electric fan coil unit schedule

Report 9 Downloads 87 Views
CONDENSER UNIT SCHEDULE SYMBOL

SERVICE

FAN COIL UNIT SCHEDULE

ELECTRICAL

COOLING CAPACITY (MBH)

HEATING CAPACITY (MBH)

WEIGHT LBS

AMBIENT TEMP (DEG F)

IEER

MINIMUM AMPACITY

KW

MANUFACTURER MODEL NO.

VOLTS/PH/HZ

CU-1

1st thru 4th FLOORS

69

62

444

95

23.1

24

-

208/3/60

MITSUBISHI/PURY-P72TLMU-A-BS

CU-2

REDUNDANT UNITS

108

99

695

95

19.9

42

-

208/3/60

MITSUBISHI/PURY-P120TLMU-A-BS

CU-3

5th FLOOR thru CAB

154

145

702

95

15.9

68

-

208/3/60

MITSUBISHI/PURY-P168TLMU-A-BS

NOTES

REMARKS: 1. PROVIDE WITH LOW AMBIENT COOLING KIT/CONTROLS TO ALLOW FOR HEATING DOWN TO -4 DEGREES F. 2. SIMULTANEOUS HEATING AND COOLING MODEL. 3. SEACOAST MODEL.

BC CONTROLLER SYMBOL

MANUFACT

BC-1

MITSUBISHI

BC-2 BC-3

MODEL

SIZE

VOLT

PH

MCA

WEIGHT

CMB-P108NU-G1

8

208/230

1

0.68

84 LB

MITSUBISHI

CMB-P105NU-G1

5

208/230

1

0.44

72 LB

MITSUBISHI

CMB-P108NU-HA1

8

208/230

1

1.7

124 LB

REMARKS:

WALL LOUVER SCHEDULE MARK

AREA SERVED

USE

MANUF

MODEL

TYPE

SIZE

MATERIAL

THICKNESS

REMARKS

WL1

TOWER STAIRS

INTAKE

GREENHECK

ESD-403

DRAINABLE

ALUMINUM

4"

1,4,5

WL2

TOWER STAIRS

RELIEF

GREENHECK

ESD-403

DRAINABLE

ALUMINUM

4"

2,3,4

WL3

OUTSIDE AIR

INTAKE

GREENHECK

ESD-403

DRAINABLE

ALUMINUM

4"

2,3,4

WL4

-

-

GREENHECK

ESD-403

DRAINABLE

ALUMINUM

4"

-

WL5

ELEVATOR

RELIEF

GREENHECK

ESD-403

DRAINABLE

ALUMINUM

4"

2,4

1. PROVIDE WITH ALUMINUM BIRDSCREEN

2. PROVIDE WITH ALUMINUM INSECT SCREEN

3. PROVIDE WITH BACKDRAFT DAMPER (BDD)

4. COLOR AS SPECIFIED BY ARCHITECT

REMARKS: 1. PROVIDE WITH OPTIONAL CONDENSATE PUMP. 2. LISTED CFM IS FOR LOW SPEED. 3. LISTED CFM IS FOR MEDIUM SPEED. 4. LISTED CFM IS FOR HIGH SPEED. 5. TEMP. SENSOR IN UNIT RETURN AIR WITH BC CONTROLLER AND G-50A CONTROLLER, SEE PLANS AND SPECIFICATIONS. 6. PROVIDE CONTROLS INTERLOCK TO EMO SWITCHES. 7. SECOND UNIT SERVES AS REDUNDANT UNIT.

AIR DEVICE

5. PROVIDE WITH MOTORIZED DAMPER

VERIFY CEILING TYPES BEFORE ORDERING AND PROVIDE SQUARE-ROUND TRANSITIONS WHERE REQUIRED BASIS OF DESIGN: PRICE

UNIT HEATER - ELECTRIC GENERAL UNIT SYMBOL

SERVICE

UH-1

FIRE PUMP ROOM

1 WALL MOUNTED THERMOSTAT

MANUF.

