Washington Metropolitan Area Transit Authority

Report 16 Downloads 643 Views
DRAWING TYPE

Washington Metropolitan Area Transit Authority CONTRACTOR DRAWING/MATERIAL SUBMITTALS

CONTRACTOR:

Potomac Construction Co., Inc. 4701 Lydell Road Hyattsville, MD 20781

A-

OA - Outline Dimensions

B-

Cross Section and Parts List

CDEFGLEPRS-

Catalog Cut Performance Data Wiring Diagram Shop Details Priced Rec. Spare Parts Data Sheet Equipment Manual Print Reproducible Samples *

ATTENTION: Mr. M Magnussen

APPROVAL CODE

600 5th Street, NW#4A-12 Washington DC 20001 CONTRACT NO.

SUB/CONTRACTOR

FQ9194

POTOMAC

1-

Approved

2-

Approved as Corrected

3-

Disapproved

SUMITTAL NO.

DATE

FQ9194-S433-B95-01

05/12/2016

FIELD OFFICE DESIGNATION

NAME

INITIAL DATE

REVIEW ASSIGNMENT:

Project Description: Rehabilitation of Rail Yard Facilities(Yard 1)

Resubmittal not Required Resubmittal Required

ITEM

CONTRACTOR NUMBER

DATE

WMATA CONTRACTOR PRINT NO.

REV.

TITLE

1

201304

05/12/2016

FQ9194-S433-B95

01

MECH (15513) Boilers (B95) (01)

TYPE 1-e copy

COMMENTS TO CONTRACTOR:

DATE:

05/12/2016

PROJECT MANAGER:

Sachin Shah

APPR’VL

WASHINGTON METROPOLITAN AREA TRANSIT AUTHORITY

METRO REHABILITATION OF RAIL YARD FACILITIES CONTRACT: YARD 1- FQ9194

MECH (15513) Boilers (B95) (01) Location: Brentwood S&I (B95) Specifications Section: 15513 Submission Date: May 12, 2016 Subcontractor: Limbach

Potomac Construction Co., Inc. 4701 Lydell Rd Hyattsville, MD 20781

POTOMAC CONSTRUCTION CO., INC. 4701 LYDELL ROAD HYATTSVILLE, MD 20781 Phone: (301) 386-3030 Fax: (301) 386-1994

QA/QC MANAGER’S STATEMENT OF COMPLAINCE

Potomac Construction Company Inc.’s quality control manager hereby ensures that all the items required for the submittal below have been submitted for review.

PROCORE Submittal # :

FQ9194-S433-B95-01

CPM Submittal # :

B95-S0503 and B95-S0508

5/12/2016 John Georgy QA/QC Manager

Date

Page 1 of 1

SOP5003/09232014/REV00

POTOMAC CONSTRUCTION CO., INC. 4701 LYDELL ROAD HYATTSVILLE, MD 20781 Phone: (301) 386-3030 Fax: (301) 386-1994 YARD 1 FQ9194 Material Submittal Checklist Job Location

Brentwood Yard Service & Inspection Shop (B95)

Applicable Task

DB-05

15513 - Condensing Boilers

Pay App. Activity #

Spec. Para. Sub Type Section

For

In This Submittal

Close Date

B95-S0503

15513

2.2

Boiler-1 & Boiler-2

X

5/12/2016

B95-S0508

15513

2.5

Boiler-1 & Boiler-2

X

5/12/2016

* ** *** N/A Closed

Will be submitted after the delivery Will be submitted during installation Will be submitted as a part of close out documents Not Applicable to this task Item submitted prviously

Page 1 of 1

S0P5006/10222014/REV00

TRANSMITTAL OF EQUIPMENT AND MATERIAL SUBMITALS SUBMITTAL NUMBER:

15513-001 B95, Rev. 001

13261 Mid Atlantic Blvd. Laurel, Maryland 20708

MECHANICAL APPROVAL

Reviewed for submission:

Limbach Engineering and Design Services 5401 Benchmark Lane Sanford, Florida 32773 Review and approval are only for conformance with the information given and the design concept of the Project as expressed in the Contract Documents, and not for the purpose of determining the accuracy and completeness of other details, such as dimensions and quantities, all of which remain the responsibility of the Contractor as required by the Contract Documents. The Engineer's review and approval of the Contractor's submittals shall not relieve the Contractor from any obligation contained in the Contract Documents.

