Sensor Technologies Passive Infrared Relay (PIR) Technology • •
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Dual Technology • • •
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Self-Adaptive Technology • •
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
North America Headquarters 203 Cooper Circle Peachtree City, GA 30269
Service & Support Center 6 Green Tree Drive South Burlington, VT 05403
P: 800-553-3879 F: 800-954-7016
P: 800-553-3879 F: 800-954-7016
Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com
[email protected] www.coopercontrol.com
[email protected] As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.
LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •
Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.
Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com
ACC101050
Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.
Printed in USA
Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049
10/11
Greengate Occupancy Sensor Guide
Occupancy Sensor Application Guide Commercial Wall Switch Sensors
Commercial Low Voltage Ceiling Sensors
Commercial Line Voltage Ceiling Sensors
PIR1500-120-347
US1500-120 or 277
US2000-120 or 277
DT2000-120 or 277
OXC-P-2MH0-R
OXC-P-1500-R
ODC-U-0100-H
ODC-U-0501-H
OMC-DT-0701-R
OMC-DT-2000-R
OMC-U-2000
OMC-U-1001
OMC-U-0501
OMC-P-1200-R
OMC-P-0450-R
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-DMV-*
ONW-D-1001-MV-*
OSW-U-0721-24AC-R-*
OSW-U-0721-GERR7-*
Specification Grade
OSW-U-0721-SP-*
OSW-U-0721-MV-*
OSW-P-0451-D347-*
OSW-P-0451-347-*
OSW-P-0451-MV-*
OSW-P-0451-DMV-*
Commercial Grade
Specifications Technology
Passive Infrared
Ultrasonic
Dual Technology
Mounting Coverage (Sq ft)
450
1000
Ultrasonic
1200
347V
120 to 277V
Not Required
Photocell
10-30VDC
RR7 Relay
Required
RR7 Relay Required
Dual Technology
24 VAC Supply 24 VAC Required
120 to 277V
347
Environmental Operating Temperature/Humidity Available Colors
Not Required
Included
SP, 3-Way*, No Neutral Required
Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*, No Neutral Required
W, V Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*
SP
700
360° 8-12’
50 linear
10-30VDC
Required
RR7 Relay Required
24 VAC Required Not Included
SP, 3-Way*, Light Icon, EcoMeter
Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
Not Included
Internal OMC-U0501-R
Included
OMC-U1001-R
OMC-U2000-R
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
SP, 3-Way* Night Light
GOOD BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD GOOD GOOD GOOD GOOD
GOOD BETTER
GOOD
GOOD
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BEST BEST
BEST BEST
BEST BEST
BEST BEST
GOOD BETTER
GOOD BETTER
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BEST BETTER
BEST BETTER
BEST BEST
BEST BEST
BEST BEST
BEST BEST
BETTER BETTER
BETTER BETTER
BETTER BETTER
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD
BETTER GOOD BEST BEST
BETTER GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BEST BETTER GOOD BEST BEST
BETTER BEST BETTER GOOD BEST BEST
BEST
GOOD BETTER
GOOD BETTER
GOOD BETTER
BETTER GOOD GOOD
BETTER GOOD GOOD
BETTER GOOD GOOD
GOOD
BETTER
BETTER
BETTER
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
8-12’ Manual Adjustment
8-15’
120 to 347V
Not Required Internal ODC-U0051-R-H
Included
ODC-U0100-R-H
Not Included
Included
Internal
Not Included
-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing
32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing
W
W
Up to 5 sensors can be used per switchpack
No switchpack required
Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST
Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD
GOOD BEST
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BEST BETTER GOOD
BETTER BETTER BEST BEST BEST BEST BEST
BETTER
BETTER
BEST
BEST
BEST
BETTER
BEST BEST BEST
BEST BEST BEST
BETTER BETTER BETTER
GOOD BEST BETTER BEST BETTER GOOD
BEST
BEST
BETTER BETTER
