Rated Voltage Operating Voltage Range Current Frequency Trip Level Phase Response Time Dielectric Withstand Surge Withstand Let Go Line Voltage Grounded Neutral Detection Power Up
120V AC, 240V AC and 120/240V, 3Ø 250V AC, 3Ø 120/208V AC. 85% to 110%. Up to 30A or device rating. 60 Hz. 4-6 mA. Single. .025 sec. Max. 1500 VRMS across contact, 4000 VRMS between conductors and enclosure. 6000V impulse, 0.5 microseconds rise time 100kHz ringing frequency with 40% decay per cycle. 60% of rated. 6 Ohms or less. Manual or automatic reset.
3.37" (85.6)
4.80" (121.9)
2.82" (12.9)
Environmental Ratings
Housing Rating Construction Type Operating Temperature Leakage Current @ 93% Humidity
UL Type 4X. Industrial grade design. Class A GFCI. -35°C to 66°C, -30°F to 150°F. Zero.
.20 x 4
¾" N.P.T.
Dimensional Drawing
Features
Life (Endurance) Grounded Neutral Protection Power On Indicator Power Off Indicator Wiring Application Switch Interface Latching Mechanism
10,000 cycles (6000 with load and 4000 without load). Open neutral protection Trips upon loss of neutral. Trips if ground and neutral touch at load side. Green light on. Red blinking light plus optional audible alarm. 3 Wire Single Phase (Hot, Neutral and Ground), 4 Wire Single Phase (Line 1,Line 2, Neutral and Ground). Double Insulated. Electromagnetic.
2.64" (67.1)
5.75" (146.0)
Physical Specifications
Wire Leads Unit Color Label Color on Portable and Hard Wired Units Weight
#10 AWG, 24" long. Gray with black cover. Automatic reset: yellow background with black lettering. Manual reset: black background with yellow lettering. 1.40 lbs.
Related Code Confined Space Construction Sites Commercial Garages Fountains Spas and Hot Tubs Marinas
www.hubbell-wiring.com
24.00" (609.6)
OSHA 29 CFR 1926.404 (b) (1) (ii) OSHA 29 CFR 1926.405 (a) (2) (ii) (G) NEC 590.6 NEC 511.12 NEC 680.5B NEC 680.40 NEC 555.3