Surge arrester MVR..K5

Report 18 Downloads 232 Views
Data sheet

Surge arrester MVR..K5

Technical data Surge arresters with metal oxide resistors without spark gaps (MO surge arresters), direct molded PUR housing, green color, designed and tested with reference to IEC 60099-4.

---

Overvoltage protection of Installations Equipment Rotating machines Cable sheaths Application Alternating current (AC) and direct current (DC) Outdoor and indoor

Nominal discharge current I n 8/20 µs

5 kA peak

High current impulse I hc 4/10 µs

65 kA peak

Long duration current impulse

250 A / 1000 µs

Short circuit rating I s

not specified

The thermal stability of the MO surge arrester is proved in the operating duty test with a high current impulse, which gives an energy input of 2,0 kJ/kV (Uc, AC). General data Ambient air temperature

-40 to +40 °C (for higher

values contact manufacturer) Altitude

up to 1800 m (for higher

values contact manufacturer) Frequency of system voltage

16.7/50/60 Hz and DC

Electrical data

Residual voltage U res in kV peak at specified impulse current

Uc

Uc

Continuous

Continuous

operating

operating

voltage AC

voltage DC wave 1/…

wave 8/20 μs

kV

kV

5 kA

0.5 kA

1.0 kA

2.5 kA

rms

DC

peak

peak

peak

peak

0.44

0.56

1.85

1.32

1.36

1.44

0.66

0.84

2.67

1.96

2.04

2.16

0.80

1.02

3.19

2.38

2.47

2.61

2  MVR..K5 | Surge arrester

wave 30/60 μs 10 kA

125 A

250 A

500 A

peak

peak

peak

peak

1.52

1.60

1.20

1.24

1.28

2.26

2.39

1.79

1.85

1.92

2.74

2.90

2.17

2.24

2.32

5 kA peak

Housing

Uc

Uc

Creepage Flashover Weight

Continuous

Continuous

­d istance

­d istance

operating

operating

voltage AC

voltage DC

kV rms

kV DC

mm

mm

kg

0.44

0.56

83

83

0.21

0.66

0.84

83

83

0.21

0.80

1.02

83

83

0.21



Dimensions (mm)

Standard dimensions without accessories (may be subject to changes) Dimensions according outline drawing 1HC0009058 Outline drawings with accessories on request

Structure of type designation

MVR 0.44 K5

Type of arrester Uc = Continuous operating voltage AC Housing size Nominal discharge current I n

Surge arrester | MVR..K5 3

ABB Switzerland Ltd High Voltage Products Surge Arresters Jurastrasse 45 CH-5430 Wettingen/Switzerland Tel. +41 58 585 29 11 Fax +41 58 585 55 70 E-mail: [email protected] www.abb.com/arrestersonline For detailed information regarding the dimensioning of our products see the following ABB documents: – Application guidelines Overvoltage protection Metal oxide surge arresters in medium voltage systems – Application guidelines Overvoltage protection Metal oxide surge arresters in railway facilities For pdf or print version please send E-mail to: [email protected]

Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders the ­a greed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and ­illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright © 2013 ABB All rights reserved

Our products are certified according ISO 9001, 14001, 18001 and IRIS

1HC0076311 E01 AB

For further information please contact: