THDC IOM 0707

Report 8 Downloads 157 Views
A e r o S y s I

n

c

o

r

p

o

r

a

t

e

d

Installation and Maintenance Instructions THDC Series Remote Condensing Unit Congratulations on selecting a THDC condensing unit from AeroSys. With proper installation and maintenance, your system will provide you with years of satisfactory operation. This system is compatable with a properly sized and Laboratory Listed direct expansion indoor air handler.

Site Preparation and Installation To insure a satisfactory air supply, locate condensing units in a clean area, away from loose dirt and foreign matter that may clog the coil. The condensing unit’s coil/blower side must not be located near any exhaust of steam, hot air, grease or corrosive fumes. The condensing unit should be located at least 30 inches from a wall, adjacent unit or other obstruction that may restrict accessibility for maintenance. For multiple unit installations, space the units so that the hot exhaust air is not directed toward the air inlet of an adjacent unit. Install on a solid base, capable of supporting the weight of the condensing unit. The base should be higher than the surrounding grade and larger than the dimensions of the condensing unit base. The base of the unit is sloped to drain water away from the maintenance access side of the equipment. When installing Blower Motor

Condenser Blower

the unit(s), make sure to maintain the drainage angle toward the coil side of the condensing unit. Maximum recommended refrigerant line length is 50 feet. Condenser Air Ducting (if used) The total external static pressure for the inlet and outlet ducts, including grille, must not exceed 0.5 inches of water. If the condensing unit draws ducted air from the outside of the building, rain hoods must be installed. In addition, install screens over rain hood openings to eliminate the possibility of birds, water, or debris entering the unit. Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work areas. Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control vibration transmission to the building. Locate the unit and ductwork so that the discharge air does not short circuit to the condenser air inlet.Avoid directing the hot exhaust air toward adjacent doors or windows.

Suction Line Service Valve

Electrical Connections Each unit ships from the factory with all internal wiring completed. Refer to the electrical schematic when making connections.

Liquid Line Service Valve

! WARNING! UNIT CONTAINS HAZARDOUS ELECTRICAL VOLTAGE. DISCONNECT POWER SUPPLY BEFORE WORKING ON IT. THE LINE SIDE OF DISCONNECT REMAINS ENERGIZED WHEN DISCONNECT IS “OFF”. Electrical connections necessary for the condensing unit at the installation site are:

Electric Box

1) Power supply to the condensing unit line side contactor,

32 Thomas Johnson Drive - Frederick, Maryland 21702

2) 24 VAC Control wiring between the evaporator unit and the condensing unit, again connected to the condensing unit contactor coil. Power Connections All power and control wiring and ground connections must be in accordance with the National Electrical Code and local codes. Refer to unit nameplate for voltage, wire size and circuit protection requirements. USE COPPER CONDUCTORS ONLY The outdoor condensing unit requires its own power source and earth ground, with a disconnect switch (field supplied) to isolate the unit for maintenance. Route the supply power to the disconnect switch and then through one of the cabinet’s holes to the unit’s contactor. Connect an earth ground to the lug provided in the electric junction box. Control Connections A field-supplied 2 wire control connection (24VAC) is required between the evaporator and the condensing unit. Control wiring must be installed in accordance with the National Electrical Code (NEC), Class 1 circuit. Control wiring between the evaporator and the condensing unit must not allow a voltage drop in the line of more than 1 volt (16 gauge minimum for 75 feet). Piping Connections Two refrigerant lines, an insulated copper suction line and a copper liquid line, are required between the evaporator and the condensing unit. A refrigerant drier must be installed in the liquid line. When piping to the unit’s refrigerant service valves, wrap the service valves with a wet rag to prevent damage to the valve.

Motor Capacitor

Field pressure testing evacuation, and refrigerant charging may be done through the side ports on the suction and liquid line service valves. These ports are open to the field side of the piping. After field evacuation, open both service valves (back valve stem out) all the way for proper system operation. Refrigeration piping should be installed with high temperature brazed joints. ALWAYS use damp rags wrapped around the valve body to protect the valve from heat damage.Good refrigeration practices should be employed for piping supports, leak testing, dehydration, and charging of the refrigeration circuits. Vibration isolating supports should be used to isolate the refrigeration piping from the building. Pack a soft flexible material around tubing to prevent damage when sealing openings in walls and to reduce vibration transmission. NOTE ON TRAPS When installing remote condensing units above the evaporator, the suction gas line should be trapped at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit starts, oil in the trap is carried UP the vertical riser and returns to the compressor. When installing remote condensing units below the evaporator, the suction gas line should be trapped with an inverted trap the height of the evaporator. This prevents refrigerant migration to the compressor during off cycles. Refrigerant Pressures Suction and discharge pressures will vary with load and ambient conditions. Normal pressures are: Suction pressure 58-75 psig. Discharge pressure 180-275 psig at 95o F Superheat 12-18o F

Maintenance

Electric Box Ground Lug

Contactor

Each year the components of the refrigeration system should be inspected for proper function and signs of wear. Since in most cases evidence of malfunction is present prior to component failure, periodic inspections can be a major factor in the prevention of most system failures. Electric Panel The electric panel should be cleaned and inspected annually for any loose electrical connections.

