Best HVAC Maintenance and Control Practices

Report 3 Downloads 160 Views
Best HVAC Maintenance and Control Practices October 30, 2009 Ryan Stroupe

Training Objectives •

9:00 Best HVAC Maintenance and Control Practices, – – – – –

• •

10:30 Break 10:45 Best HVAC Maintenance and Control Practices, continued – – – – –



Best practice goals for HVAC Retrofits for energy efficiency Optimal control strategies Understanding sequences of operation Questions

Maintenance opportunities Diagnostics and monitoring devices Mystery graphs Role of building commissioning Questions

12:00 Lunch

1

Where Does the Energy Go? • 2005 Building Energy Outlook-USDOE • Annual Energy Outlook 2003-USDOE • BOMA Data

2003 U.S. Commercial Buildings

http://www.boma.org/

• PG&E Commercial Building Surveys

http://www.pge.com/biz/energy_tools_resources/ building_survey/index.html

CA-Electric Usage by End Use

2

CA-Natural Gas Usage by End Use

Load Profiles, Peak Demand and Rates P a r t i a l

60000

P e a k

P e a k

P a r t i a l

P e a k

Megawatts

50000

40000

30000

20000

10000

0

12:00 AM

6:00 AM

12:00 PM

6:00 PM

12:00 AM

Consider that utility rates vary by time of day and year

3

End Use Loads on 2003 Peak Day Exterior Lighting 1%

Domestic Hot Water 1% Office Equipment 2% Refrigeration 5% Ventilation 10%

Cooking 1%

Air Conditioning 32%

Other 18%

Interior Lighting 30%

3 Hour Peak

End Use Loads for California Commercial Sector on 2003 Peak Day

Gigawatts/Hour

Energy Intensity by Building Type Grocery stores and food service have higher end use intensities (kWh/sf) than any other common commercial building type.

Source: 1999 Commercial Building Energy Consumption Survey (CBECS), U.S. DOE, www.eia.doe.gov.

4

Small Office Miscellaneous

Air Compressors 1%

Motors 1%

0.1%

Heating 2%

Miscellaneous 7%

0.1%

Process 0.4%

Water Heating 6.9%

Cooling 18%

Exterior Lighting 5%

Cooking

Office Equipment 21%

Ventilation 11%

Water Heating 1%

Heating

Cooking 0%

92.5%

Refrigeration 4% Interior Lighting 29%

Electric

Natural Gas

Grocery Store Miscellaneous 3% Exterior Lighting 2% Office Equipment

Motors 0%

1%

Cooling 5%

Ventilation 6% Water Heating 0% Cooking

Interior Lighting

5%

20%

Cooking 28% Heating 42%

Water Heating 30%

Refrigeration

Electric

58%

Natural Gas

5

School Air Compressors Miscellaneous 3.8%

0.1% Motors 1.5%

Heating 1.6%

Cooking

Cooling

6%

12.2%

Exterior Lighting

Miscellaneous 0%

10.7%

Office Equipment 5.3%

Ventilation

Water Heating

13.5%

24%

Water Heating 0.9%

Heating

Cooking

Cooling

3.2%

1%

69%

Refrigeration 7.0% Interior Lighting 40.1%

Electric

Natural Gas

Approach to Efficient HVAC • First step is energy conservation through reduced building loads (envelope and interior) • Second step is through selection of efficient equipment to meet loads • Third step is operating equipment and systems only as required to meet intents • Fourth step is maintenance to maintain efficiency

6

Building Loads • Heat Losses – Conduction at envelope – Infiltration at envelope

• Heat Gains – – – – – –

Conduction at envelope Infiltration at envelope Solar gain through glass Lighting Equipment People

• Units: BTU/hr

Load Control

7

Cool Roofing Desired attributes – High solar reflectance – High far IR emissivity

Donald watson - editor. Time-saver standards for Architectural Design Data. McGraw Hill, 1997. Pg. B-254.

Images courtesy of NREL Craig Miller Productions and DOE

Cooling Efficiency • Capacity = Tons 1 Ton of Cooling = 12,000 BTU/hr Note: this is a rate – not a quantity • COP – Coefficient of Performance = (What you get) / (What you pay for) Higher COP is better • kW/ton kW input / (Tons of refrigeration out) Lower kW/ton is better • Energy Efficiency Ratio (EER) (BTU/hr Cooling Out) / (Watts In) Higher EER is better • Seasonal Energy Efficiency Ratio (SEER) (BTU/hr Cooling Out) / (Watts In)

8

Heating Efficiency • Capacity = BTU/hr • Annual Fuel Utilization Efficiency (AFUE) Used for boilers and furnaces BTU-out/BTU-in Higher AFUE is better • Heating Season Performance Factor (HSPF) Seasonal heat output of heat pump in BTU / total electric energy input Higher HSPF is better • Energy Factor (EF) Used for water heaters Hot water produced per unit of fuel consumed Higher EF is better

