CURRENT MONITORING LOAD TRENDING WITH 0-5VDC OUTPUT

9EAR

7ARRANTY

H722HC

Current Transducers: 0-5VDC Analog Output The Hawkeye 722, 822, and 922 provide accurate load trending information with a proportional 0-5VDC output signal. Slide-switches provide easy field selection of monitored amperage range without jumpers (available on most models).

APPLICATIONS  Load trending  Motor control High current monitoring in a solid-core housing

 Positive proof of flow

EXAMPLE LINEAR OUTPUT

H722LC

Scale software as shown

Low current monitoring in a solid-core housing

SENSOR OUTPUT

5 VDC

H822

0 VDC

0A

Self-powered analog current sensor simplifies installation  No external power required for sensor...eliminate power supplies  Self-gripping split-core for fast retrofit installation... no need to remove conductor (H922)  Economical solid-core models feature adjustable bracket for easy alignment  No jumpers on unit...reduces installation error Selectable factory calibrated ranges for increased flexibility and resolution  Some models available with three fieldselectable ranges per unit...fewer versions to choose from, stock, and install  Removable mounting bracket for installation flexibility  Bracket on H922 can be installed in three different configurations...added flexibility  100% solid state, no moving parts to fail  5-year limited warranty

Selected Range* SENSED AMPS *Factory calibrated ranges selected with the amperage range switch

10A current monitoring in a mini solid-core housing

H822-20 Maximize Reliability Minimize Installed Cost

20A current monitoring in a mini solid-core housing H922 Series

Wide range current monitoring in a split-core housing

SPECIFICATIONS Sensor Power Insulation Class Frequency Temperature Range Humidity Range Accuracy Response Time Terminal Block Maximum Wire Size Terminal Block Torque (nominal) Agency Approvals

Induced from monitored conductor 600VAC RMS (UL), 300VAC RMS (CE) 50/60Hz nominal -15° to 60°C (5° to 140°F) 10-90% RH, non-condensing ±2% F.S. from 10% to 100% (selected range) 2 sec. 14 AWG 4 in-lbs (0.45 N-m) UL 508 open device listing CE:EN61010-1:2001-2, CAT III, deg. 2, basic insulation

For applications requiring double or reinforced insulation, please contact the factory

42

800.354.8556

503.598.4564

www.veris.com

©2008 Veris Industries

CURRENT MONITORING DIMENSIONAL DRAWINGS H722LC/H722HC

H822/H822-20

Removable/Adjustable Mounting Bracket

Removable/Adjustable Mounting Bracket 0.9" (23 mm)

ø 0.7" (18 mm)

0.9" (23 mm)

2.8" (71 mm)

0.7" Dia (19 mm)

*

3.0" (75 mm)

1.7 (43 mm)

0.4” x 0.2” Slot (x2)

*

2.8" (68 mm) 1.1" * (27 mm)

1.1" (27 mm)

2.3" (58 mm)

0.2” x 0.15” slot (2x)

*

3.8" (95 mm) 4.2" (106 mm)

H922 Removable Mounting Bracket 1.0” (25 mm) 1.1” (26 mm)

0.8” (21 mm)

APPLICATION/WIRING EXAMPLE

Bracket can be mounted on either side for added installation flexibility.

Monitoring Fan /Pump Motors for Positive Proof of Flow

* (793.1” mm) Self-gripping Iris

2.8” (70 mm)

1.4” (36 mm)

Ø = 0.3” (8 mm)

CONTACTOR CONTROLLER

*

Analog Input

2.5” (64 mm)

0-5 VDC

3.0” (76 mm)

* Terminal block may extend up to 1/8”; slide switch may extend up to 1/4” over the height dimensions shown.

MOTOR

ORDERING INFORMATION MODEL

AMPERAGE RANGE

H722LC H722HC H822 H822-20 H922

0 - 10/20/40A 0 - 50/100/200A 0 - 10A 0 - 20A 0 - 30/60/120A

H922030A H922060A H922120A

0 - 30A 0 - 60A 0 - 120A

SENSOR OUTPUT HOUSING

UL

CE

Solid-Core Solid-Core Solid-Core Solid-Core Split-Core

n

n

n

n

0 - 5VDC

Split-Core Split-Core Split-Core 4

Fan or Pump

n n n

n n4 n4 n4

Products provide reinforced insulation and 600VAC RMS insulation class.