A B C D

APPROVED APPROVED AS NOTED REVISE AND RESUBMIT REJECTED

INFORMATION:

Fabrication/installation may be undertaken. Approval does not authorize changes in Contract Sum or Contract Time.

Fabrication/installation MAY NOT be undertaken. In resubmitting, limit corrections to items marked.

NO COMMENTS COMMENTS AS

NOTED MECH:

LIMBACH ENGINEERING & DESIGN SERVICES

BY: COUNTERSIGNED: BY: SPEC. SECTION

DATE:

DATE: FILE NO.

5/11/2016

SUBMITTAL NO. 15513-001 B95 Rev1

Contractor's Review and Approval

ITEM(S): Condensing Boilers CATEGORY: Product Data

This submittal has been reviewed by a quality control representative and is compliant with the contract documents and/or is an acceptable variance to the reviewer as noted.

Benjamin Zisman Project Manager Limbach Company LLC PROJECT NAME: WMATA Yard 1 JOB NUMBER: 1713074 DATE: 5/11/2016 ARCHITECT: EDG2 10411 Motor City Drive, Suite 550 Bethesda, MD 20817 Phone: 202-466-2222

GENERAL CONTRACTOR: Potomac Construction Co., Inc. 4701 Lydell Road Hyattsville, MD 20781 Phone: 301-386-3030

SUBCONTRACTOR: Limbach Company LLC 13261 Mid Atlantic Boulevard Laurel, MD 20708 Phone: 301-623-4800

SUPPLIER: Complete Boiler Systems 405 Headquarters Drive Millersville, MD 21108

MANUFACTURER(S): RBI DRAWING OR SPEC #: 15513 REMARKS: IN RESPONSE TO WMATA COMMENTS: 1. BACNET INTERFACE SHOWN AS INCLUDED ON PAGE 4. 2. PER MANUFACTURER, VFD'S ARE NOT REQUIRED AND NOT RECOMMENDED FOR THESE BOILERS. 3. FOR THE BOILERS AT 120V, OUR FULL LOAD AMPERAGE IS ONLY 2.5 AMPS, NO NEED FOR HIGHER VOLTAGE. ALSO THERE ARE NO WMATA DESIGN CRITERIA FOR CONDENSING BOILER POWER REQUIREMENTS. 4. SEE UL/CSA LETTER PROVIDED BY MESTEK BOILER GROUP. PER LETTER, THERE IS NO DIFFERENCE BETWEEN UL AND CSA LISTING. 5. LOW-WATER CUTOFF HAS BEEN PROVIDED AS SHOWN ON PAGE 4.

13261 Mid Atlantic Blvd. Laurel, Maryland 20708

DATE: 05/11/2016 ITEM(S): Condensing Boilers MANUFACTURER(S): RBI

Submittal Information Sheet

SUBMISSION NUMBER: Rev1 SPECIFICATION: 15513 JOB NUMBER: 1713074

Boilers at the Brentwood Service & Inspection Building (B95): I. II.

B-1 B-2

This Submittal is Applicable to the Following Pay Application Number: • •

B95-S0503 B95-S0508

COMPLETE BOILER SYSTEMS LLC “ T H E

P R O F E S S I O N A L

B O I L E R

S Y S T E M S

D I S T R I B U T O R ”

SUBMITTAL for WMATA Brentwood Service and Maintenance Shop RBI Infinite Energy II Series, Quantity (2) Model IB500 Condensing Water Boilers **REVISE AND RESUBMISSION**

Contractor: Limbach Company

Date: 0D\

From: Complete Boiler Systems Inc. 405 Headquarters Dr., Suite 4 Millersville, MD 21108

405 HEADQUARTERS DRIVE, SUITE 4 MILLERSVILLE, MD

21108

410 729-1826, 3O1 912-1616, FAX: 410 729-1829 completeboiler.com

REVISE AND RESUBMIT 5/2/16

Infinite Energy 2 Series Submittal Data Sheet WMATA - BRENTWOOD B95

JOB NAME:

________________________________________________________________________________________________________

LOCATION:

________________________________________________________________________________________________________

BRENTWOOD, MD

ARCH/ENGR:

CONTRACTOR: MODEL NO: TYPE GAS:

EDG2 / LIMBACH

_____________________________________________________________________________________________________

LIMBACH COMPANY

___________________________________________________________________________________________________

(2) IB500 INFINITE ENERGY CONDENSING BOILERS

_______________________________________________________________________________________________________

NATURAL GAS

_________________________________________________________________________________________________________

BTU INPUT/OUTPUT:

500,000 / 472,000

____________________________________________________________________________________________

ADDITIONAL INFORMATION:

INCLUDES: PROBE TYPE LWCO WITH MANUAL RESET AND BACNET MODULE FOR BMS INTERFACE Standard Features

Optional Equipment

• Up to 98% Efficiency • ASME Pressure Relief Valve Loose (Boiler 50#) • ASME T&P Relief Valve Mounted (Water Heater 125#) • State of the Art Metal Mesh Burner • High Efficiency Combustion • Built-in Condensate Trap with Neutralization • Flue Gas Pressure Switch • Highly Visible, Easy Access Condensate Collector • Pressure/Temperature Gauge • Manual Reset High Temperature Limit • Low NOx and CO Emissions • Up to 20:1 Full Modulation • Suitable for Firing Natural or LP Gas • Maximum Allowable Working Pressure: 160 PSI • 316Ti (Titanium) Stainless Steel Heat Exchanger • Negative Pressure Gas Valve • Removable Jacket Panels • Drain Valves • Category IV Multiple Venting Options PVC, PP and Stainless Steel Venting • Factory Supplied Lifting Eye Bolts • Flow Meter

 Interface Modbus  ✔ BACnet Protocessor  LonWorks Protocessor  ✔ Command Cascade Manager for cascade capability one required for multiple boiler applications up to 8 units  RIB Pump Relay  Motorized Valve Kit (one per module required) ✔ Pump (Shipped Loose)  ✔ CSD-1 (LWCO required) 

CONTROL FEATURES: • Plain English Status Display • Flame Signal Logging Capability • PC Connection for Diagnostic • Auto Diagnostics • Freeze Protection • Modbus – 0-10 Vdc (Optional on size 199, required for cascade option) • Ramp Delay Step Modulation • Cascade Capabilities • System Pump Control • Boiler Pump Control • DHW Pump Control • Water Pressure Sensor • Outdoor Reset

 IE2 Modular Package* *(Boiler packages include: Supply Manifold Return Manifold Low Loss Header RIB Pump Relay Pump Check Valve LWCO Tapping Flanged Tee Threaded & Blind Flanges Gaskets Miscellaneous Hardware) *Cascade manager is required per package, Isolation valves to be field supplied.

RSUB-193

4" AIR INTAKE

4" FLUE 1" NPT GAS CONNECTION

2" NPT SUPPLY

2" NPT RETURN

CONDENSATE HOSE

FRONT VIEW

REAR VIEW

SIDE VIEW

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment. 2. Dimensions are subject to change without notice.

CENTER OF GRAVITY

BOILER CERTIFIED RATINGS & CAPACITIES

BOILER TEMPERATURE RISE / PRESSURE DROP

Fuel Type

Natural/Propane Gas

Boiler FLA

2.50*

Input BTU/hr.

500,000 / 147 kW

Min. Gas Pressure Required 3" W.C.**

Output BTU/hr.

472,000 / 138 kW

Max. Gas Pressure Allowed

13" W.C.

GPM

L/s

Ft

kPa

GPM

L/s

Ft

kPa

GPM

L/s

Ft

kPa

Electrical Requirements

120VAC/ 1 ph/ 60 hz

Operating Weight

356 lbs. / 162 kg.

37.8

2.4

37.0

109.0

31.5

1.9

26.0

76.6

27.0

1.7

20.0

58.9

BOILER / WATER HEATER TRIM & CONTROLS

25°F / 13.9°C Flow Rate

30°F / 16.7°C

Pressure Drop

Flow Rate

35°F / 19.4°C

Pressure Drop

Flow Rate

Pressure Drop

WATER HEATER HOURLY RECOVERY CAPACITY

Main Gas Valve

Sit 848 Sigma

Air Switch

HUBA

40°F

22°C

60°F

33°C

80°F

44°C

100°F

56°C

120°F

67°C

140°F

78°C

Ignition Control

Argus

Blower Motor

EBM

1460

5519

973

3679

730

2760

584

2208

487

1840

417

1577

Operating Control

Argus

Relief Valve - IW

3/4" x 3/4" @ 125 psi

High Limit

J2D-AOVJ

Relief Valve - IB

3/4" x 3/4" @ 50 psi

A.S.M.E. ASME Sect IV Htg Surface Water Volume

12.00 Sq. Ft. / 1.125 Sq. M. Design Data 4.0 gal / 15.41 Liters

* Add circulator amps. ** For incoming gas pressures lower than 3" W.C. natural or propane, consult factory.