Motor, Fan and Pump Efficiency • Output/Input • Measured as a percentage • Motor – Input electrical power – Output is mechanical power

• Fan – Input is mechanical power – Output is airflow (CFM) and pressure (in H2O)

• Pump

– Input is mechanical power – Output is liquid flow (GPM) and pressure (ft H2O)

9

CA Title 20 Standards for Single Phase Air-Cooled Air Conditioners with Cooling Capacity Less than 65,000 Btu per Hour and Single Phase AirSource Heat Pumps with Cooling Capacity Less than 65,000 Btu per Hour, Not Subject to EPAct

What to specify: Rooftop / Split

© 2008 Consortium for Energy Efficiency, Inc. All rights reserved. www.cee1.org

Energy Audits

10

Mechanical System Efficiency 25

Energy Efficiency Ratio

20

15

10

5

0 C e n tri fu gal & S cre w C h i l l e rs

Pack age d AC

Ai r C ool e d He at Pu m p

Re ci procati n g C h i l l e rs

Grou n dsou rce h e at pu m ps

Data from Global Green USA 2001

Randall Thomas. Environmental Design, An Introduction for Architects and Engineers. E&FN Spon, 1996. Pg. 112.

Chiller Options for Efficiency • Look at chilled water system as a whole, not as individual parts • High Efficiency = low kW/ton • Ability to run with low condenser water temperatures • VFDs to modulate at part loads • “Free cooling” economizer operation (turns off compressor & uses only condenser water to cool chilled water) www.commercial.carrier.com

2007

22

11

Chilled Water System EEMs • Pump Scheduling & Proper Interlocking • Variable Flow Chilled Water Distribution • Variable Speed Cooling Tower Fans • Optimized Condenser Water Setpoint • Variable Flow Condenser Water Distribution • Chilled Water Temperature Resets • Drive-line retrofit • Replacement • Lots, lots, more!!!

2007

23

Chillers - Replacement • Longish payback • Eliminates refrigerant phase-out issues • If replacement is needed, very costeffective to spec VSD • Match chiller to actual load not design load (especially in multiple chiller plant) 2007

24

12

Cooling Towers • Run fans in parallel (VFDs) • Reduce condenser water setpoint (but perhaps not all the way) • Install water-side economizer (if oversized) • Regular Maintenance

2007

25

Water Side Economizer • Utilize “free” cooling during cold weather • Heat exchanger transfers heat directly from chilled water to condenser water • Eliminates chiller power • Can extend use by – Lower condenser water setpoint (i.e. running tower harder) – Running with higher chilled water temperature

13

Rooftop Equipment Identification • Packaged Unit – All components contained in on location – Ventilation is introduced through the unit – Heating is supplied by a gas furnace, heat pump, electric resistance or a hot water coil

• Split-System – Compressor Component Only – No ventilation provided by unit – Only heating is heat pump http://www.carrier.com

2007

27

Energy Efficiency Measures (EEMs) • Retrofits

– Evaporative Cooling – High Efficiency Units – VFD’s

• Controls – – – –

Scheduling / reduce operating hours Programmable thermostats Economizer operation Demand control ventilation

www.carrier.com

• Demand Response • Operations

– Reduce cooling loads – Keep units maintained

2007

28

14

High Efficiency Replacements • Package unit replacement isn’t generally cost effective on energy savings alone • So where are the opportunities? – Older units – Early retirement – New additions

• How do we promote it? – Comfort – Reliability – Reduced O&M Costs

2007

www.trane.com

Energy Audits

29

What to specify: Heat pumps • For larger units, use Consortium for Energy Efficiency (CEE) guidelines (www.cee1.org) • Specify Tier 2 or 3 Efficiency level

www.trane.com

2007

30

15

Ground-source Heat Pumps

Geothermal Heat Pump Consortium, Inc. http://geoexchange.us/illustrations/graphics.htm

• AKA

• • • • •

– Geothermal – Ground-water source – Geo-exchange

Uses earth/groundwater for heat sink Cooling mode: rejects heat to ground Heating mode: absorbs heat from ground Efficiency depends ground temperatures Size ranges from residential to large commercial systems • Best applicability: Climates where ground temperatures offer significantly better efficiency over air source • Title 20 Sets minimum standards by size 2007

31

Ground Source Heat Pumps

16

Evaporative Cooling

Evaporative Cooling/Pre-Cooling • Cools air via evaporation of water • Direct evaporative cooling increases humidity • Indirect evaporative cooling is less effective, but does not increase humidity • Evaporative pre-cooling reduces the temperature of air entering the condenser

http://www.muntersamerica.com/

17

Evaporative Cooling

• Direct evaporative coolers draw air through evaporative media lowering the temperature and increasing humidity • Indirect evaporative coolers use a heat exchanger to reduce the air temperature without increasing humidity

