first floor plan

Report 3 Downloads 160 Views
www.luptonrausch.com

FIRE RATING NOTES

G

A

2-HR RATED FIRE EXIT ENCLOSURE PER U.L. DESIGN U-412

B

2-HR RATED HORIZONTAL DUCT PROTECTION AT _A.F.F. PER WHI DESIGN WHI 694-0300.1

C

1-HR RATED FIRE BARRIER PER U.L. DESIGN U-465

D

2-HR RATED COLUMNS PER U.L. DESIGN X-827 AND X-829 (SEE NOTE 3.)

E E

ROOF PLAN

THIRD FLOOR PLAN

SCALE 1" = 20'-0"

SCALE 1" = 20'-0"

2-HR RATED WALL STAIR SHAFT PER U.L. DESIGN U-412, U-497 AND ICC-ES EVALUATION REPORT ESR-2397 @ GLASS WALL ENCLOSURE

F

2-HR RATED ELEVATOR HOISTWAY ENCLOSURE PER U.L. DESIGN U-497

G

2-HR RATED HVAC SHAFT PER U.L. DESIGN U-412 AND U-497

H

1-HR RATED SMOKE BARRIER FOR AREA OF REFUGE PER U.L. DESIGN U-465

J

2-HR RATED ELEVATOR CONTROL EQUIPMENT ROOM ENCLOSURE PER U.L. DESIGN U-412 AND U-497

OCCUPANCY: USE GROUP (B) BUSINESS

K

2-STORY ATRIUM WITH 1HR RATED FIRE BARRIER ENCLOSURE PER U.L. DESIGN U-465 AND GLASS PROTECTION PER OBC SECTION 405.5, EXCEPTION #1. REFER TO FIRE PROTECTION DRAWINGS

::

G

1. PROVIDE JOINT SEALANT SYSTEMS FOR ANY RATED WALL/ FIREPROOFING JOINT TRANSITIONS TO MAINTAIN CONTINUITY OF FIRE RATED ASSEMBLIES. (SPEC SEAL SERIES AS200 ELASTOMERIC SPRAY) 2. PROVIDE TOP OF WALL TERMINATION AT FLOOR AND ROOF DECKS PER U.L. SYSTEM HW-D-0102 OR APPROVED EQUAL G

G

E C

E

3. REFER TO STRUCTURAL DRAWINGS FOR EXTENT OF 2-HR FIREPROOFING OF STRUCTURAL MEMBERS. (U.L. DESIGN N-759, X-827 AND X-829) 4. REFER TO VOLUME III, "I" SERIES DRAWINGS FOR ADDITIONAL USE AND OCCUPANCY INFORMATION, ACCESSORY OCCUPANCIES AND INCIDENTAL USE AREAS 614.233. 6929 fx

5. RATED WALL SYSTEMS THAT TERMINATE AT EXTERIOR WALLS SHALL EXTEND TO THE INSIDE FACE OF EXTERIOR SHEATHING OR FACE OF ALUMINUM CURTAINWALL FRAMING MEMBERS. FIRE SEAL JOINT WHERE REQUIRED.

WALL DESIGNATIONS F

F

2 HOUR FIRE WALL H

1 HOUR FIRE BARRIER

::

SMOKE BARRIER WITH 1 HR FIRE RATING.

OHIO BUILDING CODE DATA CHAPTER 3: USE OR OCCUPANCY FIRST FLOOR: (B) BUSINESS, GENERAL OFFICE SECOND FLOOR: (B) BUSINESS, GENERAL OFFICE G

E

E

THIRD FLOOR: (B) BUSINESS, GENERAL OFFICE

614.224. 9050 v

G

FOURTH FLOOR: (B) BUSINESS, GENERAL OFFICE FIFTH FLOOR: (B) BUSINESS, GENERAL OFFICE REFER TO SHEET I-004, FOR EXTENT OF ACCESORY USE AREAS

FIFTH FLOOR PLAN

SECOND FLOOR PLAN

SCALE 1" = 20'-0"

CHAPTER 5: GENERAL BUILDING HEIGHTS & AREAS

SCALE 1" = 20'-0"