Max. 160 psig & 210ºF

REP FIRM

COMPLETE BOILER SYSTEMS

SUBMITTED BY MJM JOB NAME

WMATA-BRENTWOOD

ARCHITECT ENGINEER CONTRACTOR

LIMBACH COMPANY

DATE

RESUBMIT 5/2/16

INFINITE ENERGY 2-500 Category II or IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc. Westfield, MA 01085 (413) 568-9571 SIE-500-4

4" AIR INTAKE

4" FLUE 1" NPT GAS CONNECTION

2" NPT SUPPLY

2" NPT RETURN

CONDENSATE HOSE

FRONT VIEW

CENTER OF GRAVITY

SIDE VIEW

REAR VIEW

NOTE: DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

J9-3

J13-4

J7-4

J13-5

J7-5

Heating pump Neutral (max 3A)

Local pump Line (max 3A) Alarm (NO) Volt free Alarm (NO) Volt free Ground

J13-6

Hall + PWM

J9-4

PE N

J2-1 J2-2 J2-3

L

J4-1

PE

J4-2

N

J2-4

J9-5

PE N

PE N

J4-3

L

J4-4

J7-1 J7-2 J7-3 J7-4

L L

J7-5

J9-6

J13-2

J9-2 J9-3

J13-3 J13-4 J13-5 J13-6

J9-7

J9-1

J13-1 Hall +

DHW PUMP Line (max 3A)

N

J2-1 J2-2 J2-3

L

J4-1

PE

J4-2

N

J2-4

J9-5

PE N

PE N

J4-3

L

J4-4

J7-1 J7-2 J7-3 J7-4

L L

J7-5

J9-6

J13-2

J9-2 J9-3

J13-3 J13-4 J13-5 J13-6

J9-7

J9-1

J13-1 Hall +

N

J2-1 J2-2 J2-3

L

PE N L

J2-4

J4-1 J4-2

PE N

PE N

J4-3 J4-4

J13-2

J7-2

J9-5

L

J9-6

J9-2 J9-3

J13-3

J7-4

L

J9-1

J13-1

J7-1 J7-3

J13-4 J13-5

J7-5

J13-6

J9-7

Hall +

J18

J16

J5

J18

J16

J5

J18

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

2 1

8 7 6 5 4 3 2 1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

2 1

8 7 6 5 4 3 2 1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

2 1

8 7 6 5 4 3 2 1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

2 1

PE N L

J9-4 J9-5 J9-6 J9-7

Heating pump Line (max 3A)

LWCO LWCO Ground Neutral Hot 120 Vac 60Hz

110V 110V

RPP3 RPP2

110V 110V

RPP1 RGPS

110V

PS

1

RGPR

110V

RPP4

2

J16

J5

PWM

J16

PWM

J9-4

PE

J18

Ground

J5

PWM

J9-4

PE

N

8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26 27 28 29 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26 27 28 29 109 110 113 114 109 110 113 114

DHW PUMP Neutral (max 3A)

101 102 PE 103 104 101 102 PE 103 104

J9-2

J13-3

J6-1

107 108 107 108

L

J13-2

J6-2

J6-1

L

J9-1

J13-1

J6-3

J6-2

J7-3

J6-1

Local Pump Neutral (max 3A)

