Submittal
C 132
Pump Sequencer 132
01/11 Multi-Staging
Job ___________________________
Replaces: New
Contact_ _______________________
Designer_ ______________________
The Pump Sequencer 132 is designed to operate 2 pumps by providing stand by or staging operation. It can be used in a wide range of applications, including residential installations using a backup system pump to commercial applications that require energizing a second stage for increased flow or head. The main function of the 132 is to provide lead lag capability to a standby pump setup, or to provide staging capability for a dual pump installation. The 132 can energize up to 2 pumps, as well as provide alert contacts that can be used in the event of a failure.
Front View
Side View 2-Stage 30 second delay Exercising Alarm per Pump
Pump 12 Auto
Power
70°F 48
2-Stage Demand
Clear Alarm
Pump
Alarm A
Pump 2
Alarm B
168 12
Off WWSD
6–5/8” (170 mm)
144
100 35
7/8” (23 mm)
CL
CL
96 hours
Pump Demand
Flow Proof
1/2” (13 mm)
Alarm Levels Off 10 second delay
Off Stand-by
WWSD
Mounting Base
Off
Frequency of Rotation
off red red
not testing testing testing paused
Test Made in Canada by tekmar Control Systems Ltd. Power: 120 V ±10% 60 Hz 6 VA Pump Relays: 240 V (ac) 10 A 1/2 hp, pilot duty 720 VA Alarm Relays: 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA Demands: 20 to 260 V (ac) 2 VA
Pump Sequencer 132 Stand-by / 2-Stage
58033
2 3 4 5 6
7 8 9 0 2
Pump Demand
Pump 1 1
2-Stage Demand
Flow Proof
Pump 2 2
Power L
N
3 4 5 6 Alarm A A
Alarm B B
7 8 Outdoor Sensor
Signal wiring must be rated at least 300 V
H1197B
Do not apply power
Use supply wires suitable for 120°F (50°C) above ambient
1/2” (14 mm) 1–7/8” (49 mm) 7–9/16” (193 mm)
2–13/16” (72 mm)
Ø 3/16” (5 mm)
1/2” Knock-out (x 5 back) (x 5 bottom)
Specifications------------------------------------------------------ Energy Saving Features-----------• Warm Weather Shut Down
Pump Sequencer 132 Stand-by / 2-Stage Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Pump relays Alert relays Demands Sensors –Optional Warranty
D132, A132, D001 Microprocessor control. This is not a safety (limit) control 2.9 lb. (1320 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 120°F (0 to 50°C), RH ≤90% Non-condensing 120 V ±10%, 50/60 Hz, 6 VA 240 V (ac) 10 A 1/2 hp 240 V (ac) 10 A 1/3 hp 20 to 260 V (ac) 2 VA NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 Limited 3 Year (See D132 for full warranty)
Additional Features---------------• • • • • • • •
Equal Run Time Rotation Lead lag operation 2 Stage capability Exercising Alert per pump or alert levels Adjustable flow proof delay Test sequence CSA C US certified (approved to applicable UL standards)
Special requirements N/A
www.tekmarcontrols.com
of 2
© 2011
C 132 - 01/11
Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram
132 070 S1
Alert 120 V (ac)
F1
P1
P2
Sample Electrical diagram Legend: D1 = Pump Demand F1 = Flow Switch P1 = Pump 1 P2 = Pump 2 A1 = Alert 1 A2 = Alert 2 S1 = Outdoor Sensor
2-Stage 30 second delay Exercising Alert per Pump
Pump 12 Auto
Power
Alert Levels Off 10 second delay
Off Stand-by
WWSD
70°F
96 hours
Pump Demand
48
2-Stage Demand Flow Proof
35
2-Stage 30 Second Delay Exercising Alert per Pump Alert Levels Off 10 Second Delay
Pump 1 2 Auto
Off Stand-by
Clear Alert
Pump 1
Alert A
Pump 2
Alert B
168 12
Off WWSD
DIP Setting
144
100
Off
Frequency of Rotation
off red red
not testing testing testing paused
Test Made in Canada by tekmar Control Systems Ltd. Power: Pump Relays: Al Relays: Demands:
Pump Sequencer 132 Stand-by / 2-Stage
158033
120 V ±10% 60 Hz 6 VA 240 V (ac) 10 A 1/2 hp, pilot duty 720 VA 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA 20 to 260 V (ac) 2 VA
Use supply wires suitable for 120°F (50°C) above ambient
1 2 3 4 5 6
7 8 9 10 11 12
Pump Demand
Pump 1 1
2-Stage Demand
Flow Proof
Pump 2 2
Power L
N
13 14 15 16 Alert A A
17 18
Alert B B
Outdoor Sensor
Signal wiring must be rated at least 300 V
H1197B
Do not apply power
= Required = Optional
S1 D1
120 V (ac)
F1
P1
P2
A1
A2
L N
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
2 of 2
All specifications are subject to change without notice. Printed in Canada. C 132 - 01/11.