Direct Evaporative Cooler www.muntersamerica.com

2007

35

Direct Evaporative Cooling

18

Indirect/Direct Evaporative Cooling

http://www.wescorhvac.com/

Evaporative Pre-cooler Details

19

Evaporative Pre-Cooling D inin g U nit 1 E va porative C ond en s er P e rform a nc e

85

Temperature exiting media (F)

80

75

70

65

60

55 55

60

65

70

75

80

85

90

95

10 0

T e m p e ra tu re e n te rin g m e d ia (F )

Evaporative Pre-Cooling D aily E n erg y U sag e fo r D in in g U n it 1 80.0

HD1-E vap Cooler

70.0

HD1

y = 1.9524x - 106.37 R 2 = 0.9762

Linear (HD1-E vap Cooler) Linear (HD1)

Daily Energy Consumption (kWh)

60.0

50.0 y = 1.4888x - 75.758 R 2 = 0.9542 40.0

30.0

20.0

10.0

0.0 65.0

70.0

75.0

80.0

85.0

90.0

95.0

Ave ra ge Am bie nt Dry Bulb Te m pe ra ture be tw e e n 6 a .m . a nd m idnight

2007

40

20

Furnaces

JMK

• Furnaces heat air through heat exchange with combustion gases • Rating is Annual Fuel Utilization Efficiency or AFUE • Typical ratings from 80% to 96% AFUE • Condensing Furnaces achieve higher end of efficiencies en.wikipedia.org/wiki/Furnace

Boilers • Types – Hot water (Will have circulation pump) – Steam: Low, Medium & High Pressure (May have condensate return pump) – Atmospheric and forced draft – Fire-tube and water-tube

• Nameplate – Input/Output (MMBtu) – Combustion fan information – Pump size (for boilers with integrated pump) – National Board number

http://www.raypak.com/

21

Slide 41 JMK1

This work is in the public domain in the United States because it is a work of the United States Federal Government under the terms of Title 17, Chapter 1, Section 105 of the US Code. Jim Kelsey, 1/30/2007

Automatic Stack Damper

Instantaneous DHW Implementation • Pitfalls – Spendy! – Requires greater capacity (Btuh) to meet same load

• Savings – Range of 5% to 20% (depends on volume, age of existing) – Find by comparing energy factor

• Non-energy Benefits – Never run out of hot water – Less space/weight required – May help reduce time to get hot water

www.noritz.com

22

Motor Efficiencies (Premium Efficiency) • Compile Inventory of

motors • “High Efficiency” and Premium Efficiency are not equal • Stock premium efficient motors if possible • Take advantage of Incentives and Rebates

Standard (EPAct 1992) and Premium Efficiency Motor Ratings 1200 RPM HP

1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200

EPACT (Standard)

80.0% 84.0% 85.5% 86.5% 87.5% 88.5% 90.2% 90.2% 91.0% 91.7% 92.4% 93.0% 93.0% 93.6% 93.6% 94.1% 94.1% 94.5% 94.5%

NEMA Premium Efficiency

82.5% 86.5% 87.5% 88.5% 89.5% 90.2% 91.7% 91.7% 92.4% 93.0% 93.6% 94.1% 94.1% 94.5% 94.5% 95.0% 95.0% 95.4% 95.4%

Open Drip Proof (ODP) 1800 RPM NEMA Premium Efficiency

EPACT (Standard)

82.5% 84.0% 84.0% 86.5% 87.5% 88.5% 89.5% 91.0% 91.0% 91.7% 92.4% 93.0% 93.0% 93.6% 94.1% 94.1% 94.5% 95.0% 95.0%

3600 RPM

EPACT (Standard)

NEMA Premium Efficiency

85.5% n/a 86.5% 82.5% 86.5% 84.0% 89.5% 84.0% 89.5% 85.5% 91.0% 87.5% 91.7% 88.5% 93.0% 89.5% 93.0% 90.2% 93.6% 91.0% 94.1% 91.0% 94.1% 91.7% 94.5% 92.4% 95.0% 93.0% 95.0% 93.0% 95.4% 93.0% 95.4% 93.6% 95.8% 93.6% 95.8% 94.5%

77.0% 84.0% 85.5% 85.5% 86.5% 88.5% 89.5% 90.2% 91.0% 91.7% 91.7% 92.4% 93.0% 93.6% 93.6% 93.6% 94.1% 94.1% 95.0%

