Document not found! Please try again

Circuit Breakers - Cooper Electric

Report 5 Downloads 99 Views
Circuit Breakers Arc-Fault and Ground-Fault Breakers

Selection/Wiring Diagrams

Arc-Fault Circuit Interrupters (AFCI) AFCI’s detect arcing faults (an unintentional arcing condition in a circuit) that standard circuit breakers are unable to detect. The device is intended to mitigate the effects of arcing faults by functioning to de-energize the circuit when an arc-fault is detected.

Combination Type AFCI Detects all three possible types of arc fault: line-to-ground, line-to-neutral, and series. 10,000 A IR

22,000 A IR

Catalog Number

Catalog Number

QAF/QAFH

15 20

Q115AFCa Q120AFCa

Q115AFCHna Q120AFCHna

QAF/QAFH

15 20

Q215AFCa Q220AFCa

Q215AFCHna Q220AFCHna

Breaker Type

Ampere Rating

1-Pole 120V AC

2-Pole 120/240V AC

1-Pole Combination Type AFCI

2-Pole Combination Type AFCI

Branch-Feeder AFCI Detects line-to-ground and line-to neutral arcs.

QAF/QAFH 1-Pole 120V AC

15 20

Q115AFa Q120AFa

Q115AFHna Q120AFHna

1-Pole Branch Feeder AFCI

Ground-Fault Circuit Interrupters (GFCI) Provides Class A (5mA) ground fault protection. Intended for personnel protection. De-energizes the circuit for all ungrounded conductors of the circuit.

QPF/QPHF

1-Pole 120V AC Plug-in

QPF/QPHF

2-Pole 120/240V AC Plug-in

QF115a QF120a QF125n QF130 QF215 QF220 QF230 QF240 QF250 QF260

QF115Ha QF120Hna — QF130H QF215H QF220H QF230H QF240H QF250H QF260H

1-Pole GFCI

2-Pole GFCI

1-Pole Equipment Protection

2-Pole Equipment Protection

MOLDED CASE CIRCUIT BREAKERS

Ground Fault Equipment Protection (30mA) Provides protection of equipment from damaging line-to-ground faults currents. De-energizes the circuit for all ungrounded conductors of the circuit.

QE/QEH

1-Pole 120V AC Plug-in

QE/QEH

2-Pole 120/240V AC Plug-in

15 20 30

QE115a QE120a QE130

QE115Ha QE120Ha QE130H

15 20 30 40 50 60

QE215 QE220 QE230 QE240 QE250 QE260n

QE215H QE220H QE230H QE240H QE250H QE260Hn

QAF/QPF/QE Accessories Description

Catalog Number

Padlocking Device 1-Pole

ECPLD1

Padlocking Device 2-Pole

ECPLD2

Handle Block

ECBX231M

Wiring Diagrams

n Built to order. Allow 2–3 weeks for delivery. a

7

15 20 25 30 15 20 30 40 50 60

 L Listed as SWD (Switching Duty) Rated, suitable for U 120V AC Fluorescent Lighting.

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

7-19

• Revised • 03/06/13

Circuit Breakers Type QP with INSTA-WIRE Type Continuous Current Rating @ 40° C

1-Pole Plug-In (120V

Selection

QP

10,000A IR Catalog Number AC)e Q110 Q115c Q120c Q125 Q130 Q135n Q140 Q145n Q150 Q160 Q170

10 15 20 25 30 35 40 45 50 60 70

Q210 Q215 Q220 Q225 Q230 Q235 Q240 Q245 Q250 Q260 Q270 Q280 Q290 Q2100 Q2110 Q2125

MOLDED CASE CIRCUIT BREAKERS

7

2-Pole Plug-In (Common-Trip 240V

65,000A IR

Catalog Number

Catalog Number — Q115HHnc Q120HHnc Q125HHn Q130HHn Q135HHn Q140HHn Q145HHn Q150HHn Q160HHn Q170HHn

— Q215H Q220H Q225Hn Q230H Q235Hn Q240H Q245Hn Q250H Q260H Q270H Q280Hn Q290H Q2100H Q2110H Q2125H AC)

— Q215HH Q220HH Q225HHn Q230HH Q235HHn Q240HHn Q245HHn Q250HH Q260HH Q270HH Q280HHn Q290HHn Q2100HH Q2110HHn Q2125HH

Q215R Q220R Q230R Q240R Q250R Q260R Q270R Q2100Rn

15 20 30 40 50 60 70 100

Type HQP

22,000A IR

— Q115Hc Q120Hc Q125Hn Q130H Q135Hn Q140H Q145Hn Q150H Q160Hn Q170Hn AC)

2-Pole Plug-In (Common-Trip 120/240V 10 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125

Type QPH

— — — — — — — —

— — — — — — — —

Q315H Q320H Q325Hn Q330H Q335Hn Q340H Q345Hn Q350H Q360H Q370H Q380H Q390H Q3100H

Q315HHn Q320HH Q325HHn Q330HH Q335HHn Q340HH Q345HHn Q350HH Q360HH Q370HHn Q380HHn Q390HHn Q3100HH

3-Pole Plug-In (Common-Trip 240V AC) Q315 Q320 Q325 Q330 Q335 Q340 Q345 Q350 Q360 Q370 Q380 Q390 Q3100

15 20 25 30 35 40 45 50 60 70 80 90 100

QP / QPH / HQP Internal Accessories Control Voltage AC 120V Shunt Trip 24V Shunt Trip 120V Auxiliary Switch

Catalog Number add suffix …00S01n add suffix …00S07n add suffix …01nb

n Built to order. Allow 2-3 weeks for delivery. a UL

Listed for use with 60/75° wire through 40 amps, UL listed for use with 75° wire only for 50 amps and above, HACR rated. b 1A and 1B contacts.

7-20

Field/Factory Installed Factory Factory Factory

Modifications Description 400 Hz Calibration Marine 50˚C Ambient Calibration Fungus Proofing

Listed for frequent switching applications (SWD). 120V AC Fluorescent Lighting. Listed for use on 3-phase grounded “B” systems ­­— 10,000 for this application. e Shipped 12 per sleeve.

Catalog Number add suffix …Yh add suffix …M add suffix …F

c UL

f Shipped

d UL

h UL

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

For external accessories, please refer to page 7-93

6 per sleeve. 4 per sleeve. Listed 5 KA IR. i Type QP1, UL listed for 16 AWG conductors and multiple wires. g Shipped

Product Category RESI

• Revised • 04/30/13

Circuit Breakers Duplex, Triplex and Quadplex Plug-In Breakers

Selection

Duplex Circuit Breakers Breaker Type

QT

1-Pole 10K AIC 120V AC

Ampere Rating Catalog Number 15–15 Q1515 15–20 Q1520 20–20 Q2020 20–30 Q2030 30–15n Q3015 30–20 Q3020 30–30 Q3030 SHIPPING: 12 per carton, (Wt. 4.8 lbs.)

Catalog Number Q1515NCa Q1520NCa Q2020NCa — — — Q3030NCa

Triplex Circuit Breakers Ampere Rating Breaker Type

QT

2-Pole 10K AIC 120/240V AC Inner Poles Common Trip

Common-Trip Single Pole 2-Pole 15 15 15 20 15 25 15 30 15 35 15 40 15 45 15 50 20 20 20 25 20 30 20 35 20 40 20 45 20 50 30 30 SHIPPING: 6 per carton, (Wt. 4.9 lbs.)

QT Duplex These space saver duplex breakers combine two independent 1/2" breaker poles in a common unit. This unit plugs into one load center stab and requires one panel space. HACR rated.

Catalog Number Q21515CT Q21520CT Q21525CTn Q21530CT Q21535CTn Q21540CT Q21545CTn Q21550CT Q22020CT Q22025CTn Q22030CT Q22035CTn Q22040CT Q22045CTn Q22050CT Q23030CT

QT Triplex These space saver triplex breakers provide a 2-pole common trip breaker for 120/240V AC circuits and two single poles for 120V AC circuits. Triplex require two panel spaces. HACR rated.

Quadplex Circuit Breakers Ampere Rating

QT

Catalog Number Q21515CT2 Q22020CT2 Q23020CT2 Q24020CT2 Q23030CT2 Q24030CT2 Q24040CT2 Q23050CT2

QT Quadplex These space saver quadplex breakers provide two sets of common trip, two-pole breakers for 120/240V AC circuits, and require two panel spaces. HACR rated.

For external accessories, please refer to page 7-93 For inches / millimeters conversion, see Application Data section.

