NETRUNNER™ High Capacity Vertical Managers INSTRUCTIONS CM392C © Panduit Corp. 2009
PART NUMBERS VERTICAL CABLE MANAGEMENT Front/Rear Front Only NRV6 NRV10 NRV12
NRVF6 NRVF10 NRVF12
Mounting Kits NRVCB NRVCB or WMPVSMK
Racks CMR19X47 CMR19X84S NFR84 CMR4P84D23 R4P R4P36
CMR19X84 CMR23X84 3” Deep R2P Series of 2 Post Racks CMR4P84 CMR4P84CN CMR4P84D23CN CMR4P84D23NU R4PCN R4P23 R4P36CN R4P42
Location Guide for Center Mounting (CMR19X84 with NRVCB) Dimensions in (...) parenthesis are for 10” Vertical Cable Management Dimensions in [...] brackets are for 12” Vertical Cable Management
12.5 TYP
Center of manager is forward approximately 0.9” from center of rack
3.00 TYP
16.00” = 19” RACK 20.00” = 23” RACK TYP
CMR19X84NU CMR4P84NU CMR4P84D23CNNU R4P23CN R4P42CN
NRD6 NRD10 NRD12
Bracket Installation
1
6.75 (10.0) [12.0]
20.25” = 19” RACK 24.25” = 23” RACK TYP
1.25 TYP
Doors
11.00 (14.25) [16.25]
Center of rack
Note: When installing between two racks use part number NRVCB for the additional brackets required. Bracket is keyed to be installed in the correct orientation.
2.12 TYP
Standard Rack Installation Note: Cable retainers must point upward
2
4
Mounting Orientation #12-24 Screws
3 #12-24 Screws
Bottom Mounting Location
Location pin(s)
Top Mounting Location
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp Page 1 of 2
INSTRUCTIONS CM392C 4
4-Post Rack Installation using Brackets. Note: Step 1 is the same as for the Standard Rack. 2
#12-24 Screws
Tapped Mounting Holes
Back of Post Mounting Bracket Bottom half of Manager
Top Half of Manager
#12-24 Screws
3
4 Places
Location pin(s) Installation Instructions NFR84 and 4-Post Racks using WMPVSMK side mounting kit
3
Note: Mount the racks to the floor. 1
Location pin(s)
2
3/8 Bolt, Lock Washer & Nut
3/8 Bolt, Lock Washer & Nut
Top Latch Buttons
Opening and Closing Cover Door Finger Door Latches Tabs
Wire Retainer Installation (WR5E)
To open, grasp back of door and push top button with thumb. Repeat with bottom button.
Bottom Latch Buttons Installation Line up finger tabs with door latches. Then squeeze door and fingers together to engage (4 places).
To close, grasp cable retainers and door until latched
Removal To remove door, press bottom latches first, then press top latch bottons while holding door
For instuctions in Local Languages and Technical Support: www.panduit.com/resources/install_maintain.asp
www.panduit.com Page 2 of 2
Use thumb to release wire retainer for removal
E-mail:
[email protected] Fax: (708)444-6448