Relative Motor Efficiencies By Size ODP Motor Efficiencies 100.0%

Efficiency

95.0% 90.0% 85.0% 80.0% 75.0% 0

50

100

150

200

250

HP Existing

EPACT

NEMA Premium Efficiency

TEFC Motor Efficiencies 100.0% 95.0% Efficiency

• Motor Efficiencies tend to increase with motor size • EPACT is the Energy Policy Act of 1992 which established what we now consider “Standard” efficiency motors • National Electrical Manufacturers Association (NEMA) premium efficiency motors tend to be 1 to 2 percent higher than EPACT motor efficiencies

90.0% 85.0% 80.0% 75.0% 0

50

100

150

200

250

HP Existing

EPACT

NEMA Premium Efficiency

23

Benefits of Efficient Motors • Save energy, save $ – Benefit improves with higher utility rates

• Save demand, save $ – Benefit improves with higher demand costs

• Higher power factors, save $ – Benefit improves with PF charge at facilities with PF < 0.85

• Runs cooler, save energy, save $ – Benefit improves at facilities that are cooled

• Withstand voltage fluctuations and harmonics – Benefit important at facilities with old infrastructure – Benefit important at facilities with non-sinusoidal load types

• Operate quietly – Benefit important at most facilities Efficient Motors: Selection and Application Considerations, Consortium for Energy Efficiency, 1999

Efficient Evaporator Fan Motors

GE Industrial Systems

• New motors are “electrically commutated” a.k.a. “ECM” • Old types are shaded pole or permanent split capacitor (PSC) types • Applications: refrigerated cases, walk-in coolers and freezers

www.GEindustrial.com/ecm

24

Efficient Evaporator Fan Motors

VFD’s for Fans • Many systems use variable flow air distribution • Fan power laws dictate that power is roughly proportional to the flow rate cubed • VFD quality/reliability have improved greatly over time • VFD costs have dropped significantly with wider adoption • Now required by code for many applications in new construction

www.abb.com

2007

50

25

Why fans with VFD’s Save Energy

This relationships between fan energy and fan flow are taken from the California Energy Commission Guide to Preparing Feasibility Studies and the 1998 Nonresidential ACM Approval Manual. Note that a typical system curve, DOE2 default, is assumed and these relationships are not applicable to all systems.

2007

51

Control Measures • On/off • Setbacks • Demand Control Ventilation • Lock-outs • Resets • Economizers

2007

52

26

HVAC Controls • Basic control is the thermostat • For complex systems, monitor many control points: air temperature, pressure, fan speeds, etc. • Central computer control is called Building Management System • HVAC without controls is like lighting without switches

The Opportunity: Controls General Concepts • Controls are generally the most cost effective of EEMs • Whatever doesn’t have controls probably needs it • Controls reduce opportunity for human “enhancements” • Limit hours of operation • Use to maximize system efficiencies 2007

54

27

Scheduling

• Mechanical Time Clocks • Consider Twist Timers to reduce usage during off-hours

www.tork.com

www.tork.com

• Some have seasonal / astronomical timers and/or multiple channels 2007

55

Setbacks and Programmable Thermostats • Install Programmable Thermostats on all units

www.white-rodgers.com

2007

56

28

Setback Thermostats / Scheduling • Pitfalls – Need to be set correctly, not in “hold” mode – Persistence: document with a system manual how things are intended to work

• Savings – Range widely depending on occupancy and use. Typical is 5% to 50%. – Demand savings are minimal

• Non-Energy Benefits – Reduced wear on equipment

www.white-rodgers.com

Energy Audits

57

Web-enabled Thermostats • Web-based now available • About $250 to $400 each • Include ability to monitor remotely

www.proliphixstore.com

2007

58

29

Space Temperature Setbacks Room tem perature

85

80

75

70

65

60

55

50 8/29

8/30

8/31

9/1

9/2

9/3

9/4

9/5

9/6

9/7

9/8

9/9

9/10

Controls: Lockouts • A lockout is turning a piece of equipment off when a control condition is met • Example lockouts: – Chiller lockout based on outside air temp (and associated CHW pumps, CW pumps) – Boiler lockout based on outside air temp (and associated HHW pumps)

• Lockouts are simple, cheap, effective

30

Controls: Resets A reset is creating a variable setpoint control based on a monitored condition HHW OAT Reset 200

OAT

HHW

65

140

50

180

HHW Setpoint [°F]

190 180 170

OAT = Outside Air Temperature

160

HHW = Heating Hot Water Temperature

150 140 130 120 20

40

60

80

OAT [°F]

Economizers • The economizer cycle refers to using controls and dampers to make use of outside air for “free” cooling when it makes sense • Controls used to bring in outside air instead of return air • An “economizer” is generally not a single piece of equipment, although people may refer to it as such Return Air Exhaust Air

