Split System Submittal Data

Report 0 Downloads 63 Views
Print Form

Split System Submittal Data System: 12XS71

Indoor/Outdoor: XS1271/C1271 Grille: PNR-XS1872 Ceiling Recessed Air Conditioner

Job Name: Location: Engineer: Submitted to: Submitted by: Reference:

Power Circuit Ampacity Fuse Size, Max. Compressor No. used R.L. Amps - L.R.

Approval: Date: Construction: Unit #: Drawing #:

General Data (at 115V) V/PH/Hz 115/1/60 (A) 20 (A) 20 DC Rotary Inverter (A)

1 12.6-20

Outdoor Unit Fan type Dia. (in.) - No. Speeds Type Drive - No. Speeds No. Poles No. Motors CFM F.L. Amps

(RPM) (W) (HIGH)) (A)

Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size

Aluminum Fin and Copper Pipe Corrugated Plate-Inner Rifed 2-18.1 (sq.ft.)) 3.95 (in.) 5/16”

Indoor Unit Fan type Dia. & Length (in.) - No. Speeds No. Speeds (RPM, High)) No. Poles (W) No. Motors (Hi/Med/Low) CFM Indoor Sound Rating F.L. Amps Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size Drain Connection Size

(Hi) (dB-A) (A)

Propeller 15-3/4-1 DC Motor 8-750 50-1 1059 0.6

Turbo 12-5/8/5-3/4-1 3+Auto 8-470 30-1 235/206/194 34 .346

Aluminum Plate Fin & Copper Tube Slit Plate & Inner Rifed 2-18.1 (sq.ft.)) 2.94 (in.) 9-32” (in.) 23/32”

Refrigerant R410A Lbs. - R410a (outdoor unit) 2.43 Electric Expansion Valve Control Flare Connection 65 Line Length, Max (ft.) 23 Lift Difference, Max (ft.) Line Size (in O.D. Dishcharge) 1/4” Line Size (in O.D. Suction) 3/8” Dimensions Indoor Unit Outdoor Unit

(in.) HxWxD (uncrated) 12-5/16 x 24-19/32 x 24-19/32 (crated) 11-13/32 x 24-13/16 x 28-1/8 (uncrated) 21-9/16 x 28-11/32 x 10-1/16 (crated) 23-5/8 x 33-11/16 x 14-1/4

Weight Net Shipping

Indoor (lbs.) 35.3 (lbs.) 41.9

Shipping Volume

(cu.ft.) 4.59

Outdoor 77.2 83.8

6.35

Performance Data @ ARI Standard Conditions (115V) Cooling Total Capacity (BTU/H) 11,900 (3,000-11,900) Sensible Capacity (BTU/H) 7,200 Latent Capacity (BTU/H) 4,700 SEER 16 Dehumidification (Pints/H) 4.26 (A) 12.6 (2.5-12.6) Amps (W) 1260 (250-1260) Power Inputs Outdoor Sound Rating (dB-A) 47

Dimensions Features Controls Microprocessor Remote Controller LCD Wireless Type, Temp. Sensor Built In Temperature Control IC Thermostat Timer 24 Hr Program; 1HR ON/OFF Night Setback Built-In Air Louver Automatic Power Failure Automatic Restart Built-In Built-In Self-Diagnosis Washable, Anti-Mold Air Filter Quiet Operation Built-In

Options Refrigerant Line Set Fresh Air Intake Airduct Extension Condensate Drain Pump Hard Wired Remote Controller Non-Removeable Locking Remo-con Bracket

Available Knock-out N/A Standard Available Available

Operating Range

Cooling

Indoor Air Intake Temp.

Outdoor Air Intake Temp.

95F DB/71F WB 67F DB/57F WB

Maximum Minimum

115F DB 50F DB

Outdoor Unit CH1271

1-9/32

25/32

2-3/4

5-9/16

7-23/32

2-3/32

1-27/32

1-3/32

2

16 5/ :1 ID

12-7/16

11-13/32

4-

32 3/ :2 ID

10-7/16 (265)

3-19/32

7-11/16

2

2

2 1

Narrow tube service valve dia.1/4" (6.35)

The length of the suspension bolts should be selected so that there is a gap of 1-3/16" or the ceiling (21/32" or more below the lower surface of the main unit), as shown in the figure at right. If the suspension bolts is too long, it will contact the ceiling panel and the unit cannot be installed.

2-5/32

3

24-19/32 (625) 14-3/32 (358)

Wide tube service valve dia.3/8" (9.52)

2-1/8

4-9/32

6

28-11/32 (720)

21-9/16 (548)

Less than 31/32

5

8-15/32

1-25/32 4-19/32 1-25/32

3-5/8

Less than 31/32

A View

5/8

22-5/8 (575) 2-3/32 6-5/16 6-11/16

22-5/8 (575)

8

15/32

1-3/16

Fresh air intake duct connection port (dia. 3-7/8")

4-29/32

3-19/32

3-1/8 21/32

Suspension bolt hole (4 - 1/2" x 1-1/8" hole)

13-5/32 (334)

Power supply port

24-19/32 (625)

Drain tube connection port VP20 (outer dia. 1")

12-7/8

Refrigerant tubing (gas tube) dia. 1/2" (flared)

12-7/16 21-1/32 (534) Suspension bolt pitch 23-5/8 (600) Ceiling opening dimensions

7

Refrigerant tubing (liquid tube) dia. 1/4" (flared)

21-3/16

10-13/16

1-3/16 (30)

Discharge outlet

Center of panel

11-5/32 (283)

Air intake

XHS1271 & PNR-XS1872 XHS1872 & PNR-XS1872

1 2 3 4 5 6 7 8

3. DIMENSIONAL DATA

Indoor Unit

A

23-5/8 (600) Ceiling opening dimensions 21-1/32 (534) Suspension bolt pitch

6-3/32

Unit : inch (mm) (852-0-0010-12700-0)

18