BEST BEST
BEST
BEST
BETTER
BETTER
BEST BETTER BETTER
BEST BETTER BETTER
BEST BETTER BETTER
GOOD GOOD
BETTER GOOD GOOD
BEST BEST
GOOD GOOD
GOOD BETTER
BETTER BETTER
BEST BEST
BEST BEST BETTER
BETTER BETTER BEST
BETTER BETTER BETTER
BEST BEST BEST
BETTER
BEST
BEST
BETTER BETTER BETTER
BEST BETTER BETTER
BEST
GOOD BEST BEST
BEST
BETTER
BETTER
GOOD
GOOD BEST
GOOD
BEST BEST BETTER BETTER
GOOD GOOD GOOD
BEST BEST BETTER
BEST GOOD BEST BEST
GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
1500
15 sec to 30 min
BEST BEST BEST
2000
up to 25’ Self-Adjust
GOOD GOOD BETTER
BETTER BEST
2MHO
120 or 277V
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing
SP, Light Icon, EcoMeter
Passive Infrared
Ultrasonic
360°
Not Included
W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
1500
Required Internal
Commercial Wall Switch Sensors
BETTER BEST
Dual Technology
360° Manual Adjustment
15 sec to 30 min
Included
100 linear
180°
120 to 277V
W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode
2000
15 sec to 2 hr
32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode
1000 180°
RR7 Relay
Not Included
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A
Passive Infrared
Ceiling
10-30VDC
Internal
Not Included
Ultrasonic
Self-Adjust
Not Included
BAS/HVAC Relay
500
360°
15 sec to 30 min 120 or 277V
Power Pack
Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General
450
180° 4’ Self-Adjusting
Time Delay
Feature
Passive Infrared
Ceiling
720
Pattern Mounting Height (ft) Adjustment
Voltage
Passive Infrared
Wall Switch
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
GOOD
BEST BEST
Occupancy Sensor Application Guide Commercial Wall Switch Sensors
Commercial Low Voltage Ceiling Sensors
Commercial Line Voltage Ceiling Sensors
PIR1500-120-347
US1500-120 or 277
US2000-120 or 277
DT2000-120 or 277
OXC-P-2MH0-R
OXC-P-1500-R
ODC-U-0100-H
ODC-U-0501-H
OMC-DT-0701-R
OMC-DT-2000-R
OMC-U-2000
OMC-U-1001
OMC-U-0501
OMC-P-1200-R
OMC-P-0450-R
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-DMV-*
ONW-D-1001-MV-*
OSW-U-0721-24AC-R-*
OSW-U-0721-GERR7-*
Specification Grade
OSW-U-0721-SP-*
OSW-U-0721-MV-*
OSW-P-0451-D347-*
OSW-P-0451-347-*
OSW-P-0451-MV-*
OSW-P-0451-DMV-*
Commercial Grade
Specifications Technology
Passive Infrared
Ultrasonic
Dual Technology
Mounting Coverage (Sq ft)
450
1000
Ultrasonic
1200
347V
120 to 277V
Not Required
Photocell
10-30VDC
RR7 Relay
Required
RR7 Relay Required
Dual Technology
24 VAC Supply 24 VAC Required
120 to 277V
347
Environmental Operating Temperature/Humidity Available Colors
Not Required
Included
SP, 3-Way*, No Neutral Required
Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*, No Neutral Required
W, V Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*
SP
700
360° 8-12’
50 linear
10-30VDC
Required
RR7 Relay Required
24 VAC Required Not Included
SP, 3-Way*, Light Icon, EcoMeter
Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
Not Included
Internal OMC-U0501-R
Included
OMC-U1001-R
OMC-U2000-R
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
SP, 3-Way* Night Light
GOOD BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD GOOD GOOD GOOD GOOD
GOOD BETTER
GOOD
GOOD
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BEST BEST
BEST BEST
BEST BEST
BEST BEST
GOOD BETTER
GOOD BETTER
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BEST BETTER
BEST BETTER
BEST BEST
BEST BEST
BEST BEST
BEST BEST
BETTER BETTER
BETTER BETTER
BETTER BETTER
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD
BETTER GOOD BEST BEST
BETTER GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BEST BETTER GOOD BEST BEST
BETTER BEST BETTER GOOD BEST BEST
BEST
GOOD BETTER
GOOD BETTER
GOOD BETTER
BETTER GOOD GOOD
BETTER GOOD GOOD
BETTER GOOD GOOD
GOOD
BETTER
BETTER
BETTER
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
8-12’ Manual Adjustment
8-15’
120 to 347V
Not Required Internal ODC-U0051-R-H
Included
ODC-U0100-R-H