CAPACITY

MODEL

QMARK

UNIT

MUH

TYPE

UNIT HEATER

SYMBOL

ELECTRIC

FLOW SL (CFM)

HEAT SL (BTUH)

350

-

KW

VOLT

3.0

208

PH

1

HZ

60

AMP

OPERATING WEIGHT (LB)

14.5

NOTES

50

2

2 UNIT MOUNTED THERMOSTAT

SERVICE

MANUFACT

TYPE

MODEL

FLOW @ELEV

TSP @ELEV

(CFM)

(IN.WG)

DESCRIPTION

FUNCTION

CD1

CEILING DIFFUSER

SUPPLY

CD2

CEILING DIFFUSER

CG1

CEILING GRILLE

WR1 WR2

MODEL

DRIVE TYPE

RPM

ROOF OPENING W (IN)

L (IN)

HP OR WATTS

VOLT

PH

OPERATING WEIGHT (LB)

REMARKS

TYPE

BALANCING

FIRE

DAMPER

DAMPER

MATERIAL

THROW

PLENUM

FINISH

LAY-IN

SCDA-4

LOUVERED

N/A

N/A

STEEL

ADJUSTABLE

SEMI-GLOSS

SURFACE

SCDA-3

LOUVERED

N/A

N/A

STEEL

ADJUSTABLE

SEMI-GLOSS

RETURN/TRANSF

LAY-IN

80DAL

EGGCRATE

N/A

N/A

STEEL

N/A

SEMI-GLOSS

N/A

WALL REGISTER

SUPPLY

SURFACE

N/A

N/A

STEEL

ADJUSTABLE

SEMI-GLOSS

N/A

WALL REGISTER

SUPPLY

SURFACE

N/A

N/A

STEEL

ADJUSTABLE

SEMI-GLOSS

N/A

CONTRACTOR TO PROVIDE TRANSITIONS, SUCH AS ROUND TO OVAL WHERE REQUIRED. PROVIDE ALL REQUIRED DEVICES, SUCH AS MOUNTING CLIPS, SUPPORTS.

FAN SCHEDULE UNIT No.

MOUNTING

REMARKS

FLOOR PLAN CONVENTIONS DIFFUSER/REGISTER CFM NECK SIZE/SIZE

REMARKS: 1 1/2"x1/2"x1/2" CORE SIZE

GRILLE SIZE

N/A

CD1 & CD2 NECK SIZING CFM RANGE

ROUND NECK SIZE

FACE PANEL SIZE

0-130

6" DIAM

12"x12"

0-130

6" DIAM

24"x24"

EF-1

SHOWER 202

CEILING

GREENHECK

SP-A110

100

0.25

DIRECT

-

-

17.8

115

1

20

1,3,6,7,8,12

131-210

8" DIAM

24"x24"

EF-2

RESTROOM 402

CEILING

GREENHECK

SP-A110

75

0.25

DIRECT

-

-

17.8

115

1

20

1,3,6,7,8,12

211-320

10" DIAM

24"x24"

EF-3

RESTROOM 702

CEILING

GREENHECK

SP-A110

75

0.25

DIRECT

-

-

17.8

115

1

20

1,3,6,7,8,12

321-420

12" DIAM

24"x24"

EF-4

BREAK RM 701

CEILING

GREENHECK

SP-A125

DIRECT

-

-

115

1

20

3,6,7,8,10

421-530

14" DIAM

24"x24"

EF-5

CAB 801

CEILING

GREENHECK

SP-A125

DIRECT

-

-

115

1

20

3,6,8,10,11

EF-6

CUST 203

CEILING

GREENHECK

SP-A125

75

0.25

DIRECT

-

-

17.8

115

1

20

3,6,7,8,10

SF-1

TOWER STAIRS

INLINE

GREENHECK

BSQ-xxx

1740

0.25

BELT

-

-

1/3

115

1

104

2,3,4,5

REMARKS: 1. INTERLOCK WITH LIGHTS. 2. DISCONNECT AND MOTOR STARTER. 3. COUNTERBALANCED BACKDRAFT DAMPER.

4. INTERLOCK WITH FIRE ALARM. 5. OVERSIZED MOTOR. 6. WITH SPEED CONTROLLER.

7. WITH WALL CAP. 8. WITH GRILLE. 9. WITH WALL T'STAT

1140

1

10. WITH WALL SWITCH 11. WITH ROOF CAP. 12. WITH 10 MIN DELAY TO OFF.

6501 Americas Pkwy NE , Suite 400 Albuquerque, NM 87110 505.247.0294 Fax 505.242.4845 www.whpacific.com

100% CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION AIR TRAFFIC CONTROL TOWER (ATCT)

MECHANICAL SCHEDULES NO.

DATE

REVISION

BY

I

I

FDOT FM No. 437014-1-94-1

FDOT CONTRACT No. G0383

DATE

05/07/16

REVISION DATES (SEE DESCRIPTION AT LEFT) R1

R4

R2

R5

R3

R6

AEC JOB NO.

1412

DWG. NO. SHT.

M601

SHT.

OF