F1

J4-4

J7-2

J6-2

Ground

105 106 105 106

J2-4

J7-1

J6-3

J6-3

N

J6-1

PE

F1

N

J6-2

PE

J4-3

L

F1

J4-2

N

J6-3

J4-1

PE

F1

J2-3

L CH

Main switch

SLAVE

SLAVE

SLAVE

DISPLAY

MASTER Burner

L DHW

J2-2

+ 5V

J2-1

8 7 6 5 4 3 2 1

Bus (cascade) Bus (cascade) External Reset External Reset Cascade header sensor Cascade header sensor 0-10 Vdc input (+) 0-10 Vdc input (GND) RS 485 Modbus GND RS 485 Modbus TRS 485 Modbus T+ Bus (HC command) Bus (HC command) Outdoor sensor (OS) Outdoor sensor (OS) Tank sensor (TS) Tank sensor (TS) Room thermostat (RT) Room thermostat (RT) Header sensor (HS) Header sensor (HS)

F6 = T 3 L 250V (3A Ritardato)

F4 = T 3 L 250V (3A Ritardato) F3 = T 3 L 250V (3A Ritardato)

L N GND

L N GND

L N GND

L N GND

F2 = T 10 L 250V (10A Ritardato)

PG TG HL LW

+ Hall GND PWM -

+ Hall GND PWM -

+ Hall GND PWM -

+ Hall GND PWM -

F1 = T 10 L 250V (10A Ritardato)

32 104411m1_d

885_MN10 Master 29

885_MN10 Slave

16 6

47

16

47

J9

J9

J16

J16

10

19 17

20

11

17

6

20

11

28 22

22

LWCO

J13

41

J13 16A

34 10 15

J6

15 J5 J5

9

48

J7

48

J7

HS RPP1

16A

RPP2

7

RPP2

J7

49

RPP4

OS

J9

50

RPP3

RT

41

RGPR

16A

RGPS

42

S4 F1

J6

RPP4

J4

13

J1

9

TS

J8 35 13

J4

J4

14

14

F1 3.15A J18

F1 3.15A J2

J18

J2

BUS CAS.

49 16A

J3

16A

RPP3

J6

16A

850IF

49

7

42 J2

J5

BUS COM.

47

7

15

17

35 F1

9

S4

47

19

15

9

J9

885_MN10 Slave

J7

J9

885_MN10 Master

J7 J6

J4

J13

11

J5

F1 3.15A

20

Alarm (NO) Volt free Alarm (NO) Volt free

14

20

109 110 113 114

Local pump Line (max 3A)

13

Ground Local pump Neutral (max 3A)

6

16

22

6

10

48

13

14

51

J2

16

22

J16

S4

J18

J6

J2

J4

J13

11

7

29

J16

17

S4

J5

28

F1 3.15A

J18

34

850IF 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26 27 28 29

Bus (cascade) Bus (cascade) External Reset External Reset Cascade header sensor Cascade header sensor 0-10 Vdc input (+) 0-10 Vdc input (GND) RS 485 Modbus GND RS 485 Modbus TRS 485 Modbus T+ Bus (HC command) Bus (HC command) Outdoor sensor (OS) Outdoor sensor (OS) Tank sensor Tank sensor Room thermostat (dry contact) Room thermostat (dry contact) Header sensor (HS) Header sensor (HS)

DHW pump Line (max 3A)

LWCO LWCO Ground Neutral Hot 120 Vac 60Hz

32

Heating pump Line (max 3A)

101 102 PE 103 104 105 106

Ground Heating pump Neutral (max 3A)

10

48

107 108

Ground DHW pump Neutral (max 3A)

IE2C-3

Condensing High Efficiency Gas-Fired Boilers and Water Heaters

IE2 high efficiency gas-fired boilers and water heaters utilize stateof-the-art Radial Variable Circulation (RVC) stainless steel heat exchangers for maximum heat transfer and operating efficiencies of up to 98%. Using all of today’s modern technologies including pre-mix burners, modulating firing rates of up to 20:1 and integrated cascade controls IE2 provides users with superior performance and application flexibility. Available from 199 to 1000 MBH the IE2 provides flexible solutions for all of your heating and domestic hot water needs. Units are PVC, polypropylene (PP) and stainless steel vent capable and can be installed in multiple unit configurations using its on-board control which provides flexible modulation for maximum efficiency. Features and Benefits • 199 – 1000 MBH • Up to 98% Ultra-High Efficiency • RVC Stainless Steel Heat Exchanger • PVC, PP and Stainless Steel Venting • Intuitive Integrated Control Platform • Multi-Unit Cascade Communication (8 Units) • MODBUS Based Control • Pre-Mix Burner Technology • Up to 20:1 Full Modulation • Low NOx and CO emissions (