EMERGENCY AUTOMATIC PANELS FOR GENSET UNITS TYPE ...

Report 16 Downloads 45 Views
GB GE/FO-130906

EMERGENCY AUTOMATIC PANELS FOR GENSET UNITS FITTING A DIESEL OR GASOLINE ENGINE

32 Three-phase 58 Single-phase

LEM-430/45

45

LEM-430/60

60

COMPLETE WITH DISPLAY TO SHOW: • useful signals for generator set management. 8 instruments: - mains voltmeter - generator voltmeter - generator ammeter (On request) - generator frequency meter - total hour meter - partial hour meter - battery voltmeter - fuel level indicator

Threephase

LEM-435/32

Amp (Ac1)

SIMULTANEOUS READING OF 3 INSTRUMENTS

TYPE

• REMOTE SWITCHING MAINS/GENSET • SINGLE-PHASE VOLTMETRIC MAINS/GENERATOR CONTROL • AUTOMATIC BATTERY CHARGING (1,5A) • AUTOMATIC SUPERVISION OF FAULTS • EJP FUNCTION • GLOW PLUGS CONTROL • STARTER CONTROL • REMOTE COMMANDS WITH CONTACTS (STARTUP - TEST - STOP) • PROGRAMMING OF PARAMETERS MADE EASY BY DIP SWITCHES • AVAILABLE INPUT FOR ANOMALY • CLOCK FOR PROGRAMMING THE START UP OR STOPPING OF THE GENSET • PROGRAMMABLE WEEKLY SELFTEST ON REQUEST • GENERATOR AMMETER • MAINS THREE-PHASE VOLTMETRIC CONTROL • EMERGENCY BUTTON • KEY FOR EMERGENCY MANUAL STARTUP • GENERATOR OVERLOAD SWITCH

®

• PRE-WIRED MALE CONNECTOR

Via Naviglio Alto,24/A 43100 PARMA (ITALY) Tel. 0521 772021 Fax 0521 270218 www.elcos.it e-mail: [email protected]

BRIEF INSTRUCTIONS

REMOTE CONTROLS INDICATION ON THE DESCRIPTION DISPLAY STARTING START STOPPING STOP START EJP EJP STARTING EJP SWITCHING EJP CONSENT CALL FROM EXTERNAL VOLTMETRIC RELAY

THE FUEL LEVEL INDICATOR IS DISPLAYED

TOTAL HOURTOTALE METER CONTAORE

PARTIAL HOUR METER. SHOWS HOURS OF OPERATION SINCE THE LAST TIME THE GENERATOR SET WAS SWITCHED ON.

THE DISPLAY SHOWS CLOCK FOR PROGRAMMING THE START UP OR STOPPING OF THE GENSET

THE ENGINE COOLING IS DISPLAYED

BATTERY CHARGER IN OPERATION

PUSH BRIEFLY TO SHOW THE INSTRUMENTS, HOLD DOWN TO VERIFY THE LED TEST OR THE GENERAL ALARMS SILENCING AND TO VIEW THE HISTORICAL RECORD

®

THE DISPLAY SHOWS: AUT

• VOLTMETER • MAINS/GENSET AMMETER • GENSET FREQUENCYMETER

OFF

MAN

TEST

%START VOLT AMP HZ

MAINS GENERATOR BATTERY

h

STOP

h

!

%

A1

EMERGENCY STOP

AVAILABLE FAULT

OFF

THE GLOW PLUGS PREHEATING IS DISPLAYED

AUT

TEST

STARTING FAILURE ALARM

MAN

THE DISPLAY SHOWS: THE TOTAL OPERATING HOURS AND THE GENSET FREQUENCY

STOPPAGE DUE TO OVERFREQUENCY

ALARM DUE TO NO FUEL

START

RESET

STOPPAGE DUE TO: • BELT BREAKAGE • BATTERY CHARGING FAILURE

STOP

www.elcos.it

STOPPAGE DUE TO: INSUFFICIENT OIL PRESSURE

USER IS CONNECTED TO MAINS

MAINS VOLTAGE IS PRESENT

CUMULATIVE ALARM

PRESS TO SELECT THE FUNCTIONS OF: • AUT OFF • OFF AUT MAN TEST • MAN • TEST

KEY ENABLED WHEN THE CONTROL PANEL IS IN MANUAL OPERATION, PRESS TO DIVERT THE MAINS TO THE POWER USERS, OR TO THE GENERATOR WHEN THE ENGINE IS RUNNING

PRESS TO RESET, THIS OPERATION ENABLES ALL THE BLOCKED FUNCTIONS

INSTRUMENTS

DIMENSIONS

PUSH TO START THE ENGINE WHEN THE CONTROL PANEL IS IN MANUAL FUNCTION

ENGINE IS RUNNING

THE GENERATOR IS ON: LED ON GENERATOR UNDER-VOLTAGE: FLASHING LED (A FLASH THEN A PAUSE) GENERATOR OVER-VOLTAGE: FLASHING LED (TWO FLASHES THEN A PAUSE)

PUSH TO STOP THE ENGINE WHEN THE CONTROL PANEL IS IN MANUAL FUNCTION

SUPPLIED ACCESSORIES

304 284 255 200

• MAINS VOLTMETER • GENERATOR VOLTMETER

USER IS CONNECTED TO THE GENERATOR

STOPPAGE DUE TO ENGINE OVERHEATING

KIT MOUNTING BRACKET LEM

8,5

• GENERATOR AMPEREMETER (On request) • GENERATOR FREQUENCY METER • TOTAL HOUR METER

316

• BATTERY VOLTMETER

377 400 420

• PARTIAL HOUR METER

• FUEL LEVEL INDICATOR

TECHNICAL DATA -SUPPLY VOLTAGE

SIMULTANEOUS READING OF THREE INSTRUMENTS

-DEGREE OF PROTECTION

ANOMALY HISTORICAL RECORD (Including data from the last 100 anomalies)

255

-WALLINSTALLATION

12 VDC OR 24 VDC

IP40

184