U5706 Ringless Pedestal U5707 Ring Type Pedestal To increase ...

Report 21 Downloads 68 Views
U5706 & U5707 TEMP TO FINAL SERVICE PEDESTAL ORDERING INFORMATION

U5706 Ringless Pedestal Catalog Number U5706-O-200S* U5706-O-200S-KK* U5706-O-200P U5706-O-200P-KK U5706-O-KK

Amps 200 200 200 200 200

Service 120/240 120/240 120/240 120/240 120/240

By-Pass None Horn None Horn Horn

Main Circuit Breaker 200a 2p 200a 2p 200a 2p 200a 2p Provision

Main Wired Series Series Parallel Parallel —

Replacement Main Type* UQFPH-M UQFPH-M UQFPH-M UQFPH-M —

Branch Circuits 4 4 4 4

Weight LBS. 79 79 79 79

Service 120/240 120/240 120/240 120/240 120/240

By-Pass None None None None None

Main Circuit Breaker 200a 2p 200a 2p 200a 2p 200a 2p Provision

Main Wired Series Series Parallel Parallel —

Replacement Main Type* UQFPH-M UQFPH-M UQFPH-M UQFPH-M —

Branch Circuits 4 4 4 4

Weight LBS. 79 79 79 79

U5707 Ring Type Pedestal Catalog Number U5707-O-200S* U5707-O-200S U5707-O-200P U5707-O-200P U5707-O

Amps 200 200 200 200 200

3

Up to two receptacle/circuit breaker kits can be field or factory installed. See below for ordering information. Contact factory for factory installed kits.

To increase pedestal height, order field-installed post extension kit K5708. For field installed fifth terminal in the 9 o’clock position, order kit K5T. For field converting from parallel to series wired, order kit K5194. For field converting from series to parallel wired, order kit K5193. *Stock model.

Receptacle / Circuit Breaker Kits & Receptacle Bridge Kits Catalog Number K5400-520GR K5400-620 K5400-620GB K5400-1450 K5400-1450GB

Amps/ Volts NEMA Config 20a 120v 5-20R Duplex GFI 20a 240v 6-20R Simplex 20a 240v 6-20R Simplex 50a 120/240v 14-50R 50a 120/240v 14-50R

Circuit Breaker 20a 1p 20a 2p 20a 240v GFI 50a 120/240v 50a 120/240v GFI

Conductor 12 awg 12 awg 12 awg 8 awg 8 awg

Configuration Fig. 1 Fig. 2 Fig. 3 Fig. 4 Fig. 4

K5400-BRIDGE-1POS Self-grounded ONE position bridge with hardware and instructions. Fig. 5 K5400-BRIDGE-2POS Self-grounded TWO position bridge with hardware and instructions. Fig. 6 Receptacle kits include: receptacle, circuit breaker, connected wire, cover plate, mounting screws and instructions. Contact factory for other kits. NOTE: Receptacle grounding is provided by metal contact with bridge and pedestal. Be sure to torque all fasteners per torque requirements. Fig. 1 K5400-520GR

Fig. 5 K5400-BRIDGE-1POS

Fig. 2 K5400-620

Fig. 3 K5400-620GB

Fig. 6 K5400-BRIDGE-2POS

Fig. 4 K5400-1450

Fig. 7 UQFPH-M-200

Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering or installing this equipment.

3

2

U5706 & U5707 TEMP TO FINAL SERVICE PEDESTAL PRODUCT SPECIFICATIONS

5.50 I.D. 5.5

48.00

L I N E

80.00

L O A D Grade Line

24.00

U5706-O-200P * (Shown with (2) K5400-520GR receptacles, K5400-BRIDGE-2POS & line side conductor installed.)

14.00 O.D.

3.50 O.D.3.50

SPECIFICATIONS • 200 amp, 1∅, 120/240 volt, 22K AIC, underground service only. • U5706 has Ringless meter socket available with or without KK horn type bypass. • U5707 has Ring type meter socket with MR-4 screw type meter ring. • Suitable for use as service equipment, mobile home service equipment and temporary power service equipment. *• Provisions for up to two Type 3R in-use receptacle kits. *• Order receptacle and bridge kits separately. See ordering information. • Direct burial pedestal suitable for free standing or structure mounted installation. • Separate line and load wireways are removable, lockable and sealable for security. • Left side is for utility connection. Right side is for customer underground load exit. • Convenient knockouts in post for thru-wall load exit requirements. • Type 3R enclosure constructed with type G90 galvanized steel. • Repaintable light gray polyester powder coat finish. • Wire terminations accept copper or aluminum conductors: Line & Neutral: #6-350 Ground: (4) #14-1/0. • Main circuit breaker can be series or parallel connected. See note on page 3. • Universal 4 circuit branch 125 amp interior (up to (2) 2-pole) accepts most manufacturers plug-in type circuit breakers. See wiring diagram.