Submittal - Cloudinary

Report 0 Downloads 160 Views
Submittal

C 132

Pump Sequencer 132

01/11 Multi-Staging

Job ___________________________

Replaces: New

Contact_ _______________________

Designer_ ______________________

The Pump Sequencer 132 is designed to operate 2 pumps by providing stand by or staging operation. It can be used in a wide range of applications, including residential installations using a backup system pump to commercial applications that require energizing a second stage for increased flow or head. The main function of the 132 is to provide lead lag capability to a standby pump setup, or to provide staging capability for a dual pump installation. The 132 can energize up to 2 pumps, as well as provide alert contacts that can be used in the event of a failure.

Front View

Side View 2-Stage 30 second delay Exercising Alarm per Pump

Pump 12 Auto

Power

70°F 48

2-Stage Demand

Clear Alarm

Pump 

Alarm A

Pump 2

Alarm B

168 12

Off WWSD

6–5/8” (170 mm)

144

100 35

7/8” (23 mm)

CL

CL

96 hours

Pump Demand

Flow Proof

1/2” (13 mm)

Alarm Levels Off 10 second delay

Off Stand-by

WWSD

Mounting Base

Off

Frequency of Rotation

off red red

not testing testing testing paused

Test Made in Canada by tekmar Control Systems Ltd. Power: 120 V ±10% 60 Hz 6 VA Pump Relays: 240 V (ac) 10 A 1/2 hp, pilot duty 720 VA Alarm Relays: 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA Demands: 20 to 260 V (ac) 2 VA

Pump Sequencer 132 Stand-by / 2-Stage

58033

 2 3 4 5 6

7 8 9 0  2

Pump Demand

Pump 1 1

2-Stage Demand

Flow Proof

Pump 2 2

Power L

N

3 4 5 6 Alarm A A

Alarm B B

7 8 Outdoor Sensor

Signal wiring must be rated at least 300 V

H1197B

Do not apply power

Use supply wires suitable for 120°F (50°C) above ambient

1/2” (14 mm) 1–7/8” (49 mm) 7–9/16” (193 mm)

2–13/16” (72 mm)

Ø 3/16” (5 mm)

1/2” Knock-out (x 5 back) (x 5 bottom)

Specifications------------------------------------------------------ Energy Saving Features-----------• Warm Weather Shut Down

Pump Sequencer 132 Stand-by / 2-Stage Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Pump relays Alert relays Demands Sensors –Optional Warranty

D132, A132, D001 Microprocessor control. This is not a safety (limit) control 2.9 lb. (1320 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 120°F (0 to 50°C), RH ≤90% Non-condensing 120 V ±10%, 50/60 Hz, 6 VA 240 V (ac) 10 A 1/2 hp 240 V (ac) 10 A 1/3 hp 20 to 260 V (ac) 2 VA NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 Limited 3 Year (See D132 for full warranty)

Additional Features---------------• • • • • • • •

Equal Run Time Rotation Lead lag operation 2 Stage capability Exercising Alert per pump or alert levels Adjustable flow proof delay Test sequence CSA C US certified (approved to applicable UL standards)

Special requirements N/A

www.tekmarcontrols.com

 of 2

© 2011

C 132 - 01/11

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

132 070 S1

Alert 120 V (ac)

F1

P1

P2

Sample Electrical diagram Legend: D1 = Pump Demand F1 = Flow Switch P1 = Pump 1 P2 = Pump 2 A1 = Alert 1 A2 = Alert 2 S1 = Outdoor Sensor

2-Stage 30 second delay Exercising Alert per Pump

Pump 12 Auto

Power

Alert Levels Off 10 second delay

Off Stand-by

WWSD

70°F

96 hours

Pump Demand

48

2-Stage Demand Flow Proof

35

2-Stage 30 Second Delay Exercising Alert per Pump Alert Levels Off 10 Second Delay

Pump 1 2 Auto

Off Stand-by

Clear Alert

Pump 1

Alert A

Pump 2

Alert B

168 12

Off WWSD

DIP Setting

144

100

Off

Frequency of Rotation

off red red

not testing testing testing paused

Test Made in Canada by tekmar Control Systems Ltd. Power: Pump Relays: Al Relays: Demands:

Pump Sequencer 132 Stand-by / 2-Stage

158033

120 V ±10% 60 Hz 6 VA 240 V (ac) 10 A 1/2 hp, pilot duty 720 VA 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA 20 to 260 V (ac) 2 VA

Use supply wires suitable for 120°F (50°C) above ambient

1 2 3 4 5 6

7 8 9 10 11 12

Pump Demand

Pump 1 1

2-Stage Demand

Flow Proof

Pump 2 2

Power L

N

13 14 15 16 Alert A A

17 18

Alert B B

Outdoor Sensor

Signal wiring must be rated at least 300 V

H1197B

Do not apply power

= Required = Optional

S1 D1

120 V (ac)

F1

P1

P2

A1

A2

L N

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 132 - 01/11.