circuit breakers - DLE ELECTRIC SUPPLY

Report 11 Downloads 105 Views
CIRCUIT BREAKERS CB 15

PANELBOARD BREAKERS

Type BLE 10,000 AIR

1 20/240 V AC

1 Pole(120/240VAC)

2 Pole (120/240V AC)

Amps

Catalog #

List Each

Catalog #

List Each

15 20 30 40 50 60

MB115EG MB120EG MB130EG — — —

343.00 343.00 343.00

MB215EG MB220EG MB230EG MB240EG MB250EG MB260EG

451.00 451.00 451.00 451.00 451.00 451.00

HID Lighting Application Breakers Type BL 10,000 AIC

120/240V AC

1 Pole (120/240V AC) Amps 15 20 30

2Pole(120/240VAC)

Catalog #

List Each

Catalog #

MB115HID MB120HID MB130HID

36.50 36.50 36.50

MB215HIO MB220HID MB230HID

List Each 77.00 77.00 77.00

Switching Neutral Type BL 10,000 AIC

1 20/240V AC

t Pole, 2 Wire (1 10/240 V AC) Amps

Catalog #

15 20 30

2 Pole, 3 Wire I120/240V AC) List Each

MB215SN MB220SN MB230SN

101.20 101.20 101.20

Catalog #

List Each

MB315SN MB320SN MB330SN

151.80 151.80 151.80

Type BQD®

>

480Y/277V AC 1 Pole

3 Pole

2 Pole

Amps

Catalog #

List Each

Catalog #

List Each

Catalog it

List Each

15 20 25 30 35 40 45 50 60 70 80 90 100

BQ115KM BQ120KM BQ125KM BQ130KM BQ135KM BQ140KM BQ145KM BQ150KM BQ160KM BQ170KM BQ180KM BQ190KM BQ1100KM

101.00 101.00 101.00 101.00 101.00 101.00 101.00 101.00 101.00 212.00 212.00 212.00 212.00

BQ215KM BQ220KM BQ225KM BQ230KM BQ235KM BQ240KM BQ245KM BQ250KM BQ260KM BQ270KM BQ280KM BQ290KM BO2100KM

250.00 250.00 250.00 250.00 250.00 250.00 250.00 250.00 250.00 507.00 507.00 507.00 507.00

BQ315KM BQ320KM BQ325KM BQ330KM BQ335KM BQ340KM BQ345KM BQ350KM BQ360KM BQ370KM BQ380KM BQ390KM BQ3100KM

442.00 442.00 442.00 442.00 442.00 442.00 442.00 442.00 442.00 603.00 603.00 603.00 603.00

Type ED4©

480V AC 3 Pole

2 Pole

1 Pole Amps

Catalog #

List Each

Catalog #

List Each

Catalog #

List Each

15® 20® 25 30 35 40 45 50 60 70 80 90 100 110 125

ED4115 ED4120 ED4125 ED4130 — ED4140 — ED4150 ED4160 ED4170 — — ED41100 — —

133.00 133.00 133.00 133.00 — 133.00 — 133.00 133.00 250.00 — — 250.00 — —

ED4215 ED4220 ED4225 ED4230

450.00 450.00 450.00 450.00

ED4240

450.00

ED4250 ED4260 ED4270 ED4280 ED4290

450.00 450.00 591.00 591.00 591.00

ED4315 ED4320 ED4325 ED4330 ED4335 ED4340 ED4345 ED4350 ED4360 ED4370 ED4380 ED4390 ED43100 ED43110 ED43125

589.00 589.00 589.00 589.00 589.00 589.00 589.00 589.00 589.00 693.00 693.00 693.00 693.00 1,370.00 1,370.00

Note: For additional ratings and applications consult your local Murray Sales Office. Accessories - see page CB-19. Interrupting Ratings - see page CB-20.

