Specification Sheet

Report 13 Downloads 117 Views
IA18

IA18

NEER® Grounding Fittings

Ground Clamps Type GC Bronze Use: Ground clamps for bare copper conductor. Can be used on water pipes, conduits, or pipe electrodes. Made of cast bronze alloy. For insulated or bare conductor wire, copper AWG #2 through #10. Clamp is reversible.

Trade Size Catalog (inches) Number 1 ⁄2-1 11⁄4-2 21⁄2-4 41⁄2-6

GC-1Z GC-2 GC-4 GC-6

Dimensions in Inches

A

B

C

2.28 3.62 6.38 8.50

0.33 0.33 0.33 0.30

0.70-1.89 1.38-2.97 2.73-5.94 2.66-7.75

Material/Finish: Bronze Steel Screws – Zinc Plated

Type GC-1Z

Third Party Certification: UL Listed: E37337

Applicable Third Party Standards: UL Standard: 467 NEMA: FB-1 Fed. Spec: W-F-406D, Type 5, Class 7, Style S

Type GC Zinc Use: Ground clamps for bare copper conductor. For insulated or bare conductor wire, copper AWG #2 through #8. Clamp is reversible.

Trade Size Catalog (inches) Number ⁄2-1 ⁄2-1

1 1

Dimensions in Inches

A

B

GC-5 2.24 0.33 GC-5B 2.24 0.33

C

0.54-1.61 0.54-1.61

Material/Finish: GC-5 Casting—Zinc Die Cast Screws—Steel

Type GC-5

Material/Finish: GC-5B Casting—Zinc Die Cast with Brass Plating Screws—Steel Third Party Certification: UL Listed: E37337 CSA Certified: 014489

Applicable Third Party Standards: UL Standard: 467 CSA Standard: C22.2 No. 18 NEMA: FB-1 Fed. Spec: W-F-406D, Type 5, Class 7, Style S

Effective December, 2007 Copyright 2007

Note: GC-5 is listed for use with 1⁄2” through 1” trade size copper water pipe, steel galvanized water pipe and metal gas pipe. UL requires the UL logo be removed on our GC-5B because we provide plating of a material or color different from natural zinc.

800-621-1506 www.o-zgedney.com

IA19

IA19

NEER® Grounding Fittings

Ground Clamps Type GC Direct Burial

Trade Size Catalog (inches) Number ⁄2-1

1

GC-1-DB

Dimensions in Inches

A

B

C

2.28 0.32 0.70-1.87

Use: Ground clamp for bare copper conductor. Can be used on water pipes, conduits or pipe electrodes. Suitable for direct burial in earth and concrete. Material/Finish: Bronze clamps and screws Third Party Certification: UL Listed: E37337

Type GC-1-DB

Applicable Third Party Standards: UL Standard: 467 NEMA: FB-1 Fed. Spec: W-F-406D, Type 5, Class 7, Style S

Type RC Rod – Direct Burial

Trade Size (inches)

⁄2 ⁄8 ⁄4

1 5

Use: To terminate bare copper conductor directly to ground rod. Suitable for direct burial applications.

3

Catalog Number RC-500 RC-625 RC-750

Dimensions in Inches

A

B

1.30 1.48 1.63

0.87 0.98 0.97

Wire Size Min. Max. 10 SOL 8SOL 8SOL

2 STR 1/0 STR 1/0 STR

Material/Finish: Bronze clamp and screw Third Party Certification: UL Listed: E37337

Type RC-500

Applicable Third Party Standards: UL Standard: 467 CSA Standard: C22.2 No. 18 NEMA: FB-1 Fed. Spec: W-F-406D, Type 5, Class 7, Style S

Effective December, 2007 Copyright 2007

800-621-1506 www.o-zgedney.com