Compressor Capacitor

24 VAC Contactor coil Connections

High Voltage Contactor Connections

Direct Drive Blower Package Blower impellers should be thoroughly inspected and any debris removed. Check to see if they are tightly mounted on the fan shaft and do not rub against the fan housing during rotation.

32 Thomas Johnson Drive - Frederick, Maryland 21702

Once every year add 3 drops of SAE 20 weight non-detergent oil to each of the two oil holes on the fan motor if your system is supplied with oil ports. Air Distribution Since all unit models are designed for constant volume air delivery, any unusual air flow restrictions must be avoided. Restricted airflow through the condenser coil will reduce the operating efficiency of the unit. Additionally, it can result in high compressor head pressure and loss of cooling. Using compressed air or a commercial coil cleaner, clean the

condenser coil of all debris that will inhibit airflow. In winter, do not permit snow to accumulate around the side or underneath the condenser. Check for bent or damaged coil fins and repair as necessary. Check all refrigerant lines and capillaries for vibration and support as necessary. Carefully inspect all refrigerant lines for signs of oil leaks. Refrigeration System Inspect refrigerant lines every year for signs of wear and proper support.

Trouble Shooting Guide Symptom

Possible Cause

Evaporator Coil Low airflow Ices 1) Dirty filters 2) Blower rotating backwards 3) Motor speed too low Also see “Low 4) Discharge louvers closed Suction Pressure” Thermostat located in wrong location for additional information Temperature setting too low

Possible Remedy 1) replace filters 2) reverse rotational wires 3) increase motor speed setting 4) open louvers Move thermostat to measure return air temp. Increase temp setting

Air short cycling back to return air inlet Obstruction below discharge louvers, redirect air pattern

Low Suction Pressure Also see “Evaporator” Coil Ices” for additional information

System low on charge

Add refrigerant

Leak in refrigerant piping

Find and repair leak

Expansion device stuck or clogged

Remove and replace or clean valve

Drier/strainer clogged

Remove and replace drier/strainer

System low on charge

Add refrigerant

Leak in refrigerant piping

Find and repair leak

Expansion device stuck or clogged

Remove and replace or clean valve

Drier/strainer clogged

Remove and replace drier/strainer

Temperature setting too low

Increase temp setting

Inadequate initial charge

Add refrigerant

Inadequate air flow

See “Low airflow” above

Condensing temperature too low

32 Thomas Johnson Drive - Frederick, Maryland 21702

Symptom Noisy Compressor

Possible Cause

Possible Remedy

Head pressure too high

See section for “Condenser pressure too high”

Condenser pressure too high

See section for “Condenser pressure too high”

Expansion valve open(Liquid “slugging”) Abnormally cold suction lineFeeler bulb loose; tighten& insulate

Condenser Head Pressure too High

Compressor “short cycles”

System over charged

Recover excess refrigerant

Vibration mounts tight

Loosen vibration mount nuts

Worn or scarred compressor bearings

Replace Compressor

Broken compressor valves

Replace Compressor

Restricted air flow at outside heat exchanger

Remove restriction for airflow. Wall sleeve installed incorrectly.

Condenser air discharge recirculating to condenser coil inlet

Deflect air discharge away from condenser coil inlet

Access panel not on unit, air not passing over condenser coil

Put condenser access panel on unit

Debris on condenser coil

Clean debris away; clean condenser coil

Low motor RPM

Increase fan motor speed settings

High static pressure to condenser fan

Check and remove fan restrictions

System is over charged

Recover excess refrigerant

Condenser fan running in reverse

Reverse fan rotation

Non-condensable gas (or wrong refrigerant) in refrigerant system

Recover refrigerant, evacuate system and recharge with new gas. Install new drier/strainer

Condenser fan not operating

Defective contactor motor or capacitor. Replace contactor, motor and/or capacitor

Defective contactor, motor or capacitor

Replace contactor, motor and/or capacitor

Dirty or iced evaporator coil

Clean coil, See “Evaporator Coil Ices” above

Compressor cycling on high or low pressure switches (if supplied)

Check and replace switch(es) if defective

Low voltage to compressor

Check voltage to system and correct.

Loose power terminal

Tighten electrical terminals

Compressor cycling on internal overloads

Check for, and correct: Low suction pressure, high suction and/or discharge temperature, voltage out of operating range, defective run capacitor

32 Thomas Johnson Drive - Frederick, Maryland 21702

THDC 36 = 50 MFD

:$//6/((9( 237,21$/

$

(;7(5,25%8,/',1*685)$&( 68&7,21$1'5(7851 5()5,*(5$17/,1(67