Outside Air

COLD

HOT

62

31

Air-Side Economizer • Damper Control • 100% Free Cooling (ex: OA

P

NO

SR

C NO

P

RA

C

SR

AF=0, NC=C

3-13 Psi

UNOCC, NC=C

SP O O R

28 OA

NO NC

O

OH CALC O I y=mx+b

OA

0%

OA>RAT or OAE>28, NO=C P

I IF >

TC

NC

SP O

EA

RA RESET

20

CO2

5

800

1000

45

Develop a Sequence of Operation for Fan Coil Unit

Operations & Maintenance Assuring equipment is operating properly

46

www.energy.ca.gov/pier PIER Buildings Program Design Guide: Big Savings on Small HVAC Systems

Small HVAC: Frequent Issues

93

Operations and Maintenance • • • • • •

Commissioning: Check Set points, Schedules and Resets Check for controls overrides (e.g. bypassed VFDs) Filter Changes for IAQ Check Fixed Damper and Minimum Damper Positions Adjust/tighten/replace belts Lubricate rotary equipment

47

Operations and Maintenance (cont.) • • • • • • •

Clean condenser coils Clean evaporator coils Insulate suction lines Check refrigerant charge Check thermostat/sensor calibration Insulate/seal ductwork Eliminate flex duct

2007

95

O&M Issues

48

What are Dataloggers? • What they do – Measure – Record

• What they include – – – – – – – – – –

Receive signal from sensor or transducer Analog-to-digital converter Data sampling rate Data storage rate Memory (stores readings) Internal clock Programming and data retrieval software Computer interface Microprocessor Power supply

Honeywell Service Assistant Faults detected: 1. 2. 3. 4. 5.

Low pumping efficiency High side heat transfer problem Low side heat transfer problem Fan speed too high Restricted refrigerant flow through the small orifice 6. Too little charge 7. Too much charge 8. Charge contaminated with non-condensables

49

Drywell Bath • Used for in-situ sensor calibration • Temperature maintained for calibration): 14° to 251° F (± 0.9° F) • Kit includes 1/16", 1/4", 3/16" and 1/2" removable inserts

Measuring Airflow • • • • • •

Anemometers DP sensors Pitot tubes Velgrid Flow hoods Duct blasters

50

Gas Efficiencies • Thermal: Steady State measure of the units ability to transfer heat to the water. • Combustion: Efficiency of the fuel burning process. Depends on fuel mix as measured with a combustion analyzer. • AFUE: Annual Fuel Utilization Efficiency. Similar to a SEER, rated for average seasonal conditions. • Standby Loss: A measure of the relative amount of heat that the unit will lose to the environment

Efficiency as Make-up Air Varies

http://www.engineeringtoolbox.com/boiler-combustion-efficiency-d_271.html

51

Mystery Graph #1 75

F degrees

70

65

60

55 6/17/00 0:00

6/17/00 12:00

6/18/00 0:00

The graph above is showing temperature. It represents: 1. interior temperature in an enclosed office building 2. outside air temperature over a year 3. outside air temperature over a day 4. the temperature at a light fixture 5. chilled water supply temperature

Mystery Graph #2 Mystery Graph 2 100

Three inter-related parameters

90

80

70

60

50

40 08/12/04 12:00 AM

08/12/04 03:00 AM

08/12/04 06:00 AM

08/12/04 09:00 AM

08/12/04 12:00 PM

08/12/04 03:00 PM

08/12/04 06:00 PM

08/12/04 09:00 PM

08/13/04 12:00 AM

Date

The graph at right shows three inter-related parameters. They are… 1. outside air, mixed air and supply air temperatures at an air handler 2. annual electricity, natural gas and water use 3. space temperature, air flow and damper position for a working VAV box 4. temperature, relative humidity and dew point of air 5. chilled water flow, chilled water supply temperature and condenser water supply temperature for an optimized chiller

52

Mystery Graph #3 The three variables illustrated in the graph depicted here are?

a. outside air, mixed air and return air temperatures at an air handler with an economizer b. daily electricity, natural gas and water use. c. space temperature, air flow and damper position for a working VAV box.

d. temperature, relative humidity and dew point of an air volume. e. chilled water flow, chilled water supply temperature and condenser water supply temperature for an optimized chiller.

