the floor. • Weave the heating cable across the floor area, fastening it to the strap. Distance between heating cables may be varied on-site to fit requirements and should average 2.5", 3", or 3.5" on-center. • Install the floor sensor in accordance with installation manual. • Install floor coverings as detailed in installation manual.

194°F (90°C) Continuously

Maximum Allowable Temperature

Application Parameters

WarmWire is available in various lengths with voltage options of 120 or 240 VAC.

120 VAC: 1amp per 10 ft2 240 VAC: 1amp per 10 ft2

Amp Draw

2

2.5" (63.5 mm) o.c.

14.4 W/ft (155.0 W/m )

3" (76 mm) o.c.

12.0 W/ft2 (129.0 W/m2)

3.5" (89 mm) o.c.

10.3 W/ft2 (110.8 W/m2)

UL Listed for U.S. under UL Standard 1673 and Canada under CAN/CSA C22.2 No. 130.2-93. Listing file number E185866.

3/8" (9.5 mm) Backer board over wood subfloor Polymer-modified setting bed over wood subfloor

Allowable Substrate

Allowable Floor Coverings

Polymer-modified setting bed over concrete slab Thin slab/self-leveling concrete over wood subfloor Thin slab/self-leveling concrete over concrete slab Tile/Stone Carpet Hardwood

* Most anti-fracture membranes are approved for use with WarmWire. Contact manufacturer for details on specific products.

Never cut the heating cable or damage it in any way. Use only the attachment methods as described in the Installation Manuals for SunTouch WarmWire as other methods may damage the heating element.

This Engineering Sheet is not intended to provide full installation instructions and safety information. In order to avoid property damage or injury, please refer to the complete installation manual and product safety information provided with the product.

SunTouch product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact SunTouch Technical Service. SunTouch reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on SunTouch products previously or subsequently sold.

WarmWire over wood frame floor with backer board

120 VAC WarmWire Coverage (ft2) √

WarmWire over wood frame floor with double plywood

2.5" O.C. (14.4 W/ft2)

3" O.C. (12 W/ft2)

3.5" O.C. (10.3 W/ft2)

Model#

8 13 17 21 25 29 34 38 42 51 59 67 76 84

10 15 20 25 30 35 40 45 50 60 70 80 90 100

12 18 24 30 36 42 48 54 60 72 84 96 108 120

120010 120015 120020 120025 120030 120035 120040 120045 120050 120060 120070 120080 120090 120100

Length Amps 39' 59' 78' 98' 117' 137' 157' 176' 196' 235' 274' 313' 352' 391'

1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0 9.0 10.0

240 VAC WarmWire Coverage (ft2) √

WarmWire over concrete slab

Electrical Wiring Diagram for Single Cable with SunStat Control (120/240VAC) Dedicated 120 or 240VAC, 20-amp (maximum) circuit (maximum 15 amp load through SunStat control).

2.5" O.C. (14.4 W/ft2)

3" O.C. (12 W/ft2)

3.5" O.C. (10.3 W/ft2)

Model#

17 25 34 42 51 59 67 76 84 101 118 135 151 168

20 30 40 50 60 70 80 90 100 120 140 160 180 200

24 36 48 60 72 84 96 108 120 144 168 192 216 240

240020 240030 240040 240050 240060 240070 240080 240090 240100 240120 240140 240160 240180 240200

Length Amps 78' 117' 157' 196' 235' 274' 313' 352' 391' 470' 548' 626' 704' 783'

1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0 9.0 10.0

Electrical Wiring Diagram for Multiple Cables with SunStat Control (120/240VAC) Dedicated 120 or 240VAC, 20-amp (maximum) circuit (maximum 15 amp load through SunStat control). p

Ground 120/240 VAC SunStat® Control Load 1 Black Black

Line 1 Black

Sensor

Ground 120/240 VAC SunStat® Control Load 1 Black

Sensor Wire (no polarity)

120 VAC or 240 VAC White

Line 2 White

A Bus B

Load 2 White

Black

WarmWire Cable 120 VAC or 240 VAC Heating Cable (maximum 15 amps)

Sensor

120 VAC or 240 VAC White

Line 2 White

A Bus B

Load 2 White

WarmWire Cable

WarmWire Cable

Two or more 120 VAC or 240 VAC Heating Cables (maximum 15 amps)

USA: Tel: (888) 432-8932 • Fax: (417) 831-4067 Canada: Tel: (888) 208-8927 • Fax: (905) 332-7068 Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091

A Watts Water Technologies Company

ES-ST-WarmWire 1433

Line 1 Black

Sensor Wire (no polarity)

suntouch.com