Discount Schedule "A "

©Circuit Breakers are provided with load side terminal connectors.

nKf/f/ft'U

| ^»- CIRCUIT BREAKERS

> Type BL Equipment Protection (GFCI 30ma)

CIRCUIT BREAKERS TECHNICAL INFORMATION

Time-Current Characteristic Curves

CBS Murray Time-Current Characteristic Curves 125 AMP MP Frame, Type MP-T 1, 2 & 3 Poles CURRENT IN PERCENT OF BREAKER RATING

125 Amp MP Frame, Type MP-T, 1,2&3Poles

3J O C -I

For application and coordination purposes only. Based on 40°C ambient cold start. Connected with 4 feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Type MP-T

CD

30

m

60 HZ 1 -Pole 120/240 Volts 60 HZ 2-Pole 120/240 Volts 60 HZ 3-Pole 240 Volts

> * m

30 CO

1 Pole Instantaneous Trip Table Rating Amperes

Fixed Instantaneous Trip Amperes

15-20

160-210

25-40

350-550

45-50

450-700

2 & 3 Pole Instantaneous Trip Table Rating Amperes

Fixed Instantaneous Trip Amperes

15,25-35

350-700

20

450-700

40

350-550

Interrupting Rating Symmetrical RMS Amperes Breaker Type

120V

120/240V

240V

1-Pole



10,000



2-Pole



10,000



3-Pole





10,000

Footnotes refer to curve at right. ©Single pole test data at 25°C in accordance with NEMA standards. 0-30 amperes— 50 seconds 31-50 amperes —80 seconds ©Sample Instantaneous shown (20 Amp 1, 2 & 3 Pole). For other instantaneous values, see tables above.

Industry and Government Specifications Murray circuit breakers meet or exceed the latest edition of the following specifications:

Industry NEMA—Standard #AB1 UL —Standard #489 CSA —Standard #C22.1, No. 5.1

U.S. Government Standard #W-C-375B

60°C/75°C Ampacity Rating Murray circuit breakers rated 125A and below are Listed by UL for use with 60°/75°C ampacities. This listing allows use of smaller wire sizes in many applications. Consult NEC Article #310 for application details and limitations.

I

MP(150-200A) MD-A, MD-H, MD-T, MD-HT MP05-125A) MP-T, MP-HT, MP-MT, MG, MW MP(Duplex) MH-T MP(Triplex) MH-T MP(GFCI) MP-GT, MP-HGT MP(AFCI)_____MP-AF, MP-HAF_________ *UL Type is shown on circuit breaker label.

for switching duty use on circuits controlling fluorescent lights. (1996 NEC article #240-83d).

HACR All Murray circuit breakers are UL Listed "HACR" rated for use on heating, air conditioning and refrigeration circuits per 1996 NEC article #430-53 (c) (3).

CIRCUIT BREAKERS CB

20

| ffr

Interrupting Ratings

APPLICATION DATA

RMS Symmetrical Amps (kA)

CIRCUIT BREAKERS

Breaker Type

Maximum Amperage

BQD (1-P)

100

BQD (2,3-P)

100

ED4I1-P) ED4 (2,3-P)

Volts AC

120

240 65

65 125

480

600

14 22

65

HED40-P 15-30A)

100

HED4 1-P35-70A)

100

HED4 (2,3-P)

277

65

18 65 25

100

42 25

18

ED6, (2,3-P)

125

65

QJ2

225

10

QJH2

225

22

QJ2-H

225

42

FXD6

250

65

35

22

HFD6

250

100

65

25

JXD2

400

65

JXD6

400

65

35

25

HJD6

400

100

65

35

LXD6

600

65

35

25

HLD6

600

100

65

35

LMXD6

800

65

50

25

HLMD6

800

100

65

50

MD6

800

65

50

25

HMD6

800

100

65

50

ND6

1200

65

50

25

HND6

1200

100

65

50

Note: For additional ratings and applications consult your local Murray Sales Office. Accessories - see page CB-23.

Discount Schedule "M"