Mystery Graph #4 Mystery Graph

120

Temperature, °F

110

100

90

80

70

60 5/20/05 12:00 PM

5/21/05 12:00 AM

5/21/05 12:00 PM

5/22/05 12:00 AM

5/22/05 12:00 PM

5/23/05 12:00 AM

5/23/05 12:00 PM

5/24/05 12:00 AM

Date and time

What does the temperature data above indicate? 1. temperature in a space with evening setbacks 2. the temperature at a chair indicating occupancy 3. condenser water temperature at a chip fabrication facility (with night shutdown shown) 4. the temperature in a refrigerated warehouse with a regular evening stocking crew 5. the scheduled operation of a motor

53

140

Mystery Graph #5

120

100

80

60

40

20

0

12:00 AM

6:00 AM

12:00 PM

6:00 PM

12:00 AM

What does the data above represent? 1. percent speed for a VFD-controlled fan in a retail space 2. the power draw of a chiller connected to thermal storage 3. solar radiation in San Francisco on a foggy day 4. an erratic control valve for chilled water flow in an office building 5. the lighting energy use at a quickie-mart

Mystery Graph 6 1200 1000

ppm

800

The data shown to the right is an indication of which condition?

600 400 200 0 6/28/02 12:00 AM

a. Total dissolved solids in condenser water for a cooling tower. b. Volatile organic compounds (VOC) levels during construction of an office building.

6/28/02 12:00 PM

6/29/02 12:00 AM

6/29/02 12:00 PM

6/30/02 12:00 AM

6/30/02 12:00 PM

7/1/02 12:00 AM

c. CO levels in a parking garage. d. CO2 levels in the open office area of a law office. e. CO2 levels in a movie theater.

54

Mystery Issue #7

What obvious visible indicator is shown in the image? 1. a throttled valve on the discharge of the pump 2. a strainer in need of cleaning 3. a section of pipe with inadequate insulation 4. a valve missing an actuator 5. a missing pressure gauge

What Is Building Commissioning? Commissioning is a quality assurance strategy. Commissioning is a systematic process of ensuring that all building systems perform interactively according to the contract documents, the design intent and the building owner’s operational needs.

55

Why Commission? • • • • • • • • • • •

Owners do not typically receive fully functional building systems Owners face increasing numbers of performance problems Buildings have more complex life safety, security, communication, and comfort control systems Building systems are becoming increasingly specialized and integrated Many problems are masked by energy-wasting process Multiple trades and contracts are involved (fragmentation) Conflicting loyalties and objectives Increasing costs (change orders, call backs) Emphasis on fast track Design fees do not reflect reality Requirements – LEED, CHPS, Title 24

Commissioning is Quality Assurance • A coordination process to optimize building performance (comfort, reliability, safety, energy) • Articulating/verifying energy-related design intent • Construction observation; warranty enforcement • Controlling first cost • Training operators • Enhancing safety and risk management • Creating more cohesion among team members

56

A Common Industry Perspective; Commissioning; A Bandage for a Broken Process

An Emergency Response • Treating the wound • Add-on process • Last-ditch effort – Resurrect quality – Identify deficiencies – Force accountability

Images courtesy www.talkingproud.us

Building problems (a.k.a. “deficiencies”) are pervasive – These include Design flaws; Construction defects;

Malfunctioning equipment; Deferred maintenance

EXISTING BUILDINGS

NEW CONSTRUCTION

Simultaneous heating+cooling

Oversized equipment

Mis-sized valves/dampers, chillers

Unnecessary components (valves)

Low-quality or clogged filters

Construction debris blocking ventilation

VFD or economizer overridden/stuck

Specified equipment not installed

Dumb alarms (false; ignored)

Wrong set points or control sequences

Circuitous duct or piping runs

Wrong sensors (inappropriate sensitivity)

Bad or inaccurate sensors

Improper startup (e.g. daylighting sensors)

Supply fans running; return not (or visa-versa)

57

First-cost savings alone can pay for cost of Cx!

Evan Mills: The Cost-Effectiveness of Commercial Buildings Commissioning, 2004

Payback Times: New Construction

Median Payback Time = 4.8 years

Payback times not always attractive (if NEBs excluded)

58

RCX Payback Times for Existing Buildings Excluding NEI’s

Median Payback Time = 0.7 years

Attractive payback times across a range of Cx costs

Cx Cost Outliers

Smaller bldgs tend to have higher Cx costs

Larger bldgs tend to achieve economies of scale

59

PEC: Pre and Post Commissioning Data Average Daily Electrical Consumption PG&E Pacific Energy Center 1,200

Average Daily kWh

1,000

A pril 2000 - March 2001

800

A pril 2002 - March 2003

600

A pril 2003 - March 2004 400

200

M ar ch

Fe br ua ry

Ja nu ar y

D ec em be r

O ct ob er N ov em be r

Au gu st Se pt em be r

Ju ly

Ju ne

M ay

Ap ril

0

Existing Building Cx in California (SMUD)

Avg of 8 buildings Avg of 7 buildings

Avg of 4 buildings

60

Commissioning report on site

Lab and Office 1 (1996)

N Y

Office Building 1 (1996)

N Y

Office Building 2 (1996)