Product Category RESI

n Built to order. Allow 2–3 weeks for delivery.

a

 on-CTL. For replacement use only in panels manufacN tured before 1968

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

7-21

MOLDED CASE CIRCUIT BREAKERS

2-Pole 10K AIC 120/240V AC Inner and Outter 2 Poles Common Trip

Common-Trip Common-Trip 2-Pole Inside 2-Pole Outside 15 15 20 20 20 30 20 40 30 30 30 40 40 40 50 30 SHIPPING: 6 per carton, (Wt. 4.8 lbs.)

7

Breaker Type

Circuit Breakers Special Application Breakers

Selection

HID Lighting

For high-intensity discharge lamp loads having in-rush currents above the instantaneous trip setting of a standard breaker. Breaker Type

QP

1-Pole 120V AC

QP

2-Pole 120/240V AC

Wiring Diagram Figure 1

Figure 2

Complete Breaker UL Unenclosed Ampere Rating Catalog Number 15 20 30 15 20 30

Q115HID a n Q120HID a Q130HID Q215HID Q220HID n Q230HID n

Molded Case Switch

Switching Neutral

For applications that do not require overcurrent protection.

QP

1-Pole 120V AC

QP

2-Pole 120/240V AC

Figure 1

100

Q1100S

Figure 2

30 60 125

Q230S Q260S Q2125S

No-Noise

For applications that require a reduction in the 60-cycle hum of a standard breaker.

QP

2-Pole 120/240V AC

Figure 2

50 60 70 90

Q250NNn Q260NN Q270NN Q290NNn

Water Heater

Switching Neutrals

MOLDED CASE CIRCUIT BREAKERS

7

Used where all conductors are required to be disconnected. Neutral pole of the circuit breaker does not connect to load center bus. One side is wired to neutral and the other side to the device.

QG

2-Wire Common Trip 120V AC

Figure 3

15 20 30

QG215 QG220 QG230n

Figure 4

15 20 30

QG315n QG320 QG330n

QG

3-Wire Common Trip 120/240V AC

Figure 1

Figure 2

Figure 3

Figure 4

Tungsten Lighting

For high wattage, tungsten-lamp loads having in-rush currents above the instantaneous trip setting of a standard breaker.

QP

1-Pole 120V AC

Figure 1

15 20

Figure 5

Q115T a n Q120T a

Water Heater

When installed in a loadcenter, the water heater circuit breaker does not make electrical connection with the loadcenter bussing. Separate metered circuit is connected to line terminals of the breaker. Used in special rate water heating areas.

QW

2-Pole 120/40V AC Plug-In

Figure 5

15 20 30

Wiring Diagrams

QW215 QW220 QW230

n Built to order. Allow 2–3 weeks for delivery.

a UL

Listed as SWD (Switching Duty) Rated, suitable for 120V AC Fluorescent Lighting.

Note: All circuit breakers on this page are 10K AIC

7-22

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

Product Category RESI

Circuit Breakers 3/4 Inch Plug-In Breakers

Selection

Features b 3/4" format b HACR Rated b UL Classified for use in certain Square D load centers Type QD Circuit Breakers The Type QD circuit breaker line is available in 1-pole and 2-pole common trip versions listed on this page. The circuit breakers are UL Classified and UL Listed. All QD breakers are supplied with load side connectors suitable for 60/75°C wire and are calibrated for 40°C maximum ambient applications.

Product Category RESI

2-Pole

120V

120/240V Common Trip

Catalog Number

Catalog Number

D115 a D120 a D130 D140 D150 D160

D215 D220 D230 D240 D250 D260

Shipping Weights Number of Number Per Poles Carton

Shipping Weight (lbs.)

1 2

3.8 4.2

16 8

Panelboard Compatibility List Listed Panelboards—Square D—Catalog Numbers QO2L30F/S QO2-4L70F/S QO2-4L70TS QO2-4L70RB QO6-12L100F/S QO6-12L100DF/S QO6-12L100TF/S QO6-12L100DTF/S QO6-12L100RB QO8-16L100F/S QO8-16L100DF/S QO8-16L100TF/S QO-16L100DTF/S QO8-16L100RB QO112M100/RB QO116M100/RB QO120M100/RB QO124M100 QO12L100DF/S QO12L100RB QO12-20M100/RB QO12-20M100TF/S

a

QO12M100/RB QO16-20M100/RB QO16M100/RB QO20M100/RB QO112L125G/RB QO112-24L125/RB QO112-24L125GWGC QO116L125G QO116-24L125G/RB QO12-24L125/RB QO120-24L125G QO120-24L125GWGC QO120L125G QO124L125G/RB QO124M125/RB QO16L125/RB QO16-12M125FTRB QO16-24L125/RB QO20L125/RB QO20-24L125/RB QO24L125/RB QO120-30L150G

