Data sheet
Surge arrester MVR..G5
Technical data Surge arresters with metal oxide resistors without spark gaps (MO surge arresters), direct molded PUR housing, green color, designed and tested with reference to IEC 60099-4. Nominal discharge current I n 8/20 µs
5 kA peak
High current impulse I hc 4/10 µs
65 kA peak
Long duration current impulse
250 A / 1000 µs
Short circuit rating I s
not specified
The thermal stability of the MO surge arrester is proved in the operating duty test with a high current impulse, which gives an energy input of 2.0 kJ/kV (Uc).
----
Overvoltage protection of Installations Equipment Rotating machines Cable sheaths Application Alternating current (AC) Outdoor and indoor
General data Ambient air temperature
-40 to +40 °C (for higher
values contact manufacturer) Altitude
up to 1800 m (for higher
values contact manufacturer) Frequency of system voltage
16.7/50/60 Hz
Electrical data
Uc
Ur
Continuous
Rated
operating
voltage
Residual voltage U res in kV peak at specified impulse current
voltage wave 1/…µs
wave 8/20 μs
kV
kV
5 kA
0.5 kA
1.0 kA
2.5 kA
rms
rms
peak
peak
peak
peak
1.0
1.25
4.2
2.9
3.0
3.2
1.8
2.25
6.9
5.1
5.3
5.6
3.0
3.75
11.2
8.5
8.8
3.6
4.50
13.3
10.2
4.8
6.00
17.5
6.0
7.50
6.6
8.30
2 MVR..G5 | Surge arrester
wave 30/60 μs 10 kA
125 A
250 A
500 A
peak
peak
peak
peak
3.4
3.5
2.7
2.7
2.8
5.9
6.2
4.7
4.8
5.0
9.3
9.8
10.3
7.7
8.0
8.3
10.6
11.2
11.8
12.4
9.3
9.6
10.0
13.6
14.1
14.9
15.6
16.5
12.3
12.8
13.2
21.8
16.9
17.6
18.6
19.5
20.6
15.4
15.9
16.5
23.9
18.7
19.3
20.5
21.5
22.7
17.0
17.5
18.2
5 kA peak
Housing
Uc
Creepage Flashover Height
Height
Weight
Insulation withstand voltage of empty housing
Recommended
Continuous
d istance
K
kg
1.2/50 μs
minimum clearances
d istance
H
50 Hz wet
operating
required
guaranteed
required
voltage
values
values
acc. to IEC
acc. to IEC
guaranteed E min
Fmin
kV rms
mm
mm
mm
mm
kg
kV peak
kV peak
kV rms
kV rms
mm
mm
1.0
110
95
106
86
0.54
5
20
3
8
65
125
1.8
128
114
125
105
0.85
9
27
4
11
65
125
3.0
128
114
125
105
0.90
14
27
7
11
65
125
3.6
140
129
143
123
1.10
17
34
8
14
65
125
4.8
140
129
143
123
1.15
22
34
10
14
65
125
6.0
155
145
162
142
1.35
27
42
13
17
77
125
6.6
155
145
162
142
1.40
30
42
14
17
83
125
Dimensions (mm)
Standard dimensions without accessories (may be subject to changes) Dimensions according outline drawing HAMM480705 Outline drawings with accessories on request
Structure of type designation
MVR 1.8 G5
Type of arrester Uc = Continuous operating voltage Housing size Nominal discharge current I n
Surge arrester | MVR..G5 3
ABB Switzerland Ltd High Voltage Products Surge Arresters Jurastrasse 45 CH-5430 Wettingen/Switzerland Tel. +41 58 585 29 11 Fax +41 58 585 55 70 E-mail:
[email protected] www.abb.com/arrestersonline For detailed information regarding the dimensioning of our products see the following ABB documents: – Application guidelines Overvoltage protection Metal oxide surge arresters in medium voltage systems – Application guidelines Overvoltage protection Metal oxide surge arresters in railway facilities For pdf or print version please send E-mail to:
[email protected] Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders the a greed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright © 2013 ABB All rights reserved
Our products are certified according ISO 9001, 14001, 18001 and IRIS
1HC0093990 E01 AB