Not Included
Included
Internal
Not Included
-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing
32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing
W
W
Up to 5 sensors can be used per switchpack
No switchpack required
Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST
Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD
GOOD BEST
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BEST BETTER GOOD
BETTER BETTER BEST BEST BEST BEST BEST
BETTER
BETTER
BEST
BEST
BEST
BETTER
BEST BEST BEST
BEST BEST BEST
BETTER BETTER BETTER
GOOD BEST BETTER BEST BETTER GOOD
BEST
BEST
BETTER BETTER
BEST BEST
BEST
BEST
BETTER
BETTER
BEST BETTER BETTER
BEST BETTER BETTER
BEST BETTER BETTER
GOOD GOOD
BETTER GOOD GOOD
BEST BEST
GOOD GOOD
GOOD BETTER
BETTER BETTER
BEST BEST
BEST BEST BETTER
BETTER BETTER BEST
BETTER BETTER BETTER
BEST BEST BEST
BETTER
BEST
BEST
BETTER BETTER BETTER
BEST BETTER BETTER
BEST
GOOD BEST BEST
BEST
BETTER
BETTER
GOOD
GOOD BEST
GOOD
BEST BEST BETTER BETTER
GOOD GOOD GOOD
BEST BEST BETTER
BEST GOOD BEST BEST
GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
1500
15 sec to 30 min
BEST BEST BEST
2000
up to 25’ Self-Adjust
GOOD GOOD BETTER
BETTER BEST
2MHO
120 or 277V
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing
SP, Light Icon, EcoMeter
Passive Infrared
Ultrasonic
360°
Not Included
W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
1500
Required Internal
Commercial Wall Switch Sensors
BETTER BEST
Dual Technology
360° Manual Adjustment
15 sec to 30 min
Included
100 linear
180°
120 to 277V
W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode
2000
15 sec to 2 hr
32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode
1000 180°
RR7 Relay
Not Included
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A
Passive Infrared
Ceiling
10-30VDC
Internal
Not Included
Ultrasonic
Self-Adjust
Not Included
BAS/HVAC Relay
500
360°
15 sec to 30 min 120 or 277V
Power Pack
Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General
450
180° 4’ Self-Adjusting
Time Delay
Feature
Passive Infrared
Ceiling
720
Pattern Mounting Height (ft) Adjustment
Voltage
Passive Infrared
Wall Switch
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
GOOD
BEST BEST
Occupancy Sensor Application Guide Commercial Wall Switch Sensors
Commercial Low Voltage Ceiling Sensors
Commercial Line Voltage Ceiling Sensors
PIR1500-120-347
US1500-120 or 277
US2000-120 or 277
DT2000-120 or 277
OXC-P-2MH0-R
OXC-P-1500-R
ODC-U-0100-H
ODC-U-0501-H
OMC-DT-0701-R
OMC-DT-2000-R
OMC-U-2000
OMC-U-1001
OMC-U-0501
OMC-P-1200-R
OMC-P-0450-R
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-DMV-*
ONW-D-1001-MV-*
OSW-U-0721-24AC-R-*
OSW-U-0721-GERR7-*
Specification Grade
OSW-U-0721-SP-*
OSW-U-0721-MV-*
OSW-P-0451-D347-*
OSW-P-0451-347-*
OSW-P-0451-MV-*
OSW-P-0451-DMV-*
Commercial Grade
Specifications Technology
Passive Infrared
Ultrasonic
Dual Technology
Mounting Coverage (Sq ft)
450
1000
Ultrasonic
1200
347V
120 to 277V
Not Required
Photocell
10-30VDC
RR7 Relay
Required
RR7 Relay Required
Dual Technology
24 VAC Supply 24 VAC Required
120 to 277V
347
Environmental Operating Temperature/Humidity Available Colors
Not Required
Included
SP, 3-Way*, No Neutral Required
Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*, No Neutral Required
W, V Dual Relay, 3-Way*, No Neutral Required
SP, 3-Way*
SP
700
360° 8-12’
50 linear
10-30VDC
Required
RR7 Relay Required
24 VAC Required Not Included
SP, 3-Way*, Light Icon, EcoMeter
Dual Relay, 3-Way*, Light Icon, Fan Mode, EcoMeter
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
Not Included
Internal OMC-U0501-R
Included
OMC-U1001-R
OMC-U2000-R
SP, 3-Way*, No Neutral Required, Light Icon, EcoMeter
SP, 3-Way* Night Light
GOOD BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BEST BETTER BETTER BEST
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
BETTER BEST GOOD GOOD
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD BEST BETTER
