Split System Submittal Data

Report 3 Downloads 78 Views
Print Form

Multi/Split System Submittal Data CLM1972 Flexi Multi Inverter Type Heat Pump

Job Name: Location: Engineer: Submitted to: Submitted by: Reference:

Power Circuit Ampacity Fuse Size, Max. Compressor No. used R.L. Amps - L.R. Crankcase Heater

Approval: Date: Construction: Unit #: Drawing #:

General Data (at 230V) V/P/Hz 230/1/60 (A) 15 (A) 20 DC Twin Rotary 1 6.0 - 13 30

(A) (W)

Outdoor Unit Fan type Dia. (in.) - No. Speeds Type Drive - No. Speeds No. Poles No. Motors CFM F.L. Amps

(RPM) (W) (High) (A)

Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size

Aluminum Fin & Copper Pipe Corrugated Plate - Inner Riffeled 2 - 18.1 (sq.ft.) 6.4 (in.) 3/8”

Propeller D18-1/8 - 1 DC Motor 8 - 750 90 - 1 1707 0.45

Performance Data @ ARI Standard Conditions (230V) Cooling (BTU/H) 19,700 (9,800-19,700) Total Capacity (BTU/H) 16,800 Sensible Capacity (BTU/H) 2,900 Latent Capacity 16.5 SEER (A) 7 Amps (A) 13 Max. Amps (W) 1,570 Power Inputs (W) 3,000 Max. Inputs (dB-A) 50 Outdoor Sound Rating Operating Range

R410A Refrigerant 6.17 Lbs. - R410A (outdoor unit) Electric Expansion Valve Control (in. O.D. Discharge) 1/4”Flare) Line Size (in. O.D. Discharge) 3/8” (Flare) Line Size

Indoor Air Intake Temp.

Cooling

Minimum

Heating Dimensions Outdoor Unit

Weight Net Shipping

Shipping Volume

(in.) (Uncrated) (Crated)

HxWxD 29-1/8 x 35-7/16 x 12-19/32 33-27/32 x 40-5/8 x 16-1/4

(lbs.) (lbs.)

Outdoor 138.9 147.7

(cu.ft.)

Outdoor 12.71

Maximum

Maximum Minimum

Outdoor Air Intake Temp.

95F DB/71F WB 115F DB 67F DB/57F WB 23F DB w/KMS0772, KMS0972, KMS1272 32F DB w/KMS1892, KMS2472 Indoor Air Intake Temp.

Outdoor Air Intake Temp.

80F DB/67F WB -

75F DB/65F WB 0F DB

Dimensions

Sanyo Commercial Solutions A Division of SANYO North America 1300 Michael Drive Wood Dale, IL 60191 USA www.sanyohvac.com