OCCUPANCY: USE GROUP (B) BUSINESS

TABLE 503; CONSTRUCTION TYPE II-B

OCCUPANCY: USE GROUP (B) BUSINESS

PROPOSED BUILDING STATISTICS 5-STORY BUILDING

G

71 FT AVERAGE HEIGHT ABOVE GRADE ALLOWABLE HEIGHT AND AREA WITH INCREASES ::

(B) BUSINESS USE (GENERAL OFFICE) - HEIGHT, 75FT; 5-STORY; 86,250 S.F. / FLOOR ACTUAL FLOOR AREAS

G G

E G

E

C

G

E

C

FIRST FLOOR SECOND FLOOR THIRD FLOOR FOURTH FLOOR FIFTH FLOOR

41,452 S.F. 40,630 S.F. 42,355 S.F. 42,355 S.F. 42,355 S.F.

TOTAL AREA

209,147 S.F.

E CHAPTER 6: TYPE OF CONSTRUCTION TYPE II-B TABLE 601 - FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS

4 3 0 S o u t h F r o n t S t r e e t , C o l u m b u s, O H 4 3 2 1 5

J

0-HR FIRE RATING 0-HR FIRE RATING 0-HR FIRE RATING 0-HR FIRE RATING 0-HR FIRE RATING 0-HR FIRE RATING

TABLE 602 - FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS FIRE RESISTANCE RATING FOR EXTERIOR WALLS (SEPARATION DISTANCE > 10 FEET) F

F

F

F

H

0-HR RATING

H CHAPTER 7: FIRE RESISTANT MATERIAL AND CONSTRUCTION TABLE 704.8 - MAXIMUM AREA OF EXTERIOR WALL OPENINGS (NO LIMIT TO OPENINGS WITH SEPARATION GREATER THAN 20 FT.) SECTION 706 - FIRE BARRIES 706.3.1 - SHAFT ENCLOSURE FIRE RESISTANCE RATING = 2-HR. 706.3.2 - EXIT ENCLOSURE FIRE RESISTANCE RATING = 2-HR. K

706.3.3 - EXIT PASSAGEWAY FIRE RESISTANCE RATING -2-HR 707.14.1 - ELEVATOR LOBBY SEPARATION NOT REQUIRED PER EXCEPTION #4 714.1 - STRUCTURAL MEMBERS SHALL HAVE A FIRE RESISTIVE RATING NOT LESS THAN THE RATING FOR THE RATING REQUIRED FOR THE FIRE RESISTIVE RATED ASSEMBLY SUPPORTED 714.6 - LOOSE LINTELS ARE NOT REQUIRED TO BE RATED. LINTELS SPANNING LESS THAN 6 FEET AND CONNECTED TO THE STRUCTURE ARE NOT REQUIRED TO BE RATED.

G

CHAPTER 9: FIRE PROTECTION SYSTEMS

E

E

AUTOMATIC FIRE SUPPRESSION PROVIDED THROUGHOUT IN ACCORDANCE WITH 903.3.1.1

FOURTH FLOOR PLAN

FIRST FLOOR PLAN

SCALE 1" = 20'-0"

SCALE 1" = 20'-0"

OCCUPANCY: USE GROUP (B) BUSINESS

NEW OFFICE BUILDING

10 WEST NATIONWIDE BOULEVARD 10 WEST NATIONWIDE BOULEVARD COLUMBUS, OHIO 43215

PROJECT NUMBER

11012.0

ISSUED FOR PERMIT AND BID

OCCUPANCY: USE GROUP (B) BUSINESS A

NATIONWIDE REALTY INVESTORS

10/03/11

B

G

E C

0

E E

C

A

5

10

20

40FT

NORTH

E

ARCHITECTURE + INTERIOR

DESIGN

G

B

::

J

F

H

LUPTON RAUSCH

F

G-003

F

SHEET NUMBER

F

J

LIFE SAFETY PLANS AND CODE DATA

C

SHEET TITLE

G

::

STRUCTURAL FRAME BEARING WALLS NON-BEARING EXTERIOR WALLS NON-BEARING INTERIOR WALLS FLOOR CONSTRUCTION ROOF CONSTRUCTION