N N

Office Building 3 (1996)

Y Y N

Office Buidling 4 (1994)

N

-

-

Office Building 5 (1997)

N

-

Y

Medical Facility 1 (1998)

Y

Y

Y

Medical Facility 2 (1997)

Y

Y

Y

Lab and Office 2 (1997)

N

-

Y

Lab and Office 3 (2000)

N

-

N

Occupancy sensor

Skylight louver operation

PREFUNCTIONAL TESTS

Scheduling

Sensor error or failure

Sensor placement or addition

Wiring and instrumentation

Valve modification

AIR HANDLING AND DISTRIBUTION

Piping and fitting problems

Terminal units

Space temperature control

Duct static pressure

Dessicant cooling

VFD modulation

Simultaneous heating and cooling

CENTRAL PLANT

Discharge air temperature reset

Economizer control algorithm

Hydronic control

Boiler control

DOCUMENTS

Cooling tower control

BUILDING (year commissioned)

Chiller control

Control sequences available

California

Commissioning report used

Pacific Northwest

Emergence & Persistence of Energy Savings

New Construction Persistence Research Results

Red = did not persist Blue = persisted

OTHER

61

Commissioning Benefits • • • • • • • •

Energy savings Smoother turnover from construction to occupancy Improved occupant comfort/satisfaction Reduced construction and warranty issues More complete documentation Avoided O&M costs / increased reliability Team building with all role players Brings an integration perspective to design – – – –

Minimizes design related commissioning issues Buildings are integrated, interactive assemblies An Integrated Design leads to an Integrated Project Can reduce first cost of construction

Examples from Cx Projects

62

Types of Deficiencies Discovered New (N=3300)

Existing (N=3500) Envelope 0.2% Plug loads 0.2% Lighting 5%

Facility-wide (e.g. EMCS or utility related) 10%

Facility-wide (e.g. EMCS or utility related) 4% HVAC (combined heating and cooling) 6%

Plug loads 8%

HVAC (combined heating and cooling) 15%

Cooling plant 16% Cooling plant 9%

Terminal units 6%

Lighting 16%

Heating plant 6%

Heating plant 9%

Terminal units 11%

Air handling & distribution 54%

Air handling & distribution 25%

Fixed Economizer Actuator Motor

63

Looking at Multiple Trends Why doesn’t the AHU ever shut off ?

Looks like there are not any equipment lockouts

Why is the TES system melting ice at night?

Hot Water System Evaluation & Trending HWST & Pump status with time

Pump status

HWS Temp (deg F)

Low HWS Temp on Mondays

It takes all of Monday to heat up the HW Loop

64

Commissioning Resources

Resources •

PECI



CA Commissioning Collaborative online library



LBNL cost-benefit study



Commissioning Functional Test Guide



Design Intent Tool http://ateam.lbl.gov/DesignIntent/home.html



Energy Design Resources



Pacific Energy Center Cx workshops!

http://www.peci.org http://resources.cacx.org/library/

(and spreadsheet download) http://eetd.lbl.gov/emills/PUBS/Cx-Costs-Benefits.html http://buildings.lbl.gov/hpcbs/FTG

http://energydesignresources.com

65

Energy Design Resources • Building Commissioning Guidelines • Design Briefs –Building Commissioning –Field Review –Design Review –Smart Buildings

• Commissioning Assistant Tool • www.energydesignresources.com

Public Interest Energy Research • • • • • • •

Functional Test Guide Is Commissioning Once Enough? Persistence of Benefits from New Building Commissioning Persistence of Savings Obtained from Continuous Commissioning Optimization Measures that Persist in Existing Buildings Strategies for Improving the Persistence of Commissioning Benefits www.energy.ca.gov/pier

66

California Commissioning Collaborative • Download documents from California Cx Collaborative’s Online Library • www.cacx.org/library

ASHRAE and Green This nearly 200-page book offers essential reference and guidance to HVAC&R system designers involved in green or sustainable building design. The GreenGuide is a step-by-step manual for the entire building lifecycle, from the very earliest stages of a green building design project and through to the resulting structure’s construction, operation, maintenance, and eventual demolition. [Source: ASHRAE]

67

TLL homepage: www.pge.com/pec/tll

On-line Tool Request Form • Method for all loans • Information requested – About borrower – About project

• Sends automatic email to TLL staff • Typical response is within 24 hours • Tools can be shipped across California

68

Sign-out Sheet • To borrow tools – Business card – Signature

• Agree

– To return tools – That borrower is liable for damages to equipment and/or customer facility – Use licensed electrician for installing meters on equipment over 12v – Software cannot be copied for use after loan

On-line Catalog

69

Application Notes

Universal Translator (utonline.org) • Data Management Tool – – – – – –

Trend and logger data Re-sampling Time corrections Slope and offset corrections Calculated channels Schedule and data filters

