KL BI-PIN - Columbia Lighting

Report 7 Downloads 30 Views
KL BI-PIN

Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8 PROJECT INFORMATION Project Name

Type

Catalog No.

Date

CONSTRUCTION

FEATURES • • • • • • •

Available in 4' and 8' lengths Apertured reflectors have 15% uplight Spring loaded turret lampholders 6' lamp spacing For individual or continuous row mounting Channel ends double as joiners Full depth end closures available

Heavy steel housing with longitudinal reinforcing ribs for extra strength. Reflector die-embossed with transverse ribs for maximum rigidity. Solid top or 15% uplight versions with extruded openings available. FINISH

White painted parts are treated with a five stage phosphate bonding process and finished with a high reflectance baked enamel. LSR and M4R reflectors specular room side, Mill finish aluminum top surface. BALLASTS

Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated

ORDERING INFORMATION KL MODEL

SIZE 4 4' 8 8'

– NO. OF LAMPS IN CROSS SECTION 2 Two 3 Three 4 Four

ACCESSORIES (ORDER SEPARATELY) KZT Zip Tee Hanger - 1½" spacer on T-bar ceiling KTH Slide Clamp Tong Hanger S18 18" Stem, canopy and 8° aligner SS18 18", 45° Swivel Stem & Canopy KHC 24" Chain Hanging Assembly KLEC Full Depth End Closure KLWG4 Wire Guard 4' lg. - 2 required per 8' fixture OS1360K Occupancy/Daylight sensor kit, 120/277/347V, one relay, 360 Lens, snap on drop down adaptor, quick connect wiring1

ELECTRICAL

Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CECcompliant ballast disconnect is standard. CERTIFICATION

All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924.

EXAMPLE KL4-232-U-EU-GLR-PAF



KL Premium Industrial

A, unless otherwise specified. CEE NEMA Premium compliant.





LAMP TYPE

REFLECTOR TYPE

VOLTAGE

28 4', T5: 28 Watt 32 4', T8: 32, 30, 28 or 25 Watt 54 4', T5HO: 54 or 51 Watt

U Apertured Reflector for Uplight ST Solid Top (No Uplight) M4RST Solid Top Reflector with 95% Reflective Specular Silver Finish M4RU Apertured Reflector with 95% Reflective Silver Finish

U 120V-277V 347 347V

OPTIONS GLR GMF EL BC

Fast Blow Fuse Slow Blow Fuse Emergency Battery Pack Branch Circuit Plug-on Wiring System (See options section for details.) PAF Paint After Fabrication NYC NYC Compliant

BALLAST E Electronic T8, Instant Start 4E 4-Lamp Electronic T8, Instant Start EP Electronic, Program Start 4EP 4-Lamp Electronic, Program Start For others available, see Ballast Options.

Use programmed start ballast. Not recommended for use with instant start. For more occupancy/daylight harvesting sensor accessories see Technical section.

1

Page 1/2 Rev. 08/23/17 © 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

INDUSTRIALS / KL BI-PIN

KL BI-PIN

Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8

PHOTOMETRIC DATA

ZONAL LUMEN SUMMARY Zone

LUMINAIRE DATA

0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180

KL4-232-U KL Industrial 1' × 4' 2-Lamp Industrial with Apertured White Reflector R2P32 0.95 FO32/41K 2900 74 N/A 0º = 1.27  90º = 1.30 Length: 4.00 Width: 1.02 Height: 0.00

Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet

1090 1807 3314 4396 179 263 518 817 5212

18.8 31.1 57.1 75.8 3.1 4.5 8.9 14.1 89.9

ENERGY DATA

20.9 34.7 63.6 84.3 3.4 5.0 9.9 15.7 100.0

INDOOR CANDELA PLOT

RCR

70 94 85 77 71 65 60 55 51 48 45

80 50 30 90 86 78 71 68 60 60 52 53 45 48 39 43 35 39 31 36 28 33 26

10 82 66 54 46 39 34 30 26 23 21

70 90 81 74 67 62 57 53 49 46 43

70 50 30 86 83 75 69 65 58 58 50 51 44 46 38 42 34 38 31 35 28 32 25

10 79 64 53 45 38 33 29 26 23 21

50 80 69 60 53 48 43 39 35 33 30

50 30 77 64 55 47 41 36 32 29 26 24

10 74 61 50 42 36 32 28 25 22 20

89.9%

Luminaire Efficacy Rating (LER) IESNA RP-1-1993 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens

67 Non-Compliant $3.58 based on 3000 hrs. and $0.08 per KWH

AVG. LUMINANCE (Candela/Sq. M.)

COEFFICIENTS OF UTILIZATION (%) RC RW 1 2 3 4 5 6 7 8 9 10

Total Luminaire Efficiency

Average Luminance Angle

Luminaire

Test 10183 Test Date 1/8/03

Lumens % Lamp % Fixt.

0 0 62 51 42 36 31 27 24 21 19 17

0 30 40 45 50 55 60 65 70 75 80 85

0.0

22.5

45.0

67.5

90.0

3654 3616 3578 3544 3509 3459 3387 3296 3155 2956 2674 2149

3654 3622 3595 3582 3579 3569 3493 3477 3595 3374 3464 2967

3654 3671 3706 3712 3776 3923 3894 3652 3718 4210 3342 2876

3654 3726 3788 3921 4104 3905 3704 3839 4327 4353 2370 2785

3654 3717 3833 4000 4059 3827 3667 3964 4536 3955 2355 2815

RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance

DIMENSIONAL DATA

MOUNTING ACCESSORIES 9813/16" 887/8"

2"

2"

11/8" 15/16" 431/32"

4913/32"

NOTE: Fixtures with T5/T5HO lamping are 48" and 98" in length.

2"

497/16" 39½"

2"

15/16" 11/8" 39½" 431/32"

KHC

S18

43/16"

61/8" 35/8" 6" 133/8" KZT

KTH

A: 7/8" Diameter knockout B: .570" × .656" Strain Relief knockout E: 11/8" Diameter knockout NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.

Page 2/2 Rev. 08/23/17 © 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

INDUSTRIALS / KL BI-PIN