QO120-30M150/RB QO124L150G QO124M150 QO130L150G/RB QO130M150/RB QO16L150/RB QO16M150/RB QO16-30L150/RB QO18-16M150FTRB QO20-30M150/RB QO20-30M150TF/S QO20-30L150 QO24L150/RB QO24M150/RB QO30L150/RB QO30M150/RB QO8-16M200FT/RB QO112L200G/RB QO120-40M200/RB QO120-40M200TC QO124M200 QO130L200G/RB

QO130-40M200 QO130200/RB QO130-40L200G/RB QO140M200/RB QO16L200/RB QO16M200/RB QO18-16M200FTRB QO20-40L200/RB QO20-40M200TF/S QO20-40M200/RB QO24L200/RB QO24M200/RB QO30L200/RB QO30M200/RB QO30-40L200/RB QO30-40M200/RB QO40M200/RB QO140M225 QO142L225G/RB

 L Listed for frequent switching applications (SWD). U 120V AC Fluorescent Lighting. One or two load conductors.

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

7-23

MOLDED CASE CIRCUIT BREAKERS

For inches / millimeters conversion, see Application Data section.

15 20 30 40 50 60

1-Pole

7

UL Classified Siemens Type QD circuit breakers are UL Classified for use in specific Square D load centers in place of Square D Type QO® circuit breakers. A Panelboard Compatibility List packaged with each QD breaker shows which type QD circuit breakers are acceptable for use in Square D load centers. The interrupting rating on these circuit breakers is 10,000A IR maximum and they are not series rated with Square D circuit breakers or equipment. This UL Classification allows a Siemens Type QD circuit breaker to be used in place of a Square D Type QO circuit breaker in those load centers that are specifically shown on the Panelboard Compatibility list. For additional information, contact your local Siemens sales engineer.

Continuous Current Rating @ 40°C

• Revised • 11/05/13

Circuit Breakers Main and Branch Circuit Breakersa Breaker Type

QN

2-Pole 120/240V AC

Ampere Rating 150 175 200

Selection

Catalog Number

Catalog Number

QN2150 QN2175n QN2200

QN2150R b QN2175R b n QN2200R b

QNH

150 QN2150H QN2150RH b 175 QN2175RH bn QN2175H n 200 QN2200H QN2200RH b 150 HQN2150 HQN2150R b HQN — 175 HQN2175 n 2-Pole 120/240V AC 200 HQN2200 HQN2200R b Requires 4 panel spaces, 2 adjacent and 2 opposite. SHIPPING: 1 per carton 2-Pole 120/240V AC

UL Interrupting Ratings (kA) 10 10 10 22 22 22 65 65 65 (Wt. 3 lbs.)

QNRe

QNe

Main Breaker Kits For use in Ultimate Load Centersd

For use in EQIII Load Centers

UL Type EQ8681 EQ8682 EQ8693 — EQ8695 EQ8696

UL Type EQ9675 EQ9677 EQ9683 EQ9684 EQ9685 EQ9686

Ampere Rating 100 125 150 — 200 225

Catalog Number MBK100A MBK125A MBK150A — MBK200A MBK225A

Ampere Rating 100 125 150 175 200 225

Catalog Number MBK100 MBK125 MBK150 MBK175n MBK200 MBK225

Breaker Type

Ampere Rating

Catalog Number

UL Interrupting Ratings (kA)

QPJ

125 150 200

QPJ3125 QPJ3150 QPJ3200

10 10 10

c

3-Pole 240V AC

UL Interrupting Ratings (kA) 22 22 22 22 22 22

EQ96XX

Requires 6 spaces due to cross over design. Fits only EQIII 125-400A 3-phase load centers



SHIPPING: 5 per carton (Wt. 17 lbs.)