GOOD GOOD GOOD GOOD GOOD GOOD
GOOD BETTER
GOOD
GOOD
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BEST BEST
BEST BEST
BEST BEST
BEST BEST
GOOD BETTER
GOOD BETTER
GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BETTER BETTER
BEST BETTER
BEST BETTER
BEST BEST
BEST BEST
BEST BEST
BEST BEST
BETTER BETTER
BETTER BETTER
BETTER BETTER
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD GOOD
GOOD
BETTER GOOD BEST BEST
BETTER GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BEST
GOOD BEST BEST
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BETTER BEST BETTER BETTER BETTER BETTER
BETTER BEST BETTER GOOD BEST BEST
BETTER BEST BETTER GOOD BEST BEST
BEST
GOOD BETTER
GOOD BETTER
GOOD BETTER
BETTER GOOD GOOD
BETTER GOOD GOOD
BETTER GOOD GOOD
GOOD
BETTER
BETTER
BETTER
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
8-12’ Manual Adjustment
8-15’
120 to 347V
Not Required Internal ODC-U0051-R-H
Included
ODC-U0100-R-H
Not Included
Included
Internal
Not Included
-40°F to 125°F (-40°C to 52°C) / less than 95%, non-condensing
32°F to 104°F (0°C to 40°C) / less than 95%, non-condensing
W
W
Up to 5 sensors can be used per switchpack
No switchpack required
Commercial Low Voltage Ceiling Sensors BETTER GOOD BEST BEST
Commercial Line Voltage Ceiling Sensors BEST GOOD BEST GOOD GOOD
GOOD BEST
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BETTER BEST BETTER BEST BETTER
BEST BETTER GOOD
BETTER BETTER BEST BEST BEST BEST BEST
BETTER
BETTER
BEST
BEST
BEST
BETTER
BEST BEST BEST
BEST BEST BEST
BETTER BETTER BETTER
GOOD BEST BETTER BEST BETTER GOOD
BEST
BEST
BETTER BETTER
BEST BEST
BEST
BEST
BETTER
BETTER
BEST BETTER BETTER
BEST BETTER BETTER
BEST BETTER BETTER
GOOD GOOD
BETTER GOOD GOOD
BEST BEST
GOOD GOOD
GOOD BETTER
BETTER BETTER
BEST BEST
BEST BEST BETTER
BETTER BETTER BEST
BETTER BETTER BETTER
BEST BEST BEST
BETTER
BEST
BEST
BETTER BETTER BETTER
BEST BETTER BETTER
BEST
GOOD BEST BEST
BEST
BETTER
BETTER
GOOD
GOOD BEST
GOOD
BEST BEST BETTER BETTER
GOOD GOOD GOOD
BEST BEST BETTER
BEST GOOD BEST BEST
GOOD BEST BEST
GOOD BEST BEST
BEST
GOOD
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out. SP: single pole Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
1500
15 sec to 30 min
BEST BEST BEST
2000
up to 25’ Self-Adjust
GOOD GOOD BETTER
BETTER BEST
2MHO
120 or 277V
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing
SP, Light Icon, EcoMeter
Passive Infrared
Ultrasonic
360°
Not Included
W, V, LA Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode, EcoMeter
1500
Required Internal
Commercial Wall Switch Sensors
BETTER BEST
Dual Technology
360° Manual Adjustment
15 sec to 30 min
Included
100 linear
180°
120 to 277V
W, V, LA, G, & B SP, 3-Way*, Dual Relay Light Icon Fan Mode
2000
15 sec to 2 hr
32°F - 104°F (0°C - 40°C) / Less than 95%, non-condensing
Dual Relay, 3-Way*, No Neutral Required, Light Icon, Fan Mode
1000 180°
RR7 Relay
Not Included
60°F - 80°F (15°C - 26°C) / Less than 95%, non-condensing W, V, A
Passive Infrared
Ceiling
10-30VDC
Internal
Not Included
Ultrasonic
Self-Adjust
Not Included
BAS/HVAC Relay
500
360°
15 sec to 30 min 120 or 277V
Power Pack
Applications Cafeteria Classroom Closet Utility Computer Room Conference Room Copy Room Day Care Center File Room Hallway Loading Dock Office Executive Office Home Office Open Office Private Office Space Office w/ cubicles Open Area Parking Garage Refrigerated Storage Residential Room Restroom Non-Partitioned Restroom Partitioned Restroom Residential Stairwell Storage Room Vending Room Warehouse Aisles Warehouse Open Work Space General
450
180° 4’ Self-Adjusting
Time Delay
Feature
Passive Infrared
Ceiling
720
Pattern Mounting Height (ft) Adjustment
Voltage
Passive Infrared
Wall Switch
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
GOOD
BEST BEST
Sensor Technologies Passive Infrared Relay (PIR) Technology • •