– – – – – –

Economizer Run time of equipment Lighting controls Plug load controllers Psychrometrics Set-point analysis

• Data Analysis Tool

70

Universal Translator Interface

TLL Measurement Equipment • • • • • • • • • • • •

Temperature Humidity Electrical power (kW) Run time (EMF) Gas use (therms) CO2 CO Liquid flow Pressure (high) Air flow Pressure (low) Refrigerant charge

71

Tool Lending Library • Tool loaned for FREE • Intended for EE projects • Can be used for building diagnostics, sensor calibration or commissioning • Over 5000 tools in library • Support information at: www.pge.com/pec

Thank You, Ryan [email protected]

72

Mystery 1 The three variables illustrated in the graph depicted here are?

a. outside air, mixed air and return air temperatures at an air handler with an economizer b. daily electricity, natural gas and water use. c. space temperature, air flow and damper position for a working VAV box.

c. temperature, relative humidity and dew point of an air volume. d. chilled water flow, chilled water supply temperature and condenser water supply temperature for an optimized chiller.

73

Mixed is warmer than return, but much cooler than outside when outside temp is above return.

Mystery 1

The three variables illustrated in the graph depicted here are?

Mixed and return track when air handler is off.

Mixed tracks outside when the outside temp is below return.

a. outside air, mixed air and return c. temperature, relative air temperatures at an air humidity and dew point of an handler with an economizer air volume. b. daily electricity, natural gas and d. chilled water flow, chilled water use. water supply temperature and condenser water supply c. space temperature, air flow and temperature for an optimized damper position for a working chiller. VAV box.

1200

Mystery 2

1000

ppm

800

The data shown to the right is an indication of which condition?

600 400 200 0 6/28/02 12:00 AM

6/28/02 12:00 PM

a. Total dissolved solids in condenser water for a cooling tower. b. Volatile organic compounds (VOC) levels during construction of an office building.

6/29/02 12:00 AM

6/29/02 12:00 PM

6/30/02 12:00 AM

6/30/02 12:00 PM

7/1/02 12:00 AM

c. CO levels in a parking garage. d. CO2 levels in the open office area of a law office. e. CO2 levels in a movie theater. .

74

1200

The movie schedule is apparent in CO2 spikes.

Mystery 2

1000

The data shown to the right is an indication of which condition?

ppm

800 600 400

The night shut-down of the air handler causes the CO2 levels to dissipate slowly.

200 0 6/28/02 12:00 AM

6/28/02 12:00 PM

a. Total dissolved solids in condenser water for a cooling tower. b. Volatile organic compounds (VOC) levels during construction of an office building.

6/29/02 12:00 AM

6/29/02 12:00 PM

6/30/02 12:00 AM

6/30/02 12:00 PM

7/1/02 12:00 AM

c. CO levels in a parking garage. d. CO2 levels in the open office area of a law office. e. CO2 levels in a movie theater. .

Underfloor Air Distribution

75

Radiant Heating

Radiant Heating

76

Radiant Heating

Demand Response: HVAC Measures • Setback temperatures

• Fan speed limiting • Pre-cooling • Production scheduling

12:00 AM

10:00 PM

8:00 PM

6:00 PM

4:00 PM

2:00 PM

12:00 PM

8:00 AM

10:00 AM

6:00 AM

4:00 AM

2:00 AM

12:00 AM

kW

– Zone temps – CHW temps – Supply air temps

77

Thermal Storage Partial Peak

140

Peak

Partial Peak

120

kW

100 80 kW w/ thermal storage

60 kW w/o thermal storage

40 20 0

12:00 AM

6:00 AM

12:00 PM

6:00 PM

12:00 AM

Full Storage vs. Demand Limiting

78

Thermal Storage Issues • Peak demand reduction (saves $) • More efficient operation at night • Smaller electrical service required • Requires space • Requires knowledgeable facility engineers • Efficiency losses as cooling is stored and retrieved

Alternative Approach: NightBreeze System • Summer: If house is warm and it’s cool outside, system brings outside air • Winter: Heats the house using heat from the water heater or from a conventional gas furnace and also introduces outside air to provide adequate ventilation. • Primarily Residential, but some small commercial application

2007

http://www.davisenergy.com/technologies/nightbreeze.php

158

79

Night Ventilation Cooling

Night Ventilation Cooling Actual Performance Conventional A/C vs NightVent Cooled House Performace

100

12 Outdoor Temperature NightVent Indoor Temp A/C Indoor Temp NightVent Power A/C Power

10

80

8

70

6

60

4

50

2

40

0 0:00

6:00

12:00

Power (kW)

Temperature (deg F)

90

18:00

Hour

80