MOLDED CASE CIRCUIT BREAKERS

7

Breaker Type

QPP

2-Pole 120/240V AC

QPPH

2-Pole 120/240V AC

HQPP

2-Pole 120/240V AC

HQPPH

2-Pole 120/240V AC

Ampere Rating 125 150 175 200 225 125 150 175 200 225 125 150 175 200 225 100 125 150 175 200 225

Catalog Number Q2125B Q2150B Q2175Bn Q2200B Q2225B Q2125BH Q2150BH Q2175BHn Q2200BH Q2225BHn Q2125BHHn Q2150BHH Q2175BHHn Q2200BHH Q2225BHHn HQ2100BHn HQ2125BHn HQ2150BHn HQ2175BHn HQ2200BHn HQ2225BHn

For inches / millimeters conversion, see Application Data section. n Built to order. Allow 2–3 weeks for delivery.

UL Interrupting Breaker Ratings (kA) Volts AC 120/240 10 10 10 10 10 22 22 22 22 22 65 65 65 65 65 100 100 100 100 100 100

a All circuit breakers on this page are common trip. b Reverse handle. c CSA Listed. d MBK100A for use in 100 and 125A load centers.

MBK125A for use in 125A load centers. MBK150A for use in 150, 200 and 225A load centers. MBK200A for use in 200 and 225A load centers. MBK225A for use in 225A load centers. MBK175A for use in 200 and 225A load centers.

7-24

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

MBK (100,125)A

MBK (150,200,225)A

2-Pole QPP

QPJ

e

 NR required for horizontal applications or vertical Q applications where the lugs are facing up. The QN breaker is required for vertical applications where the lugs are facing down as shown.

Product Category RESI

Circuit Breakers Main and Branch Circuit Breakers QS Breaker PowerMod's core offering of residential Meter Stacks, type WMM, offers the widest product offering & flexibility in the industry.  Each meter stack houses the QuickSystem features to maximize productivity and minimize labor costs. To further simplify installation, our 225 Amp meter stacks feature the QS breaker. The QS breaker adds to the Siemens exclusive feature set in our Power Mod product line. Benefits and part numbers include:

Front View

▪ An exclusive side wired design saves wiring space and eliminates difficult "S bends" ▪ No need for costly filler plates — QS 225 Amp breaker takes the same space as standard 100 Amp QPs ▪ Single right hand bend wiring - saves time and wire ▪ Provides 100K AIC flexibility from 100 up to 225 Amps ▪ 10K to 100K AIC Series Rating QS Breaker Breaker Type

QS

QSH

QSHH

HQS

HQSH

Amperage

10K AIC

22K AIC

42K AIC

65K AIC

100K AIC

100

QS2100

QS2100H

QSH2100

QS2100HH

HQS2100H

125

QS2125

QS2125H

QSH2125

QS2125HH

HQS2125H

150

QS2150

QS2150H

QSH2150

QS2150HH

HQS2150H

175

QS2175

QS2175H

QSH2175

QS2175HH

HQS2175H

200

QS2200

QS2200H

QSH2200

QS2200HH

HQS2200H

225

QS2225

QS2225H

QSH2225

QS2225HH

HQS2225H

QS Breaker Dimension Drawing .19

1.00

.58

.96

7

PRECAUCION

MOLDED CASE CIRCUIT BREAKERS

CAUTION

1.38

7.89 4.31

000A 000000

ON

2.22

20 NEUTRAL

OFF

.99 20

.19 .28 1.39

2.01 2.38 2.56 2.66

.16

1.34

.37

1.06 1.16 2.12

 For

PowerMod information, please refer to Section 2, page 2-49

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

7-25

Circuit Breakers Line Diagrams

1-Pole

Dimension Drawings

2-Pole

3-Pole

3" 23/8"

31/8" Type QT

Type QPF, QPHF, QE, QAF, QAFH

Type EQ8681, EQ8682

Type EQ8693, EQ8695, EQ8696

Type QPJ

Type QN, QNH, HQN

Type QNR, QNRH, HQNR

Type QPP, QPPH, HQPP, HQPPH

MOLDED CASE CIRCUIT BREAKERS

7

QP, QPH, HQP

a

 ll standard circuit breakers are calibrated to 40°C maxiA mum ambient application.