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Dual Technology • • •
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Self-Adaptive Technology • •
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
North America Headquarters 203 Cooper Circle Peachtree City, GA 30269
Service & Support Center 6 Green Tree Drive South Burlington, VT 05403
P: 800-553-3879 F: 800-954-7016
P: 800-553-3879 F: 800-954-7016
Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com
[email protected] www.coopercontrol.com
[email protected] As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.
LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •
Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.
Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com
ACC101050
Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.
Printed in USA
Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049
10/11
Greengate Occupancy Sensor Guide
Sensor Technologies Passive Infrared Relay (PIR) Technology • •
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Dual Technology • • •
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today. This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use. Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Self-Adaptive Technology • •
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
About Energy Codes Energy costs and consumption continue to rise in the United States. Today, many energy codes and energy policies either require or incentivize the use of energy efficient lighting controls on commercial projects. ASHRAE 99.1-1999, 2001, 2004, 2007 In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off. • Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the ASHRAE standard. • In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee cafeterias and break rooms.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
North America Headquarters 203 Cooper Circle Peachtree City, GA 30269
Service & Support Center 6 Green Tree Drive South Burlington, VT 05403
P: 800-553-3879 F: 800-954-7016
P: 800-553-3879 F: 800-954-7016
Cooper Controls Ltd Usk House, Lakeside, Llantarnam Park, Cwmbran, NP44 3HD. UK P: +44 (0)1923 495495 F: +44 (0)1923 867880 www.coopercontrol.com
[email protected] www.coopercontrol.com
[email protected] As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum. States have until 2010 to ensure that their building codes meet or exceed this standard.
LEED Green Building Rating System Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009. • Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
California Title 24 Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied: • • • •
Offices 250 sq ft or smaller Multipurpose rooms of less than 1000 sq ft Classrooms of any size Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices. Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC • ASHRAE and Title 24 requirements must be met. • IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Commercial Building Tax Deduction An incentive for building owners to adopt the most energy-efficient lighting control strategies with tax credit capped at 60¢ per square foot and was recently extended through December 31, 2013. Bi-level occupancy sensors can meet the bi-level switching requirements in the Commercial Tax Deduction. These occupancy sensors turn all of the lights in a space on to 50% when an occupant enters a room. Occupants can then manually turn the lights on to 100%, if they require maximum illumination.
Cooper Industries 600 Travis, Suite 5800 Houston, TX 77002 P: 713-209-8400 F: 713-209-8995 www.cooperindustries.com
ACC101050
Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, DemandKeeper, AnalogKeeper, IntelliRelay, NeoSwitch,TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.
Printed in USA
Canada 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-507-4000 F: 905-568-7049
10/11
Greengate Occupancy Sensor Guide