7-26

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

Circuit Breakers Lug Data Circuit Breaker Type

Reference Circuit Breaker Ampere Rating

Cables Per Connector

Connector Wire Range

2

#14-#16 AWG Cu

1 1 1 1 1 1 1 1

#14–#6 AWG Cu #14–#6 AWG Al #8–#6 AWG Cu #8–#4 AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #14–#6 AWG Cu #14–#6 AWG Al

1

#8 AWG CU-Al

1 1 1 1 1 1 1 1

#8–#6 AWG Cu #8–#4 AWG Al #14–#10 AWG Cu #12–#8 AWG Al #8–#6 AWG Cu #8–#4 AWG Al #14–#12 AWG Cu #12–#10 AWG Al

2

#14–#8 AWG Cu Only

1 1 1 1 1 1

#14–#12 AWG Cu #12–#10 AWG Al #10–#8 AWG Cu #10–#6 AWG Al #8–#6 AWG Cu #8–#4 AWG Al

150–200

1

#1–300kcmil Cu-Al

100–225

1

#3–300kcmil Cu-Al

100

1

#4–3/0 AWG Cu-Al

125

1

#4–3/0 AWG Cu-Al

150

1

#1–300kcmil Cu-Al

200

1

#1–300kcmil Cu-Al

225

1

#1–300kcmil Cu-Al

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

#1 AWG Cu #2/0 AWG Al #1/0 AWG Cu #3/0 AWG Al #2/0 AWG Cu #4/0 AWG Al #3/0 AWG Cu 250kcmil AWG Al #4/0 AWG Cu 300kcmil AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #1/0 AWG Cu #3/0 AWG Al #3/0 AWG Cu 250kcmil AWG AL #3/0 AWG Cu 250kcmil AWG Al #4/0 AWG Cu 300kcmil AWG Al

1

#2–300kcmil Cu-Al

LOAD SIDE

QP, QPH, HQP, Plug-in

10 15–35 40–50 55-125

QT

15–35 40 40–50

QPF, QPHF

15–30 40–60

QAF, QAFH QD

15–20 15–20 15–20 25–35 40–60

150 175 200 225

EQ9675-EQIII EQ9677-EQIII EQ9683-EQIII EQ9684 EQ9685-EQIII EQ9686-EQIII QPJ

100 125 150 175 200 225 125–200

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

MOLDED CASE CIRCUIT BREAKERS

125

7

QN, QNH, HQN QS, QSH, QSHH, HQS, HQSH EQ8681-Ultimate EQ8682-Ultimate EQ8693-Ultimate EQ8695-Ultimate EQ8696-Ultimate QPP, QPPH, HQPP, HQPPH

7-27

Surge Protection Circuit Breaker and Surge Protective Device (SPD) Features

Circuit Breaker and Surge Protective Device (SPD)

▪ 2 inch wide plug-on design — Includes (2) 1 Pole circuits breakers ­— No loss of load center spaces ▪ Easy to install and perfect for retrofit ▪ LEDs provide protection status

Benefits

By installing a Siemens Circuit Breaker and Surge Protective Device (SPD) in the load center of the residence, surge protection is provided for all branch circuits. Two green LED indicator lights are provided to show that surge protection is provided for all circuits connected to the load center. These breakers should be used for circuit protection of frequently used household or facility circuits because the lights and devices connected to these circuits provide an effective indication that surge protection is being provided. The circuit breaker and SPD utilize Siemens-built 150V AC, 40mm, metal oxide varistors (MOVs). The maximum impulse rating for the SPD module is 40kA. The standard interrupting rating for the circuit breakers is 10k AIC. All Type QP circuit breakers and SPD are plug-on style, with load terminals provided. The devices are rated for 120/240V AC and are calibrated for 40 degrees C maximum ambient applications. Breaker Type QP 1- Pole 120/240V AC 10K AIC

Ampere Rating

Catalog Number

Surge Type

(2) 15

QSA1515SPD

SPD

(2) 20

QSA2020SPD

SPD

MOLDED CASE CIRCUIT BREAKERS

7

Catalog Number Amperage Number of Poles Initial Clamping Level Transient Energy Rating Transient Suppression Voltage Rating Peak Current Rating (impulse) Discharge Voltage Characteristic Discharge Current Withstand Rating Circuit Breaker Interrupting Rating Listings/Certifications

QSA1515SPD QSA2020SPD 15 or 20 Amp (2) 1-Pole Circuit Breakers 240 Volts 360 Joules line-to-neutral 720 Joules line-to-line 500 volts peak, line-to-neutral 1000 volts peak, line-to-line 40,000 amperes @ 1,500A, 600 volts @ 5,000A, 800 volts (both line-to-neutral) 10,000 amperes line-to-neutral 10,000A, 120/240V AC UL, CSA Meets UL 1449 3rd Edition

 For

warranty information please refer to the surge website www.usa.siemens.com/surge

7-28

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

Product Category RESI